| 2007-10-25 13:37:56 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ***NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED |
| | FOR ALL CUT SECTIONS OF PIPE. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | ***NOTE: NOT ALL PIPE SIZES OR MATERIALS ARE INDICATED. |
| | PLEASE CLARIFY IF THE 8' RISER OF 1" POLY U/G IS |
| | MISLABELED, SHOULDN'T IT BE 8' OF 1" GALV. A/G. PLEASE |
| | BE AWARE THAT THE 199,000 BTU WATER HEATER NEEDS TO BE |
| | 1-1/4" SCH. 40 METALLIC PER TABLE 402.4 (2) WITH THE |
| | 99' DEVELOPED LENGTH. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ***NOTE: PLEASE REFERENCE COMMENT #1. PLEASE KNOW THAT |
| | SYSTEM IS NOW SIZED WITH TABLES USING A LONGEST LENGTH |
| | OF 100'. IF COMMENT #1 CHANGES THE DEVELOPED LENGTH AS |
| | BEING OVER 100', THE SYSTEM WILL NEED TO BE RESIZED. |
| | |
| | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***NOTE:THE SUBMITTED MANUFACTURER SHEETS FOR THE |
| | FOLLOWING APPLIANCES NEED THE FOLLOWING INFORMATION ON |
| | THE RESUBMITTAL. |
| | |
| | **A} ISOKERN UNVENTED GAS LOG: |
| | A) VERIFICATION OF THE APPLIANCE BTU LOAD. |
| | B) VERIFICATION THAT THE APPLIANCE IS LISTED BY A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | |
| | **B} JENN-AIR RANGE: |
| | A) VERIFICATION OF THE APPLIANCE BTU LOAD. |
| | |
| | 5. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | ***NOTE: THE GAS RISER AND PLAN-SHOP DRAWINGS HAS |
| | GORDON F. BUCK OF BUCK ENGINEERING AS HAVING REVIEWED |
| | THE DRAWINGS BUT IS NOT TAKING THE RESPONSIBILITY OF |
| | THE DRAWINGS. SOMEONE NEEDS TO TAKE THE RESPONSIBILITY |
| | FOR THE DESIGN ON THE RESUBMITTAL. |
| | |
| | 6. NOTE: SHEET 3.1 IS A REVISION FOR MASTER PERMIT |
| | #07020398 AND MUST BE SUBMITTED AS SUCH PER FBC-2004 |
| | CHAPTER 1, SECTION 106.4, AMENDED CONSTRUCTION |
| | DOCUMENTS. THIS SHEET WILL NOT BE REVIEWED ON THIS |
| | PERMIT APPLICATION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |