Plan Review Details - Permit 07100273
Plan Review Stops For Permit 07100273
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-17 Cont ID  
Sent By rmcdouga Date 2007-10-17 Time 14:06 Rev Time 0.00
Received By rmcdouga Date 2007-10-17 Time 14:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By rmcdouga Date 2007-10-10 Time 18:22 Rev Time 0.00
Received By rmcdouga Date 2007-10-10 Time 18:22 Sent To  
Notes
2007-10-10 18:34:58REROOF FLAT DECK
 2004 FBC W/2007 REVISIONS
 SPECIFIED FASTENING OPTION #2 ON PAGE 33 OF NOA
  
 DENIED BY BUILDING
  
 1) THE FASTENER SPACING SPECIFIED IS NOT ADEQUATE TO
 MEET THE SPECIFIED UPLIFT PRESSURES IN PERIMETER AND
 CORNER AREAS. SUBMIT RAS 117 CALCULATIONS AS REQUIRED
 BY LIMITATION #7 ON PAGE 34 OF NOA 05-0830.10.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714