Plan Review Details - Permit 07100316
Plan Review Stops For Permit 07100316
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-11-14 Cont ID  
Sent By mperson Date 2007-11-14 Time 14:36 Rev Time 0.00
Received By mperson Date 2007-11-14 Time 14:36 Sent To PC
Notes
2007-11-14 14:37:42REVISION: "OK" CHANGED NEW UNDERGROUND LINE FROM
 GALVANIZED TO PE.
  
 ****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-10-24 Cont ID  
Sent By mperson Date 2007-10-24 Time 15:35 Rev Time 0.00
Received By mperson Date 2007-10-24 Time 15:35 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 11:06 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 11:06 Sent To G
Notes
2007-11-08 11:06:41TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-24 Cont ID  
Sent By mperson Date 2007-10-24 Time 15:35 Rev Time 0.00
Received By mperson Date 2007-10-11 Time 10:41 Sent To  
Notes
2007-10-11 10:47:46TO "G" BOX