| 2008-03-14 09:14:08 | ** DENIED2RD REVIEW ** |
| | |
| | ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS DUE TO INFORMATION NOW BEING ADDED TO PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE RISER WHICH SHOWS NO OCP FOR |
| | PANEL. |
| | 230.70, 230.71. IS THIS A METER CENTER? |
| | |
| | 2) NOTE: PLEASE SEE THE RISER SHOWS 3-#3, 1#8 AND |
| | ANOTHER #8? WHAT IS THIS SECOND #8? |
| | PLEASE CLARIFY. |
| | 230, 215, 310 |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE WITH RESPECT |
| | TO 210.11C1, 210.52B1 AND 220.52 AS ONE OR MORE OF THE |
| | SMALL APPLIANCE, DINING ROOM RECEPTACLE CIRCUITS ETC |
| | ARE REQUIRED TO BE FIGURED AT 1500VA. PLEASE SEE LOAD |
| | CALCULATIONS ONLY SHOW THE TWO SMALL APPLIANCE |
| | CIRCUITS. |
| | |
| | 4) NOTE: PLEASE SEE THE CU IS BEING SHOWN ON A 1-POLE |
| | 20AMP CIRCUIT.HOW CAN THIS BE CORRECT WITH A 2.5 TON |
| | CU.THE MODEL AS GIVEN BY THE MANUFACTURE STATES A |
| | MINIMUM OF 230V. |
| | PLEASE ADJUST. |
| | 240.4, 310.16, 408.4, 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE KITCHEN COUNTER WHICH REQUIRES GFI |
| | WITHIN 2FT OF THE END OF COUNTER SPACE. |
| | PLEASE ALSO SEE THE DISPOSAL IN KITCHEN DOES NOT SHOW |
| | ANY METHOD FOR CONTROL. WILL THIS BE SELF ACTUATING? |
| | 210.52C1 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 6) NOTE: PLEASE SEE 424.3B WHICH REQUIRES OCP FOR HEAT |
| | IN AHU TO BE SIZED AT 125%. PANEL SHOWS 40AMP OCP. MIN |
| | PER SECTION OF CODE GIVEN SHOULD BE 45AMPS. |
| | THE SIZING OF BRANCH-CIRCUIT CONDUCTORS AND |
| | OVER-CURRENT DEVICES SUPPLYING FIXED ELECTRIC |
| | SPACE-HEATING EQUIPMENT AT 125 PERCENT OF THE TOTAL |
| | LOAD OF THE HEATERS (AND MOTORS) IS PREDICATED ON THE |
| | NEED TO PROTECT OVER-CURRENT DEVICES, PARTICULARLY IN |
| | PANEL-BOARDS, AND CONDUCTORS FROM OVERHEATING DURING |
| | PERIODS OF PROLONGED OPERATION. |
| | ** THIS ALSO AFFECT FEEDERS AND LOAD CALCULATIONS. |
| | |
| | 7) NOTE: PLEASE GO OVER LOAD CALCULATIONS. BASED ON |
| | COMMENTS ABOVE THE LOAD WILL BE INCREASING DUE TO SOME |
| | ITEMS MISSING. |
| | PLEASE ALSO SEE LOADS SUCH AS DISPOSAL WHICH IS BEING |
| | SHOWN AS 1500VA ON PANEL SCHEDULE AND 1000VA ON LOAD |
| | CALCULATIONS. WHAT HAPPENED TO THE OTHER 500VA? PLEASE |
| | SEE 422.13 AS THIS SPECIFICALLY IDENTIFIES AN ELECTRIC |
| | WATER HEATER WITH A STORAGE CAPACITY OF 120 GAL OR LESS |
| | AS A CONTINUOUS LOAD. THIS REVISION REQUIRES THE BRANCH |
| | CIRCUIT OVERCURRENT DEVICE AND CONDUCTORS TO BE SIZED |
| | BASED ON 125 PERCENT OF THE WATER HEATER NAMEPLATE |
| | RATING UNLESS THE OVERCURRENT DEVICE AND THE ASSEMBLY |
| | IT IS INSTALLED IN ARE LISTED TO BE USED AT 100 PERCENT |
| | OF ITS CONTINUOUS CURRENT RATING. IN ADDITION, FEEDERS |
| | AND SERVICES THAT SUPPLY WATER HEATER BRANCH CIRCUITS |
| | ARE ALSO IMPACTED BY THE FACT THAT THIS TYPE OF |
| | EQUIPMENT IS CONSIDERED TO BE A CONTINUOUS LOAD. |
| | AS THE LOAD ON THE SERVICE PANEL IS SHOWN VERY CLOSE TO |
| | BEING OVERLOADED THERE IS CONCERN OVER THE SIZE. 220, |
| | 215 ETC |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE SPECIFIC NOTES ON PREVIOUS REVIEW |
| | AND ALOGN WITH FBC AND FS REQUIRES THE CODE ADOPTED AND |
| | UNDER DESIGN FOR ANY PROJECT TO BE STATED ON PLANS |
| | ALONG WITH LEVEL OF ALTERATION. |
| | FS 553.73 |
| | CODES WERE ADDED HOWEVER NOT YEAR EDITION AS GIVEN ON |
| | PREVIOUS REVIEW. |
| | 2005 NFPA70 |
| | 2003 NFPA_101 |
| | 2002 NFPA-72 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |