| 2007-10-16 10:30:11 | 2004 FBC W/2007 REVISIONS | | | REROOF WITH METAL ROOF | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVAL FOR THE SOUTHEASTERN 5V-CRIMP | | | METAL ROOF SYSTEM HAS A MAXIMUM UPLIFT DESIGN PRESSURE | | | OF -57.5 PSF WITH NO ENHANCED FASTENING ALLOWED. THIS | | | PRESSURE IS TOO LOW FOR THE CORNER AREAS WHICH REQUIRE | | | -83.1 PSF PER FBC TABLE 1609.6.2.1(2). | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|