Plan Review Details - Permit 07100426
| Plan Review Stops For Permit 07100426 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2007-11-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-03 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-03 |
Time |
08:05 |
Sent To |
PC |
|
| Notes |
| 2007-11-03 09:40:06 | BUILDING PROVISO: | | | TO BE IN PLACE AT C.O: | | | | | | PRIVATE FBC 2004 | | | 1) 424.2.17.1 OUTDOOR SWIMMING POOLS. | | | OUTDOOR SWIMMING POOLS SHALL BE PROVIDED | | | WITH A BARRIER COMPLYING WITH | | | 424.2.17.1.1 THROUGH 424.2.17.1.14. | | | | | | 424.2.17.1.5 CHILD SAFETY BARRIER | | | ASTM D5034 100 LB TENSILE STRNGTH | | | ASTM D3787 150 LB BALL BURST | | | STRENGTH | | | 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED. | | | SPAS AND HEATED SWIMMING POOLS SHALL BE | | | EQUIPPED WITH A COVER DESIGNED TO | | | MINIMIZE HEAT LOSS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-22 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-22 |
Time |
12:10 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-10-30 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-10-30 |
Time |
13:02 |
Sent To |
B |
|
| Notes |
| 2007-10-30 13:04:12 | NOTE: THERE IS NO POOL HEATER, GAS OR ELECTRIC. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-07 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-07 |
Time |
09:30 |
Sent To |
Z |
|
| Notes |
| 2007-11-07 09:30:32 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-11-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-03 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-16 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2007-10-16 08:21:08 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-10-30 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-10-30 |
Time |
12:59 |
Sent To |
G |
|
| Notes |
| 2007-10-30 13:02:43 | ****************PROVISO**************** | | | A} FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. | | | R4101.9 WATER SUPPLY, LOCAL ORD. | | | #2853-95, BACKFLOW REQUIRED ON WATER | | | SERVICE.(ADD TO NOTES) | | | | | | B} FBC-2004 SEC. 424.2.13.2, OR | | | FBCR-2004 SEC.R4101.13.2 JOINTS AND | | | CONNECTIONS, FBC PLMG SEC 605.21, PURPLE | | | PRIMER REQUIRED ON PVC PIPING.(ADD TO | | | NOTES) | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-11-09 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-11-09 |
Time |
13:41 |
Sent To |
PC |
|
| Notes |
| 2007-11-09 13:41:53 | ***APPROVED - RESUB #1*** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-22 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-22 |
Time |
08:33 |
Sent To |
E |
|
| Notes |
| 2007-10-22 08:35:43 | ***FAILED*** | | | | | | | | | 1)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT | | | FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT | | | SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO | | | THE MINIMUM STANDARDS PROVIDED BELOW. | | | | | | PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND | | | DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C): | | | B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE | | | OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT | | | ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF | | | THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | | HEIGHT ABOVE GRADE. | | | C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE | | | THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND | | | SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR | | | WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF | | | GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL | | | SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH | | | WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT | | | SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | | | 2)INDICATE THE SETBACK DIMENSIONS FROM THE POOL | | | EQUIPMENT TO THE PROPERTY LINES.NOTE: MUST BE A | | | MINIMUM OF 7' TO REAR PROPERTY LINE, AND A MINIMUM OF | | | 1' TO SIDE PROPERTY LINE. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|
|