| 2007-11-28 19:04:06 | PROJECT: 854 CONNISTON ROAD/# 07100262 |
| | |
| | PROJECT SCOPE: |
| | |
| | CHANGE OF OCCUPANCY: CHURCH TO THEATER |
| | REMOVE CHURCH PEWS AND INSTALL NEW SEATING,FLOORING, |
| | THEATER CURTAINS. |
| | |
| | CODE REVIEW: |
| | |
| | 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS |
| | 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS |
| | CITY OF WEST PALM BEACH ADMINISTRATION AMENDMENTS, |
| | CHAPTER 1, 2004 EDITION |
| | |
| | STATUS: FAILED |
| | |
| | COMMENTS: |
| | |
| | ****PLEASE REVISE PROJECT DETAIL ON THE PERMIT |
| | APPLICATION TO REFLECT ACTUAL WORK COMPLETED.***** |
| | |
| | 1) PLEASE INDICATE THE LEVEL OF ALTERATION: |
| | |
| | 301.5 . A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO SECTION |
| | 303,304 & 305 OF THIS CODE. |
| | |
| | 2)AS PER THE FBC 106.3.5, PLEASE PROVIDE THE |
| | FOLLOWING DATA: |
| | |
| | A) BUILDING CONSTRUCTION TYPE |
| | B) OCCUPANCY LOAD |
| | C) OCCUPANCY GROUP |
| | D) SPRINKLERED OR NON-SPRINKLERED. |
| | |
| | 3) PLEASE SHOW THE DIMENSIONS OF THE BUILDING AND FLOOR |
| | AREA. |
| | |
| | 4) PLEASE INDICATE THE SLOPE OF THE AISLES. |
| | |
| | 5) PLEASE INDICATE THE CLEAR WIDTH DIMENSION OF THE |
| | AISLE ACCESSWAY: |
| | |
| | 1024.10 AISLE ACCESSWAYS. |
| | |
| | THE AISLE ACCESSWAY BETWEEN ROWS OF SEATING SHALL HAVE |
| | A CLEAR WIDTH OF NOT LESS THAN 12 INCHES (305 MM), AND |
| | THE MINIMUM WIDTH SHALL BE INCREASED IN ACCORDANCE WITH |
| | SECTIONS 1024.10.2 FOR SEATING NOT AT TABLES AND |
| | SECTION 1024.10.2.2 FOR SEATING AT TABLES. THE WIDTH OF |
| | AISLE ACCESS-WAYS SHALL BE THE CLEAR HORIZONTAL |
| | DISTANCE FROM THE BACK OF THE ROW AHEAD AND THE NEAREST |
| | PROJECTION OF THE ROW BEHIND. WHERE CHAIRS HAVE |
| | AUTOMATIC OR SELF-RISING SEATS THAT COMPLY WITH ASTM F |
| | 851, TEST METHOD FOR SELF-RISING SEAT MECHANISMS, THE |
| | MEASUREMENT SHALL BE MADE WITH SEATS IN THE RAISED |
| | POSITION. WHERE ANY CHAIR IN THE ROW DOES NOT HAVE AN |
| | AUTOMATIC OR SELF-RISING SEAT, THE MEASUREMENTS SHALL |
| | BE MADE WITH THE SEAT IN THE DOWN POSITION. FOR SEATS |
| | WITH FOLDING TABLET ARMS, ROW SPACING SHALL BE |
| | DETERMINED WITH THE TABLET IN THE USEABLE POSITION. |
| | EXCEPTION: WHEN NOT MORE THAN FOUR PERSONS ARE SERVED, |
| | THERE SHALL BE NO MINIMUM CLEAR WIDTH REQUIREMENT FOR |
| | THE PORTION OF THE AISLE ACCESSWAY HAVING A LENGTH NOT |
| | EXCEEDING 6 FEET (1.8 M) MEASURED FROM THE CENTER OF |
| | THE SEAT FARTHEST FROM THE AISLE. |
| | |
| | 6) PLEASE INDICATE THE EGRESS TRAVEL DISTANCE TO THE |
| | EXIT DOORS, COMMON PATH OF TRAVEL, |
| | EXIT LIGHTS: PROVIDE LIFE SAFETY PLAN AS PER THE |
| | FOLLOWING: |
| | |
| | FLORIDA EXISTING BUILDING CODE |
| | |
| | 812.4FIRE AND LIFE SAFETY. |
| | THE FIRE AND LIFE SAFETY PROVISIONS OF THIS SECTION |
| | SHALL BE APPLICABLE TO BUILDINGS OR PORTIONS OF |
| | BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 7) PLEASE INDICATE THE ACCESSIBLE PARKING AND THE |
| | ACCESSIBLE ROUTE: |
| | |
| | 806.1GENERAL. |
| | ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A |
| | CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| | CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 8) PLEASE PROVIDE |
| | CLASSIFICATIONS/SPECIFICATIONS/TESTING RESULTS FOR THE |
| | WALL AND CEILLING INTERIOR FINISHES. ALL MATERIALS |
| | SHALL COMPLY WITH THE FOLLOWING: |
| | |
| | FLORIDA EXISTING BUILDING CODE |
| | |
| | 812.3.1MINIMUM REQUIREMENTS. |
| | REGARDLESS OF T HE OCCUPANCY GROUP INVOLVED, THE |
| | FOLLOWING REQUIREMENTS SHALL BE MET: |
| | 1. THE CAPACITY OF THE MEANS OF EGRESS SHALL |
| | COMPLY WITH FLORIDA BUILDING CODE, BUILDING. |
| | 2. THE INTERIOR FINISH OF WALLS AND CEILINGS SHALL |
| | COMPLY WITH THE REQUIREMENTS OF THE FLORIDA BUILDING |
| | CODE, BUILDING FOR THE NEW OCCUPANCY GROUP. |
| | 3. COMPLIANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | FLORIDA BUILDING CODE |
| | |
| | 803.1 GENERAL. |
| | |
| | INTERIOR WALL AND CEILING FINISHES SHALL BE |
| | CLASSIFIED IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR |
| | FINISH MATERIALS SHALL BE GROUPED IN THE FOLLOWING |
| | CLASSES IN ACCORDANCE WITH |
| | THEIR FLAME SPREAD AND SMOKE-DEVELOPED INDEX. |
| | |
| | CLASS A: |
| | FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX |
| | 0-450. |
| | CLASS B: |
| | FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX |
| | 0-450. |
| | CLASS C: |
| | FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX |
| | 0-450. |
| | EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN |
| | ACCORDANCE WITH SECTION 803.2. |
| | 803.2INTERIOR WALL OR CEILING FINISHES OTHER THAN |
| | TEXTILES. |
| | INTERIOR WALL OR CEILING FINISHES, OTHER THAN |
| | TEXTILES, SHALL BE PERMITTED TO BE TESTED IN ACCORDANCE |
| | WITH NFPA 286. FINISHES TESTED IN ACCORDANCE WITH NFPA |
| | 286 SHALL COMPLY |
| | WITH SECTION 803.2.1. |
| | |
| | 9) THE PROJECT VALUATION APPEARS TO BE LOW. PLEASE |
| | PROVIDE DOCUMENTATION TO REFLECT THE ACTUAL REMODEL |
| | COST. |
| | |
| | |
| | |
| | |
| | PLAN REVIEW: KEN CONRAD |
| | PHONE: 561.805.6666 |
| | E-MAIL: KCONRAD @WPB.ORG |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |