Plan Review Details - Permit 07100365
Plan Review Stops For Permit 07100365
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-17 Cont ID  
Sent By rmcdouga Date 2007-10-17 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2007-10-17 Time 18:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By rmcdouga Date 2007-10-16 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2007-10-16 Time 10:11 Sent To  
Notes
2007-10-16 10:30:112004 FBC W/2007 REVISIONS
 REROOF WITH METAL ROOF
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL FOR THE SOUTHEASTERN 5V-CRIMP
 METAL ROOF SYSTEM HAS A MAXIMUM UPLIFT DESIGN PRESSURE
 OF -57.5 PSF WITH NO ENHANCED FASTENING ALLOWED. THIS
 PRESSURE IS TOO LOW FOR THE CORNER AREAS WHICH REQUIRE
 -83.1 PSF PER FBC TABLE 1609.6.2.1(2).
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 12:33 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 12:33 Sent To B
Notes
2007-10-17 12:33:59TO "RMCDOUGAL" DESK/RESUB