Plan Review Details - Permit 07100361
Plan Review Stops For Permit 07100361
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-09-15 Cont ID  
Sent By mjacobs Date 2008-09-15 Time 08:25 Rev Time 0.00
Received By mjacobs Date 2008-09-12 Time 15:07 Sent To Z
Notes
2008-09-15 08:33:21THERE IS NO ZONING STAMPS ON THE PLANS. SO I AM SENDING
 THE PACKAGE TO THEZONING TEC MCRUZ

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-08-12 Cont ID  
Sent By mjacobs Date 2008-08-12 Time 11:00 Rev Time 0.00
Received By mjacobs Date 2008-08-12 Time 07:07 Sent To PC
Notes
2008-08-12 07:48:19REVIEW: 3RD
 ACTION: DENIED
 8-12-08
  
 1A) OK
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) OK
 2) OK
 3) OK
 4) OK
 5) OK
 6) OK
 7) OK
 8) OK
 9) OK
 10) OK
 11) OK
  
 **NOTED; HOWEVER, THIS NEEDS TO BE DONE BEFORE THE
 PERMIT CAN BE ISSSUED**
 12) BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE INFORMATION.
  
 **NOTED, HOWEVER THE PLANS NEEDS TO BE SPECIFIC** 13)
 FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL
 14) OK
 **NO RESPONSE NOT ADDRESSED**
 15) THERE IS NO RECORD FOR THE INTERIOR MODIFICATION OF
 THE EXISTING STRUCTURE; THEREFORE PLANS SHALL BE
 SUBMITTED FOR THE REMODEL WORK. A FAIR MARKET VALUE
 SHALL BE INDICATED ON THE PERMIT APPLICATION. ONCE
 AGAIN THE VALUE SHALL BE ADJUSTED PRIOR THE TO THE
 PERMIT BE ISSUED. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COST AND OVERHEAD AND PROFIT EXCLUDING
 LAND. 108.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-01-16 Cont ID  
Sent By mjacobs Date 2008-01-16 Time 10:32 Rev Time 0.00
Received By mjacobs Date 2008-01-16 Time 08:39 Sent To  
Notes
2008-01-16 10:31:22 
 BUILDING PLAN REVIEW
 PERMIT: 07100361
 ADD: 339 WESTMINSTER PL
 CONT: BATTEN CONST.
 TEL: (561)820-0027
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 1-16-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **NO RESPONSE NOT ADDRESSED**
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 **NO RESPONSE NOT ADDRESSED**
 2)2004 FBC EXISTING 301.5. A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 **NO RESPONSE NOT ADDRESSED**
 3)THE CERTIFICATE OF AUTHORIZATION FOR BROWER
 ARCHITECTURE ASSOCIATES INC SHALL BE INDICATED ON EACH
 SHEET PER F.S 481.219 AND F.A.C. 61G1-16.004. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE A VALID CERTIFICATE OF AUTHORIZATION NUMBER.
  
 **NO RESPONSE NOT ADDRESSED**
 4)AN EXISTING AND A PROPOSED FLOOR PLAN SHALL BE
 SUBMITTED SHOWING THE CHANGES TO EACH WALL AND ROOM. A
 WALL LEGEND SHALL BE PROVIDED SHOWING EACH NEW WALL,
 EXISTING WALL TO BE DEMOED AND REMAINING WALLS. THE
 FLOOR PLAN SHALL CONSIST OF THE ENTIRE STRUCTURE FOR
 THE EXISTING AND THE PROPOSED. A DETAIL OF EACH WALL
 WITH ALL MATERIALS, STUD SPACING AND UL NUMBER IS
 REQUIRED.THE PLANS SHALL INDICATE THE TYPE OF
 CONSTRUCTION AS DEFINED IN CHAPTER 6, TABLE 601/ THE
 USE AND OCCUPANCY IN ACCORDANCE WITH THE PROVISIONS OF
 CHAPTER 3 AND THE OCCUPANT LOAD SEE 1004. THE BUILDING
 OFFICIAL MAY REQUIRE ADDITIONAL INFORMATION DUE TO THE
 CHANGE OF OCCUPANCY. W.P.B AMENDMENTS 106.1.2
  
 **NO RESPONSE NOT ADDRESSED**
 5)A LIFE SAFETY PLAN SHALL BE SUBMITTED SHOWING THE
 MEANS OF EGRESS WHICH SHALL INCLUDE EXIT, EXIT ACCESS
 AND EXIT DISCHARGE.
  
