| 2007-10-26 16:05:05 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| | DOES NOT SHOW ALL CUT SECTIONS OF PIPE AND |
| | CORRESPONDING LENGTHS. PLEASE CORRECT AND RESUBMIT. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | **NOTE: THE ONLY PIPING MATERIAL BEING INDICATED IS FOR |
| | THE UNDERGROUND PE PIPE. WHAT IS THE ABOVE GROUND |
| | PIPING MATERIAL? PLEASE CORRECT AND RESUBMIT. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **NOTE: PLEASE REFERENCE COMMENT #1 AND COMPLY ON THE |
| | RESUBMITTAL. |
| | |
| | 4. PER FBC-2004 FUEL GAS SEC. 404.12 OUTLET CLOSURES: |
| | GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE |
| | CAPPED GAS TIGHT. |
| | **NOTE: PLEASE INDICATE THIS FOR THE FUTURE BBQ AND |
| | POOL HEATER ON THE RESUBMITTAL. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | **NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATIONS FOR |
| | THE MP REGULATORS INDICATING THE MAKE, MODEL NUMBER, |
| | BTU LOAD CAPACITY, AND A LISTING FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY. |
| | |
| | 6. THE VALUE OF $450.00 SEEMS TO LOW PER FBC-2004, |
| | CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | **NOTE: PLEASE ADJUST THE VALUE ON THE PERMIT |
| | APPLICATION PRIOR TO THE RESUBMITTAL AND PAY FEES IF |
| | APPICABLE OR PROVIDE A COPY OF THE SIGNED CONTRACT THAT |
| | REFLECTS THE INDICATED VALUE ON THE PERMIT |
| | APPLICATION. |
| | |
| | 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |