| 2007-10-25 11:42:30 | |
| | |
| | |
| | |
| | *** DENIED *** |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS WHICH STATE THE RELEVANT |
| | CODES IN DESIGN WHICH ARE CURRENTLY ADOPTED BY THE |
| | STATE. THE FOLLOWING IS WHAT IS NEEDED FOR ELECTRICAL |
| | REVIEW. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE ON THE COMPLETE SCOPE OF |
| | WORK SHOWN ON PLANS IS REQUIRED TO MEET FBC 108.3. THIS |
| | VALUE IS TO INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, |
| | DESIGN COST ETC. (EVEN IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. |
| | VALUE FOR BUILDING AND ELECTRICAL IS LOW AND ONE COULD |
| | BE ASSESSED USING ADOPTED STANDARDS BY THE FBC. PLEASE |
| | REVISE AND ADJUST. |
| | |
| | 3) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH |
| | THE SUBMITTED PANEL SCHEDULES. PLEASE BE SURE THE PANEL |
| | DESIGNATIONS ARE THE SAME. |
| | PLEASE SEE FOR EXAMPLE: CIRCUIT P-P-20 ON PLANS IS |
| | SHOWN AS A SPARE 2-POLE 30AMP CIRCUIT ON PANEL *P*> |
| | PLEASE COORDINATE ALL. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 408.4 |
| | |
| | 4) NOTE: PLEASE SEE FBC CHAPTER 13 AND SUBMIT LIGHTING |
| | POWER DENSITY CALCULATIONS AS STATED IN 13-415.2 FOR |
| | LIGHTING PERFORMANCE CALCULATIONS. |
| | PLEASE BE SURE TO SEE FBC 13-415.2.ABC.1.2 FOR TRACK |
| | LIGHTING CALCULATIONS AND MINIMUM VA TO BE USED FOR |
| | PERFORMANCE CALCULATIONS. |
| | |
| | 5) NOTE: PLEASE SHOW LIGHTING CONTROL REQUIREMENTS PER |
| | 13-415.1.ABC.1.2. |
| | PLEASE ALSO SEE 13-415.1.ABC.1.1. |
| | |
| | 6) NOTE: PLEASE SEE 600.5 AS THE REQUIRED SIGN CIRCUIT |
| | SHALL BE DEDICATED AND MAY NOT FEED OTHER ITEMS SUCH AS |
| | GENERAL RECEPTACLES AS SHOWN ON PLANS. |
| | PLEASE ALSO SEE THAT THE MINIMUM VA TO BE FIGURED FOR |
| | CIRCUIT INTO THE LOAD CALCULATIONS IS TO BE 1200VA. |
| | PLEASE ALSO SEE THAT THE SIGN CIRCUIT IS REQUIRED TO BE |
| | LOCATED AT THE FRONT ENTRANCE LOCATION. |
| | |
| | 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS ARE TO MEET |
| | NEC 220. PLEASE SEE MISSING TRACK LIGHTING CALCULATIONS |
| | PER 220.43B |
| | PLEASE SEE THAT ALL CONTINUOUS LOADS INCLUDING THE LOAD |
| | FOR SIGN CIRCUIT AS NOTED ABOVE SHALL BE FIGURED AT |
| | 125%. THIS IS LIGHTING LOADS. |
| | 215.3, 230.42 ETC. |
| | |
| | 8) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE AS SHOWN IS |
| | REQUIRED TO BE UNDER SEPARATE PERMIT(S). THESE PLANS |
| | MAY BE USED FOR REFERENCING HOWEVER WILL BE SEPARATE |
| | PERMITS. |
| | PLEASE KNOW IF A *SECURITY SYSTEM* SUCH A BURGLAR ALARM |
| | SYSTEM IS A SEPARATE LV PERMIT FROM THE OTHER LV AS |
| | SHOWN ON PLANS. (NO PLANS ARE NEEDED FOR BURGLAR |
| | ALARM. |
| | CATV< CAMERAS< PHONE MAY BE ON ONE LV PERMIT |
| | APPLICATION WITH THE EXCEPTION OF BURGLAR ALARM WHICH |
| | IS SEPARATE. |
| | THIS IS NOTED FOR INFORMATIONAL PURPOSE ONLY. |
| | |
| | 9) NOTE: PLEASE PROVIDE THE MINIMUM LIGHTING LEVELS FOR |
| | STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS PER LIFE |
| | SAFETY CODE. PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2. |
| | |
| | 10) NOTE: PLEASE SEE DISCONNECT FOR THE AHU DOES NOT |
| | MEET 440.11. |
| | PLEASE RELOCATE. |
| | |
| | 11) NOTE: PLEASE SEE 13-413.1.ABC.2.2 AND PROVIDE. |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE NEXT REVIEW. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |