Plan Review Details - Permit 07100432
Plan Review Stops For Permit 07100432
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-14 Cont ID  
Sent By mjacobs Date 2007-12-14 Time 15:46 Rev Time 0.00
Received By mjacobs Date 2007-12-14 Time 13:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-27 Cont ID  
Sent By mjacobs Date 2007-10-27 Time 11:46 Rev Time 0.00
Received By mjacobs Date 2007-10-27 Time 08:41 Sent To  
Notes
2007-10-27 11:46:48 
  
 BUILDING PLAN REVIEW
 PERMIT: 07100432
 ADD: 208 S. OLIVE AVE
 CONT: ROBBINS DEVELOPMENT GROUP
 TEL: (561) 744-4707
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 3)PROVIDE A LIFE SAFETY PLAN SHOW THE MEANS OF EGRESS
 WHICH SHALL INCLUDE THE EXIT ACCESS, THE EXIT AND THE
 EXIT DISCHARGE. THE OCCUPANT LOAD SHALL ALSO BE
 INDICATED ON THE DRAWINGS FOR THE FIRST FLOOR AND THE
 MEZZANINE. PROVIDE AN INTERIOR ELEVATION OF THE
 MEZZANINE. INDICATE IF THE BUILDING HAS A SPRINKLER
 SYSTEM.
  
 4)FBC 505.4 A MEZZANINE SHALL BE OPEN AND
 UNOBSTRUCTED TO THE ROOM IN WHICH IT IS LOCATED EXCEPT
 FOR WALLS NOT MORE THAN 42 INCHES HIGH.
  
 5)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-19 Cont ID  
Sent By dpalmer Date 2007-12-19 Time 11:31 Rev Time 0.00
Received By dpalmer Date 2007-12-19 Time 11:31 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-11 Cont ID  
Sent By dpalmer Date 2007-12-11 Time 14:12 Rev Time 0.00
Received By dpalmer Date 2007-12-11 Time 14:12 Sent To  
Notes
2007-12-11 14:12:25**** TEMPORARY DENIED ****
  
 1) NOTE: PLEASE SEE AS NOTED ON THE PREVIOUS REVIEW THE
 VALUE FOR THE APPLIED SCOPE OF WORK AS SHOWN ON PLANS
 IS LOW.
 PLEASE SEE FBC 108.3 AS THE VALUE FOR ALL EQUIPMENT,
 LABOR, MATERIALS AND DESIGN COST SHALL BE INCLUDED.
 ELECTRICAL PLANS ARE OK AND HAVE BEEN STAMPED. REVIEW
 STATUS WILL REMAIN IN A *F* STATUS UNTIL APPROPRIATE
 VALUE HAS BEEN ADJUSTED.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By dpalmer Date 2007-10-25 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2007-10-25 Time 11:42 Sent To  
Notes
2007-10-25 11:42:30 
  
  
  
 *** DENIED ***
  
 1) NOTE: PLEASE SUBMIT PLANS WHICH STATE THE RELEVANT
 CODES IN DESIGN WHICH ARE CURRENTLY ADOPTED BY THE
 STATE. THE FOLLOWING IS WHAT IS NEEDED FOR ELECTRICAL
 REVIEW.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE VALUE ON THE COMPLETE SCOPE OF
 WORK SHOWN ON PLANS IS REQUIRED TO MEET FBC 108.3. THIS
 VALUE IS TO INCLUDE ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST ETC. (EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 VALUE FOR BUILDING AND ELECTRICAL IS LOW AND ONE COULD
 BE ASSESSED USING ADOPTED STANDARDS BY THE FBC. PLEASE
 REVISE AND ADJUST.
  
 3) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 THE SUBMITTED PANEL SCHEDULES. PLEASE BE SURE THE PANEL
 DESIGNATIONS ARE THE SAME.
 PLEASE SEE FOR EXAMPLE: CIRCUIT P-P-20 ON PLANS IS
 SHOWN AS A SPARE 2-POLE 30AMP CIRCUIT ON PANEL *P*>
 PLEASE COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2
 NEC 408.4
  
 4) NOTE: PLEASE SEE FBC CHAPTER 13 AND SUBMIT LIGHTING
 POWER DENSITY CALCULATIONS AS STATED IN 13-415.2 FOR
 LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE BE SURE TO SEE FBC 13-415.2.ABC.1.2 FOR TRACK
 LIGHTING CALCULATIONS AND MINIMUM VA TO BE USED FOR
 PERFORMANCE CALCULATIONS.
  
 5) NOTE: PLEASE SHOW LIGHTING CONTROL REQUIREMENTS PER
 13-415.1.ABC.1.2.
 PLEASE ALSO SEE 13-415.1.ABC.1.1.
  
 6) NOTE: PLEASE SEE 600.5 AS THE REQUIRED SIGN CIRCUIT
 SHALL BE DEDICATED AND MAY NOT FEED OTHER ITEMS SUCH AS
 GENERAL RECEPTACLES AS SHOWN ON PLANS.
 PLEASE ALSO SEE THAT THE MINIMUM VA TO BE FIGURED FOR
 CIRCUIT INTO THE LOAD CALCULATIONS IS TO BE 1200VA.
 PLEASE ALSO SEE THAT THE SIGN CIRCUIT IS REQUIRED TO BE
 LOCATED AT THE FRONT ENTRANCE LOCATION.
  
 7) NOTE: PLEASE SEE THE LOAD CALCULATIONS ARE TO MEET
 NEC 220. PLEASE SEE MISSING TRACK LIGHTING CALCULATIONS
 PER 220.43B
 PLEASE SEE THAT ALL CONTINUOUS LOADS INCLUDING THE LOAD
 FOR SIGN CIRCUIT AS NOTED ABOVE SHALL BE FIGURED AT
 125%. THIS IS LIGHTING LOADS.
 215.3, 230.42 ETC.
  
 8) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE AS SHOWN IS
 REQUIRED TO BE UNDER SEPARATE PERMIT(S). THESE PLANS
 MAY BE USED FOR REFERENCING HOWEVER WILL BE SEPARATE
 PERMITS.
 PLEASE KNOW IF A *SECURITY SYSTEM* SUCH A BURGLAR ALARM
 SYSTEM IS A SEPARATE LV PERMIT FROM THE OTHER LV AS
 SHOWN ON PLANS. (NO PLANS ARE NEEDED FOR BURGLAR
 ALARM.
 CATV< CAMERAS< PHONE MAY BE ON ONE LV PERMIT
 APPLICATION WITH THE EXCEPTION OF BURGLAR ALARM WHICH
 IS SEPARATE.
 THIS IS NOTED FOR INFORMATIONAL PURPOSE ONLY.
  
 9) NOTE: PLEASE PROVIDE THE MINIMUM LIGHTING LEVELS FOR
 STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS PER LIFE
 SAFETY CODE. PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2.
  
 10) NOTE: PLEASE SEE DISCONNECT FOR THE AHU DOES NOT
 MEET 440.11.
 PLEASE RELOCATE.
  
 11) NOTE: PLEASE SEE 13-413.1.ABC.2.2 AND PROVIDE.
  
 ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-17 Cont ID  
Sent By mawillia Date 2007-12-17 Time 12:51 Rev Time 0.00
Received By mawillia Date 2007-12-17 Time 12:38 Sent To  
Notes
2007-12-17 12:48:30*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS LS-1 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By mawillia Date 2007-10-29 Time 12:11 Rev Time 0.00
Received By mawillia Date 2007-10-29 Time 11:37 Sent To  
Notes
2007-10-29 12:11:29*****DENIED*****
  
  
 1.PROVIDE INFORMATION AS TO THE TYPE OF OCCUPANCY AND
 THE OCCUPANT LOAD FOR THIS OCCUPANCY.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OR
 THE VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES).
  
 4.DISPLAY THE 2A:10BC FIRE EXTINGUISHER(S) ON THE
 FLOOR PLAN WHICH SATISFIES THE 75' TRAVEL DISTANCE.
  
 5.ON SHEET E-1, THERE IS AN EXIT SIGN/EMERGENCY LITE
 - FIXTURE ON THE SOUTH (REAR) WALL.WHERE IS THIS
 FIXTURE DIRECTING PERSON(S) TO EXIT THE BUILDING?
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-04 Cont ID  
Sent By adarroug Date 2007-12-04 Time 12:19 Rev Time 0.00
Received By adarroug Date 2007-12-04 Time 12:19 Sent To  
Notes
2007-12-10 09:41:40TO "BOB"#1
2007-12-04 12:19:19WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-29 Cont ID  
Sent By mawillia Date 2007-10-29 Time 12:13 Rev Time 0.00
Received By mawillia Date 2007-10-16 Time 09:51 Sent To  
Notes
2007-10-24 17:00:13TO "BOB"#4
2007-10-16 09:51:39WAITING FOR "BOB"

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-29 Cont ID  
Sent By choops Date 2007-10-29 Time 09:30 Rev Time 0.00
Received By choops Date 2007-10-29 Time 09:30 Sent To  
Notes
2007-10-29 09:30:22*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.