 **NO RESPONSE NOT ADDRESSED**
 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY. PROVIDE A FINISH
 SCHEDULE INDICATING THE FINISH IN EACH ROOM.
  
 **NO RESPONSE NOT ADDRESSED**
 7)SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR. 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST
 27" HIGH 30" WIDE, AND 19" DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK. PROVIDE ELEVATION DRAWINGS SHOWING
 COMPLIANCE.
  
 **NO RESPONSE NOT ADDRESSED**
 8)ON THE DRAWINGS SHOW CLEARLY THESE REQUIREMENTS FOR
 THE RAMP. 11-4.8.4. (2) LANDINGS. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARANCE. 11-4.8.4(3) IF RAMPS CHANGE DIRECTION AT
 LANDINGS, THE MINIMUM LANDING SIZE SHALL BE 60" X 60".
 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN
 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 **NO RESPONSE NOT ADDRESSED**
 9)AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY
 OF THE SITE SHALL BE PROVIDED FROM PUBLIC
 TRANSPORTATION STOPS, ACCESSIBLE PARKING, AND
 ACCESSIBLE PASSENGER LOADING ZONES, AND PUBLIC STREETS
 OR SIDEWALKS TO THE ACCESSIBLE BUILDING ENTRANCE THEY
 SERVE. THE ACCESSIBLE ROUTE SHALL, TO THE MAXIMUM
 EXTENT FEASIBLE, COINCIDE WITH THE ROUTE FOR THE
 GENERAL PUBLIC. FBC.11-4.3.2. INDICATE THE ACCESSIBLE
 ROUTE.
  
 **NO RESPONSE NOT ADDRESSED**
 10)THE DRAWINGS SHALL SHOW THE ACCESSIBLE PARKING FOR
 THE BUILDING, WHICH SHALL BE LOCATED ON THE SHORTEST
 SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM THE PARKING LOT
 TO THE ENTRANCE TO THE BUILDING. 11-4.6.2.
  
 **NO RESPONSE NOT ADDRESSED**
 11)THE DRAWINGS MAKE REFERENCES TO DETAILS WHICH ARE
 NOT SUBMITTED E.G. A2.03 / A2.02. THE DRAWINGS ALSO
 MAKE REFERENCE TO NEW SITE WALL; HOWEVER, THERE IS NO
 INFORMATION OR DETAILS OF THE NEW WALL ON THE PLANS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS. FBC 106.1.1.
  
 **NO RESPONSE NOT ADDRESSED**
 12)BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY.THE ACTUAL
 PERMIT PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE INFORMATION.
  
 **NO RESPONSE NOT ADDRESSED**
 13)FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR.
  
 14)OK
  
 **NO RESPONSE NOT ADDRESSED**
 15)THERE IS NO RECORD FOR THE INTERIOR MODIFICATION
 OF THE EXISTING STRUCTURE; THEREFORE PLANS SHALL BE
 SUBMITTED FOR THE REMODEL WORK. A FAIR MARKET VALUE
 SHALL BE INDICATED ON THE PERMIT APPLICATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-03 Cont ID  
Sent By mjacobs Date 2008-01-03 Time 11:50 Rev Time 0.00
Received By mjacobs Date 2008-01-02 Time 16:53 Sent To  
Notes
2008-01-03 11:50:08BUILDING PLAN REVIEW
 PERMIT: 07100361
 ADD: 339 WESTMINSTER PL
 CONT: BATTEN CONST.
 TEL: (561)820-0027
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 1-2-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2)2004 FBC EXISTING 301.5. A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 3)THE CERTIFICATE OF AUTHORIZATION FOR BROWER
 ARCHITECTURE ASSOCIATES INC SHALL BE INDICATED ON EACH
 SHEET PER F.S 481.219 AND F.A.C. 61G1-16.004. THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE A VALID CERTIFICATE OF AUTHORIZATION NUMBER.
  
