| 2007-10-21 10:06:49 | 2007-10-21 10:06:49 |
| | |
| | *** DENIED *** |
| | |
| | 2ND FLOOR |
| | |
| | 1) NOTE: PLEASE COORDINATE ALL PLANS, PERMIT |
| | APPLICATION AND SCOPE OF WORK. PLEASE SEE THE BELOW AS |
| | THE PLANS FOR ELECTRICAL WOULD BE OK. PLANS WOULD BE |
| | STAMPED HOWEVER AS SEVERAL SHEETS DO NOT CORRELATE |
| | LOCATION FOR FLOOR ETC. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE PERMIT APPLICATION IS FOR 2ND FLOOR, AND |
| | THE COVER SHEET INDICATES 2ND FLOOR ALONG WITH SHEET |
| | A-2 AND TITLE BLOCKS ON SHEETS A-3, HOWEVER PLEASE SEE |
| | THE SHEET A-3 INDICATES 2ND FLOOR ON FLOOR PLAN LAYOUT |
| | AND THEN INDICATES 3RD FLOOR ON THE CEILING PLAN |
| | LAYOUT. |
| | |
| | A CALLED WAS PLACED TO THE CONTRACTOR AND A MESSAGE WAS |
| | LEFT THAT THOSE TWO NEW SHEETS A-3 COULD BE BROUGHT IN |
| | IF NO OTHER REVIEWS START. THIS WOULD NEED TO BE DONE |
| | BY FIRST THING MONDAY THE 22ND. IF OTHER REVIEWS HAVE |
| | COMMENCED AND IF THERE ARE COMMENTS FROM ANY OTHER |
| | TRADE THEN THESE SHEETS WOULD ONLY BE BROUGHT IN ONCE |
| | ALL REVIEWS ARE COMPLETED AND PLANS ARE RE-SUBMITTED |
| | FOR REVIEW. |
| | ** ELECTRICAL IS OK HOWEVER COORDINATION NEEDS TO BE |
| | ADDRESSED. |
| | FBC 106.5, 106.1, 106.1.2 FOR COORDINATION AND |
| | ADDITIONAL INFORMATION. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |