Plan Review Details - Permit 07100272
Plan Review Stops For Permit 07100272
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-29 Cont ID  
Sent By btrobaug Date 2008-01-29 Time 11:46 Rev Time 0.00
Received By btrobaug Date 2008-01-29 Time 11:23 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By btrobaug Date 2007-10-11 Time 11:05 Rev Time 0.00
Received By btrobaug Date 2007-10-11 Time 10:30 Sent To I
Notes
2007-10-11 11:05:34 
  
 APPLICATION # 07100272
 ELECTRICAL PLAN REVIEW
 1020 PASEO ANDORRA
 10/11/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. A
 METER IS DRAWN ON THE RISER BUT A ?METER/MAIN? IS
 INDICATED. THERE IS NO EQUIPMENT GROUND TO THE PANEL
 SHOWN, IT IS UNCLEAR IF THE PANELIS PART OF THE
 ?METER/MAIN? OR STAND ALONE.
  
 2} PROVIDE AN AIC RATING FOR THE NEW EQUIPMENT BEING
 INSTALLED PER 110.9 AND110.10.
  
 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE. THE NOTES (11) REFERENCE 2002 NEC.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 5} A RECEPTACLE NEEDS TO BE ADDED OR THE ONE SHOWN
 RELOCATED, TO COMPLY WITH 210.52(A)(1) IN THE ?PATIO,
 WHICH IS NOW A HABITABLE ROOM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 11:59 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 11:59 Sent To E
Notes
2008-01-28 12:00:11TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-11 Cont ID  
Sent By btrobaug Date 2007-10-11 Time 11:06 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 10:43 Sent To PC
Notes
2007-10-10 10:43:16TO "E" BOX