 4)AN EXISTING AND A PROPOSED FLOOR PLAN SHALL BE
 SUBMITTED SHOWING THE CHANGES TO EACH WALL AND ROOM. A
 WALL LEGEND SHALL BE PROVIDED SHOWING EACH NEW WALL,
 EXISTING WALL TO BE DEMOED AND REMAINING WALLS. THE
 FLOOR PLAN SHALL CONSIST OF THE ENTIRE STRUCTURE FOR
 THE EXISTING AND THE PROPOSED. A DETAIL OF EACH WALL
 WITH ALL MATERIALS, STUD SPACING AND UL NUMBER IS
 REQUIRED.THE PLANS SHALL INDICATE THE TYPE OF
 CONSTRUCTION AS DEFINED IN CHAPTER 6, TABLE 601/ THE
 USE AND OCCUPANCY IN ACCORDANCE WITH THE PROVISIONS OF
 CHAPTER 3 AND THE OCCUPANT LOAD SEE 1004. THE BUILDING
 OFFICIAL MAY REQUIRE ADDITIONAL INFORMATION DUE TO THE
 CHANGE OF OCCUPANCY. W.P.B AMENDMENTS 106.1.2
  
 5)A LIFE SAFETY PLAN SHALL BE SUBMITTED SHOWING THE
 MEANS OF EGRESS WHICH SHALL INCLUDE EXIT, EXIT ACCESS
 AND EXIT DISCHARGE.
  
 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY. PROVIDE A FINISH
 SCHEDULE INDICATING THE FINISH IN EACH ROOM.
  
 7)SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR. 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST
 27" HIGH 30" WIDE, AND 19" DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS. 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK. PROVIDE ELEVATION DRAWINGS SHOWING
 COMPLIANCE.
  
 8)ON THE DRAWINGS SHOW CLEARLY THESE REQUIREMENTS FOR
 THE RAMP. 11-4.8.4. (2) LANDINGS. ALL LANDINGS ON RAMPS
 SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH
 RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARANCE. 11-4.8.4(3) IF RAMPS CHANGE DIRECTION AT
 LANDINGS, THE MINIMUM LANDING SIZE SHALL BE 60" X 60".
 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN
 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 9)AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY
 OF THE SITE SHALL BE PROVIDED FROM PUBLIC
 TRANSPORTATION STOPS, ACCESSIBLE PARKING, AND
 ACCESSIBLE PASSENGER LOADING ZONES, AND PUBLIC STREETS
 OR SIDEWALKS TO THE ACCESSIBLE BUILDING ENTRANCE THEY
 SERVE. THE ACCESSIBLE ROUTE SHALL, TO THE MAXIMUM
 EXTENT FEASIBLE, COINCIDE WITH THE ROUTE FOR THE
 GENERAL PUBLIC. FBC.11-4.3.2.
  
 10)THE DRAWINGS SHALL SHOW THE ACCESSIBLE PARKING FOR
 THE BUILDING, WHICH SHALL BE LOCATED ON THE SHORTEST
 SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM THE PARKING LOT
 TO THE ENTRANCE TO THE BUILDING. 11-4.6.2.
  
 11)THE DRAWINGS MAKE REFERENCES TO DETAILS WHICH ARE
 NOT SUBMITTED E.G. A2.03 / A2.02. THE DRAWINGS ALSO
 MAKE REFERENCE TO NEW SITE WALL; HOWEVER, THERE IS NO
 INFORMATION OR DETAILS OF THE NEW WALL ON THE PLANS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS. FBC 106.1.1.
  
 12)BEFORE A PERMIT TO CONSTRUCT MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY.THE ACTUAL
 PERMIT PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE INFORMATION.
  
 13)FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET ABOVE THE FLOOR.
  
 14)ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH SECTION 11-4.13. DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. FBC
 11-4.22.2.
  
