Plan Review Details - Permit 07100288
Plan Review Stops For Permit 07100288
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-10-29 Cont ID  
Sent By jwitmer Date 2007-10-29 Time 11:19 Rev Time 2.22
Received By jwitmer Date 2007-10-29 Time 07:32 Sent To  
Notes
2007-10-29 11:22:01 
  
 BUILDING PROVISO:
 07100288
 525 S. FLAGLER DR
  
  
 TO BE IN PLACE AT C.O.:
  
  
 PUBLIC POOLS
 424.1.3.1.9 ALL PUBLIC POOLS SHALL BE SURROUNDED BY A
 MINIMUM 48" IN HEIGHT FENCE. A SELF LATCHING SELF
 CLOSING LOCKABLE GATE OF 48" MINIMUM HEIGHT WITH THE
 LATCH LOCATED NEAR THE TOP. SAFETY COVERS THAT COMPLY
 WITH ASTM F 1346 DO NOT SATIFY THIS REQUIREMENT.
  
 13-412.1ABC2.6.2 POOL COVERS. HEATED POOLS SHALL BE
 EQUIPPED WITH A VAPOR RETARDANT POOL COVER ON OR AT THE
 WATER SURFACE. POOLS HEATED TO MORE THAN 90 DEGREES
 (F)
 SHALL HAVE A POOL COVER WITH A MINIMUM INSULATION VALUE
 OF R-12.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-07 Cont ID  
Sent By dpalmer Date 2007-12-07 Time 16:57 Rev Time 0.00
Received By dpalmer Date 2007-12-07 Time 16:57 Sent To  
Notes
2007-12-07 16:57:14**** PROVISO ****
  
 1) NOTE: ALL EQUIPMENT SHOWN IS EXISTING AND IS TO BE
 REPLACED.PANELS ARE TO REMAIN AS IS. ALL ELECTRICAL
 PANELS SHALL BE INSPECTED IN FIELD FOR CONDITION FOR
 DETERIORATING CONDITIONS PER 110.11.
 PROVIDE REVISED PANEL SCHEDULES BEFORE FINAL ALONG WITH
 ANY OTHER CHANGES FOR NEW TO BE INSTALLED.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-30 Cont ID  
Sent By dpalmer Date 2007-10-30 Time 11:08 Rev Time 0.00
Received By dpalmer Date 2007-10-30 Time 11:08 Sent To  
Notes
2007-10-30 11:08:57** DENIED REVIEW **
  
  
 1) NOTE: PLEASE PROVIDE INFORMATION ON THE ELECTRICAL
 PANEL AS SHOWN IF THIS EXISTS OR OF THIS IS NEW. PLEASE
 PROVIDE OVER CURRENT PROTECTION, FEEDERS AND LOADS ON
 WHERE THIS IS BEING FED FROM.
 PLEASE CORRELATE ALL ELECTRICAL ON PLANS WITH THE
 CIRCUITS TO BE SHOWN ON PANEL SCHEDULE. PLEASE SEE
 PANEL SCHEDULE SHOWS ONLY THREE PUMPS.
 PLEASE CLARIFY WHERE LIGHTING IS BEING FED FROM. NOT
 LISTED ON PANEL SCHEDULE OR PANEL EQUIPMENT SCHEDULE.
 PLEASE BE SURE TO SHOW DETAIL ON LIGHTING.
 NEC. 680, 240.4, 310.16, 220, ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-11-30 Cont ID  
Sent By mperson Date 2007-11-30 Time 09:36 Rev Time 0.00
Received By mperson Date 2007-11-30 Time 09:36 Sent To PC
Notes
2007-11-30 09:37:48NOTE: POOL HEATERS ARE EXISITNG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 15:03 Sent To  
Notes
2007-12-06 15:06:39TO "COMM" BD#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-30 Cont ID  
Sent By mperson Date 2007-11-30 Time 09:37 Rev Time 0.00
Received By mperson Date 2007-10-10 Time 16:07 Sent To  
Notes
2007-10-26 15:54:22TO "COMM" BD#6
2007-10-10 16:08:22WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-11-17 Cont ID  
Sent By rregueir Date 2007-11-17 Time 14:51 Rev Time 0.00
Received By rregueir Date 2007-11-17 Time 14:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By mperson Date 2007-12-12 Time 06:03 Rev Time 0.00
Received By mperson Date 2007-12-12 Time 06:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-11-30 Cont ID  
Sent By mperson Date 2007-11-30 Time 08:27 Rev Time 0.00
Received By mperson Date 2007-11-30 Time 08:27 Sent To G
Notes
2007-11-30 09:35:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2 COMMERCIAL POOL RENOVATION, EXISTING WEST
 POOL PLAN PIPING: EXISTING GUTTER DRAINS INDICATE (16
 PLACES), THE PLANS ARE INDICATING 12 GUTTER DRAINS.
 PLEASE CORRELATE THIS ON THE RESUBMITTAL. PER *106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. SHEET A-2: THE RELOCATED DRAIN INLET INDICATED ON
 SHEET A-1 POOL DECK PLAN-DEMOLITION BY THE STEPS IS
 MISSING. PLEASE CLARIFY OR CORRECT THIS ON THE
 RESUBMITTAL. PER *106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. SHEET A-3: DELETE THE STUDOR VENT ON THE "CROSS
 SECTION THRU PLANTER W/NEW DRAIN SYSTEM". A STUDOR VENT
 IS NOT REQUIRED ON THE STORM DRAINAGE SYSTEM BECAUSE
 THERE ARE NO TRAPS ON THE SYSTEM.
  
 4. SHEET A-3 "DECK DRAIN- CROSS SECTION" DETAIL: THE
 INDICATED TILE TECH PEDESTAL SYSTEM APPEARS TO OBSTRUCT
 THE DRAINAGE TO THE INDICATED DECK DRAINS BELOW THIS
 SYSTEM. PLEASE PROVIDE INFORMATION ON HOW THIS SYSTEM
 WILL WORK AND BE CODE COMPLIANT TO *1106.3 BUILDING
 STORM DRAINS AND SEWERS, AND PER *106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 5. SHEET A-2: PLEASE CLEARLY INDICATE WHICH DRAINS ARE
 LOCATED IN THE TILE TECH PEDESTAL SYSTEM ON THIS SHEET.
 PER *106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 6. DOES THIS EXISTING DECK HAVE ANY SECONDARY
 (EMERGENCY) DRAINAGE? WITH THE NEW ELEVATIONS OF THE
 DECK WITH THE INSTALLATION OF THE TILE TECH PEDESTAL
 SYSTEM DOES THIS EFFECT ANY EXISTING SECONDARY
 (EMERGENCY) DRAINAGE. PER *1107 SECONDARY (EMERGENCY)
 ROOF DRAINAGE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-10-22 Cont ID  
Sent By mflis Date 2007-10-22 Time 11:42 Rev Time 0.00
Received By mflis Date 2007-10-22 Time 11:42 Sent To E
Notes
2007-10-22 11:43:09ZONING REVIEW: PASSED
  
 * POOL MODIFICATIONS OF EXISTING FACILITIES
  
 MATT FLIS - 822-1445