Plan Review Details - Permit 07100382
Plan Review Stops For Permit 07100382
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-22 Cont ID  
Sent By amorse Date 2007-12-22 Time 08:07 Rev Time 0.00
Received By amorse Date 2007-12-22 Time 08:07 Sent To PC
Notes
2007-12-22 08:23:48 
  
 DENIED
  
 THE FOLLOWING COMMENTS HAVE NOT BEEN ADDRESSED FROM THE
 1ST REVIEW:
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
 ******FEES ADJUSTED FOR VALUE OF $63560.00*******
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
 ******** FEES ARE DUE IN THE AMOUNT OF $143.74 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN
 REVIEW********
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
 *******THE PLANS ARE REQUIRED TO BE STAMPED FOR IMPACT
 FEES AT COUNTY EVEN IF $0.00 FEE BALANCE IS DUE*******
  
 5)MAKE CORRECTIONS TO ENERGY CALCULATIONS PLEASE NOTE
 THAT NO VALUES WERE ASSESSED TO THE FRAMED WALLS THAT
 SEPARATE CONDITIONED AND NON-CONDITIONED SPACES AT
 LAUNDRY ROOM
  
 14)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING
  
  
  
  
 ********REMOVE ALL OLD SETS AND UNUSED PRODUCT
 APPROVALS FROM RESUBMITTAL********
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-06 Cont ID  
Sent By amorse Date 2007-11-06 Time 17:06 Rev Time 0.00
Received By amorse Date 2007-11-06 Time 17:06 Sent To PC
Notes
2007-11-06 17:10:28 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $163.33 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 5)MAKE CORRECTIONS TO ENERGY CALCULATIONS PLEASE NOTE
 THAT THE MIN WALL INSULATION ON THE SHORT FORM IS R-5
 BUT CALCULATIONS SHOULD MATCH THE DRAWINGS WHICH STATE
 ON SHEET 2.1 THAT R-6 BATT WILL BE USED ON WALLS.
  
 6)WINDOW PRODUCT APPROVALS ARE A COMBINATION OF
 DIFFERENT INFORMATION, THE STATE OF FLORIDA APPROVAL IS
 FOR MANY DIFFERENT MODELS ALL WITH DIFFERENT PRESSURE
 MAXIMUMS, THE STC TEST IS FOR A MODEL THAT IS NOT IN
 THE PRODUCT APPROVAL, THE MIAMI-DADE IS FORANOTHER
 MODEL AND THE DRAWINGS STATE TO USE TWO MORE MODELS.
 PLEASE PICK THE TYPE OF WINDOW AND SUBMIT THE PRODUCT
 APPROVAL FOR THAT WINDOW ONLY. (IF THE STC VALUE MEETS
 THE REQUIREMENTS THAT YOU NEED THAT IS OK BUT FOR PLAN
 REVIEW NO REQUIREMENTS NEED TO BE MET AND THE
 INFORMATION IS NOT REQUIRED)
  
 7)WINDOW PRODUCT APPROVAL FROM MIAMI-DADE IS FOR
 NON-IMPACT WINDOWS THEREFORE IMPACT PROTECTION WILL BE
 REQUIRED. PLEASE SUBMIT SHUTTER PRODUCT APPROVALS.
  
 8)DOOR PRODUCT APPROVALS ARE FOR SINGLE DOOR ONLY AND
 IS FOR A 7'-0" TALL DOOR. PLEASE SUBMIT PRODUCT
 APPROVAL FOR THE DOUBLE DOORS AND MEET THE 6'-8" THAT
 YOU REQUIRE.
  
 9)NO PRODUCT APPROVALS WERE SUBMITTED FOR ASPHALT
 SHINGLES, PROPOSED SKYLIGHTS OR STORM SHUTTERS
  
 10)MAXIMUM RISER HEIGHT AT DOORS TO LAUNDRY ROOM IS 7
 3/4" PLEASE MAKE CORRECTION ON DRAWINGS
  
 11)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD
  
 12)CORRECT MIN ROOF SHEATHING ATTACHMENT FOR ZONE 3
 PER R803.2.3.1 FBC RES.
  
 13)PROVIDE POURED/REINFORCED BLOCK CELL IN EXISTING
 BUILDING AT LOCATION OF EXISTING KITCHEN AND BATH AND
 THE INTERSECTION OF L-10 LINTEL THAT CARRIE ROOF LOAD
 OVER CONCRETE PATIO.
  
 14)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF
 NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES ONLY
 FOR REFERENCE
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 12:45 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 12:45 Sent To M
Notes
2007-12-03 12:46:12EXISTING WASHER AND DRYER ARE TO BE DELETED AND ALL
 ELECTRICAL IS TO BE REMOVED.
 PANEL AND LOAD CALCULATIONS ARE SHOWN FOR ONE SET
 ONLY.
 THE NEW WET BAR SHALL NOT BE USED AS A KITCHEN.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By dpalmer Date 2007-10-18 Time 08:35 Rev Time 0.00
Received By dpalmer Date 2007-10-17 Time 16:39 Sent To M
Notes
2007-10-18 08:35:54 
 *** DENIED *****
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODE IS STATED ON
 PLANS.
 2002 NFPA-72.
  
 2) NOTE: PLEASE PROVIDE A LAYOUT OF THE EXISTING
 DWELLING WHICH SHOWS EITHER EXISTING SMOKE ALARMS
 MEETING NFPA-72 OR NEW TO BE INSTALLED.
 PLEASE SEE FBC R313 AND NFPA-72 11.5.1.1.1, 118.3
  
 3) NOTE: PLEASE SEE THE FOLLOWING ITEMS WHICH REQUIRE
 DISCONNECTS ARE INDICATING 240V RECEPTACLE OUTLETS ON
 PLANS.
 CONDENSING UNIT MISSING DISCONNECT PER 440.11.
 TANKLESS WATER HEATER MISSING DISCONNECT PER
 422.30/422.31.
 AIR HANDLER UNIT MISSING DISCONNECT PER 440.11
  
 4) NOTE: CONDENSING UNIT MISSING GFI PER 210.63, 210.8
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR THE NEW TANKLESS WATER HEATER. PLEASE KNOW THERE
 ARE SEVERAL OF THESE UNITS ON THE MARKET WHICH ARE NOT
 A LISTED PRODUCT BY ANY NRTL. (NATIONALLY RECOGNIZED
 TESTING LABORATORY). IE UL, ETL, CSA, TUV, MET ETC.
 90.7, 110.3
 FBC106.1.2
  
 6) NOTE: PLEASE CLARIFY THE RISER AS SHOWN AS THE PLANS
 CALL FOR THIS AS BEING EXISTING YET THE PLANS DO NOT
 SHOW THE MAIN DISCONNECT AS SHOWN ON RISER.
 PLEASE ALSO VERIFY THE CONDUCTORS AS SHOWN ON RISER.
 THIS SHOWS 4/0 AS THE SERVICE ENTRANCE CONDUCTORS AND
 THEN 2/0 TO THE 150 PANEL. THE CONDUCTORS SIZES AS
 SHOWN ARE HIGHER THAN NORMAL AND ARE OK, HOWEVER IF
 SHOWN AS THIS SIZE, THIS IS WHAT WILL BE REQUIRED TO BE
 INSTALLED.
 PLEASE ALSO CLARIFY WHERE THE EXISTING PANEL FOR HOUSE
 IS. AS THE RISER SHOWS THIS PANEL AS NEW, IT IS NOT
 CLEAR WHAT EXISTS AND WHICH IS NEW.
  
 7) NOTE: PLEASE SEE THE MINIMUM WORKING CLEARANCES FOR
 THE TANK-LESS WATER HEATER NEEDS TO BE MET. THE
 LOCATION AND SPACE AS SHOWN ON PLANS DO NOT SEEM TO
 INDICATE ENOUGH CLEARANCES.
 110.3, SEE ALSO MANUFACTURES SPECS/CUT SHEETS FOR
 UNIT.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 08:18 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 08:18 Sent To Z
Notes
2007-11-29 08:18:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-11-06 Time   Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 11:24 Sent To  
Notes
2007-10-15 11:25:08TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By tgordon Date 2007-12-03 Time 15:47 Rev Time 0.25
Received By tgordon Date 2007-12-03 Time 15:47 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 11:54 Rev Time 0.30
Received By tgordon Date 2007-10-18 Time 11:54 Sent To P
Notes
2007-10-18 12:04:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 9A-1 SHOWS R4.1 INSULATION,
 SEE TABLE 6C-1 ON BACK OF ENERGY CAL'S. THE MINIMUM
 INSULATION IS R-5, PLEASE CORRECT AND HAVE ENGINEER
 CORRECT PAGE 2.1 WALL INSULATION, SEE FBC 13-602.1.C.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By jleech Date 2007-12-12 Time 08:59 Rev Time 0.00
Received By jleech Date 2007-12-12 Time 08:59 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By jleech Date 2007-10-31 Time 07:14 Rev Time 0.00
Received By jleech Date 2007-10-31 Time 07:14 Sent To B
Notes
2007-10-31 07:20:53DENIED;
 PAGE A-1 BOTH THE FLAT DRAWING AND THE SANITARY RISER
 DIAGRAM SHOW THE DISCHARGE OF THE W/M GOING THREW THE
 BATHROOM GROUP. THE W/M MUST DISCHARGE DOWN STREAM OF
 THE BATHROOM GROUP. SEE FBC-2004 PLUMBING SECTION
 909.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status F Date 2007-11-30 Cont ID  
Sent By choops Date 2007-11-30 Time 15:38 Rev Time 0.00
Received By choops Date 2007-11-30 Time 15:38 Sent To E
Notes
2007-11-30 15:29:58***FAILED- RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)THE VALUE OF PROPOSED WORK EXCEEDS 50% OF THE
 VALUE OF THE HOME.PURSUANT TO ARTICLE XIV OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS(ZLDRS), A
 LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION 94-442
 AND 94-445 OF THE ZLDR'S SHALL BE SUBMITTED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-17 Cont ID  
Sent By choops Date 2007-10-17 Time 09:26 Rev Time 0.00
Received By choops Date 2007-10-17 Time 09:26 Sent To E
Notes
2007-10-17 09:39:06***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS), AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50%
 OF THE VALUE OF THE STRUCTURE, LANDSCAPING SHALL BE
 BROUGHT TO COMPLIANCE.PLEASE PROVIDE A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTION 94-442 OF THE ZLDRS.
  
 2)SURVEY SHOWS THE PROPOSED ADDITION CONNECTING TO
 AN EXISTING FRAME UTILITY BUILDING.PLEASE CLARIFY. IF
 UTILITY STRUCTURE DOES EXIST, THIS WILL NOT BE
 PERMITTED AS THE REAR BUILDING DOES NOT MEET THE
 REQUIRED SETBACKS SET FORTH IN SECTION 94-72(A)(2) OF
 THE ZLDRS.
  
 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED ADDITION
 TO ALL PROPERTY LINES SHOWING COMPLIANCE WITH SECTION
 94-72(A)(2) OF THE ZLDRS.
  
 4)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720
  
  
 SENT TO "E" - DP