 15)THERE IS NO RECORD FOR THE INTERIOR MODIFICATION
 OF THE EXISTING STRUCTURE; THEREFORE PLANS SHALL BE
 SUBMITTED FOR THE REMODEL WORK. A FAIR MARKET VALUE
 SHALL BE INDICATED ON THE PERMIT APPLICATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By kconrad Date 2007-10-18 Time 19:29 Rev Time 0.00
Received By kconrad Date 2007-10-18 Time 19:29 Sent To I
Notes
2007-10-18 19:30:27REQUIRE PLANS FOR CHANGE OF OCCUPANCY. PLANS SHALL
 COMPLY WITH SECTION 800 OF THE FLORIDA EXISTING
 BUILDING CODE.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2008-09-18 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 11:02 Rev Time 0.00
Received By btrobaug Date 2008-09-18 Time 10:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-08-01 Cont ID  
Sent By btrobaug Date 2008-08-01 Time 16:00 Rev Time 0.00
Received By btrobaug Date 2008-08-01 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-23 Cont ID  
Sent By btrobaug Date 2008-01-23 Time 11:46 Rev Time 0.00
Received By btrobaug Date 2008-01-23 Time 11:40 Sent To  
Notes
2008-01-23 11:46:17 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 SAME COMMENTS AS PREVIOUS REVIEW WITH NO RESPONSE.
  
 1}7.8 ILLUMINATION OF MEANS OF EGRESS, INDICATE
 COMPLIANCE FOR SAME. 7.8 NFPA-101
  
 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE
 CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR
 13-415.2.C.1 DENSITIES. DENSITY AND LIGHTING CONTROLS
 MUST BE SUBMITTED FOR REVIEW, AND THE FIXTURE SCHEDULE
 MUST AGREE. 13-101.6 BUILDING SYSTEMS.THERMAL
 EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING BUILDING
 SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR REPLACED IN
 EXISTING BUILDINGS, AND FOR WHICH A PERMIT MUST BE
 OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM
 EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR
 COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL
 BUILDINGS.
  
 3} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-31 Cont ID  
Sent By btrobaug Date 2007-12-31 Time 14:29 Rev Time 0.00
Received By btrobaug Date 2007-12-31 Time 13:06 Sent To  
Notes
2007-12-31 14:29:03 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1}7.8 ILLUMINATION OF MEANS OF EGRESS, INDICATE
 COMPLIANCE FOR SAME. 7.8 NFPA-101
  
 2} INDICATE COMPLIANCE WITH 13-415.2ABC.1, PERFORMANCE
 CALCULATION PROCEDURES. SUBMIT FORMS WITH 13-415.2B OR
 13-415.2.C.1 DENSITIES. DENSITY AND LIGHTING CONTROLS
 MUST BE SUBMITTED FOR REVIEW, AND THE FIXTURE SCHEDULE
 MUST AGREE. 13-101.6 BUILDING SYSTEMS.THERMAL
 EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING BUILDING
 SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR REPLACED IN
 EXISTING BUILDINGS, AND FOR WHICH A PERMIT MUST BE
 OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM
 EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR
 COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL
 BUILDINGS.
  
 3} THE ARCHITECTURAL FIRM MUST DISPLAY THE CERTIFICATE
 OF AUTHORIZATION ON THE TITLE BLOCK PER 481.221 (8).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-08-04 Cont ID  
Sent By mawillia Date 2008-08-04 Time 16:11 Rev Time 0.00
Received By mawillia Date 2008-08-04 Time 15:34 Sent To  
Notes
2008-08-04 16:05:44*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A1.02, A1.03, A1.04, AND
 A2.02, WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-01-23 Cont ID  
Sent By mawillia Date 2008-01-23 Time 13:42 Rev Time 0.00
Received By mawillia Date 2008-01-23 Time 13:31 Sent To  
Notes
2008-01-23 13:37:32*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 03.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM
 THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 04.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 05.DUE TO THE CHANGE IN OCCUPANCY, THE DIMENSION OF
 THE ADDRESS NUMBER SHALL BE NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH.PLEASE SHOW THE ADDRESS
 NUMBERS ON THE APPROPIATE EXTERIOR ELEVATION WHICH
 FRONTS WESTMINISTER PLACE.
  
 06.PROVIDE THE OCCUPANT LOAD (NUMBER OF PERSONS FOR
 WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED)
 BASED UPON THE CHARACTERISTICS OF THE USE OF THE SPACE
 OR AS DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF
 THE SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
 07. PLEASE SHOW EXISTING LAYOUT OF THE STRUCTURE AS TO
 BE COMPARED TO THE PROPOSED LAYOUT DETAILING THE SCOPE
 OF WORK (CONVERSION FROM A RESIDENTIAL OCCUPANCY TO A
 NEW BUSINESS OCCUPANCY).
  
 08.SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
  
 09.PROVIDE LIFE SAFETY PLAN CRITERIA SHOWING TRAVEL
 DISTANCE TO REACH EXIT(S).THE LOCATION OF EXIT LIGHTS
 AND EMERGENCY LIGHTS MAY ALSO BE SHOWN.
  
 10.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75 FEET TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM AWAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-03 Cont ID  
Sent By mawillia Date 2008-01-03 Time 15:58 Rev Time 0.00
Received By mawillia Date 2008-01-03 Time 14:55 Sent To  
Notes
2008-01-03 14:56:02*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES).
  
 03.COMBUSTIBLE WASTE MATERIALS SHALL BE REMOVED FROM
 THE SITE AT THE END OF EACH SHIFT OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 04.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 05.DUE TO THE CHANGE IN OCCUPANCY, THE DIMENSION OF
 THE ADDRESS NUMBER SHALL BE NO LESS THAN 6" IN HEIGHT
 AND NO LESS THAN 1" IN WIDTH.PLEASE SHOW THE ADDRESS
 NUMBERS ON THE APPROPIATE EXTERIOR ELEVATION WHICH
 FRONTS WESTMINISTER PLACE.
  
 06.PROVIDE THE OCCUPANT LOAD (NUMBER OF PERSONS FOR
 WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED)
 BASED UPON THE CHARACTERISTICS OF THE USE OF THE SPACE
 OR AS DETERMINED AS THE MAXIMUM PROBABLE POPULATION OF
 THE SPACE UNDER CONSIDERATION, WHICHEVER IS GREATER.
  
 07. PLEASE SHOW EXISTING LAYOUT OF THE STRUCTURE AS TO
 BE COMPARED TO THE PROPOSED LAYOUT DETAILING THE SCOPE
 OF WORK (CONVERSION FROM A RESIDENTIAL OCCUPANCY TO A
 NEW BUSINESS OCCUPANCY).
  
 08.SPECIFY INTERIOR WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY
 INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II.
  
 09.PROVIDE LIFE SAFETY PLAN CRITERIA SHOWING TRAVEL
 DISTANCE TO REACH EXIT(S).THE LOCATION OF EXIT LIGHTS
 AND EMERGENCY LIGHTS MAY ALSO BE SHOWN.
  
 10.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75 FEET TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM AWAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-01-11 Cont ID  
Sent By ssherman Date 2008-01-11 Time 14:05 Rev Time 0.00
Received By ssherman Date 2008-01-11 Time 14:05 Sent To  
Notes
2008-01-11 14:06:16HISTORICAL APPROVAL PER GALINA JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-08 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 11:03 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 16:09 Sent To B
Notes
2008-09-08 16:10:04TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-24 Cont ID  
Sent By adarroug Date 2008-07-24 Time 13:27 Rev Time 0.00
Received By adarroug Date 2008-07-24 Time 13:27 Sent To  
Notes
2008-08-01 11:25:42TO "BOB"#3
2008-07-24 13:27:55WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:16 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:16 Sent To  
Notes
2008-01-11 17:16:52TO "BOB" # 6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-26 Cont ID  
Sent By spalmer Date 2007-12-26 Time 15:00 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 15:00 Sent To  
Notes
2007-12-26 15:00:59TO "BOB" # 7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-20 Cont ID  
Sent By mmiller Date 2007-12-20 Time 17:43 Rev Time 0.00
Received By mmiller Date 2007-12-20 Time 17:40 Sent To  
Notes
2007-12-20 17:41:41WAITING FOR "BOB" MMILLER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-27 Cont ID  
Sent By tgordon Date 2007-12-27 Time 11:10 Rev Time 0.20
Received By tgordon Date 2007-12-27 Time 11:10 Sent To  
Notes
2007-12-27 11:11:19NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-08-05 Cont ID  
Sent By mperson Date 2008-08-05 Time 15:19 Rev Time 0.00
Received By mperson Date 2008-08-05 Time 15:19 Sent To  
Notes
2008-08-05 15:24:17****************PROVISO*****************
 A} PER FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTION 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING
 FOUNTAIN IS PROVIDED ON A FLOOR, THERE SHALL BE A
 DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO INDIVIDUALS
 WHO USE WHEELCHAIRS IN ACCORDANCE WITH SECTION 11-4.15
 AND ONE ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY BENDING
 OR STOOPING.(THIS CAN BE ACCOMMODATED BY THE USE OF A
 HI-LO FOUNTAIN OR BY SUCH OTHER MEANS AS WOULD ACHIEVE
 THE REQUIRED ACCESSIBILITY FOR EACH GROUP ON EACH
 FLOOR).
  
 B} A CLEANOUT IS REQUIRED AT THE BASE OF THE DRINKING
 FOUNTAIN WASTE STACK. PER FBC-2004 PLUMBING SECTION
 708.3.5 BASE OF STACK.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-17 Cont ID  
Sent By jleech Date 2008-01-17 Time 14:37 Rev Time 0.00
Received By jleech Date 2008-01-17 Time 14:36 Sent To  
Notes
2008-01-17 14:51:14DENIED;
 PLUMBING PLAN REVIEW COMMENTS FROM 1/2/08 HAVE NOT BEEN
 ADDRESSED;
 1. NO; PLANS DO NOT SHOW REQUIRED DRINKING FOUNTAIN.
 SEE TABLE 403.1 2004 FBC-PLUMBING.
 2. NO; SHOW A DETAIL OF SINK WITH ALL REQUIRED
 MESSUREMENTS TO COMPLY WITH FBC-BUILDING CHAPTER 11,
 SECTIONS 11-4.24.1 THRU 11-4.24.7.
 3. NO; SANITARY RISER DIAGRAM IS REQUIRED SEE
 FBC-BUILDING CHAPTER 1 ADMINISTRATION CODE SECTION
 106.3.5.1.3 (13).
 A COPY OF FIRST REVIEW IS ATTACHED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By jleech Date 2008-01-02 Time 07:38 Rev Time 0.00
Received By jleech Date 2008-01-02 Time 07:25 Sent To  
Notes
2008-01-02 08:02:59DENIED;
 1.FBC-PLUMBING TABLE 403.1 MINIMUM PLUMBING
 REQUIREMENTS REQUIRES A DRINKING FOUNTAIN. THE DRINKING
 FOUNTAIN SHALL MEET THE REQUIREMENTS OF FBC-BUILDING
 CHAPTER 11 SECTIONS 11-4.15.1 THRU 11-4.15.5. SHOW A
 DETAIL ON PLANS WITH ALL REQUIRED MEASUREMENTS AND SHOW
 CLEAR FLOOR SPACE REQUIRED.
 2. DUE TO CHANGE OF OCCUPENCY THE KITCHEN BECOMES A
 COMMON AREA AND THE SINK IS REQUIRED TO MEET THE
 REQUIREMENTS OF BUILDING CHAPTER 11 SECTIONS 11-4.24.1
 THRU 11-4.24.7. SHOW A DETAIL ON PLANS WITH ALL
 REQUIRED MEASUREMENTS AND SHOW THE CLEAR FLOOR SPACE ON
 PLANS.
 3. DUE TO THE REQUIREMENTS FOR A DRINKING FOUNTAIN A
 SANITARY RISER DIAGRAM IS REQUIRED, SEE AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2004 EDITION SECTION 106.3.5.1.3(13).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2008-09-17 Cont ID  
Sent By mcruz Date 2008-09-17 Time 10:13 Rev Time 0.00
Received By mcruz Date 2008-09-17 Time 10:11 Sent To  
Notes
2008-09-17 10:14:45ZONING PASSED WITH PROVISO:
  
 LANDSCAPING AND PARKING APPROVED ON
 PERMIT #07011025, SHALL BE INSTALLED AND
 COMPLETED PRIOR TO THE ISSUANCE OF A CO.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-12-28 Cont ID  
Sent By choops Date 2007-12-28 Time 15:35 Rev Time 0.00
Received By choops Date 2007-12-28 Time 15:35 Sent To  
Notes
2007-12-28 15:36:30LANDSCAPING AND PARKING APPROVED ON PERMIT # 07011025,
 SHALL BE INSTALLED AND COMPLETE PRIOR TO THE ISSUANCE
 OF A CO.


Account Summary | Usage Policy | Privacy Policy