Plan Review Details - Permit 07100262
Plan Review Stops For Permit 07100262
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-28 Cont ID  
Sent By kconrad Date 2007-11-28 Time 19:05 Rev Time 0.00
Received By kconrad Date 2007-11-28 Time 16:00 Sent To FIRE
Notes
2007-11-28 19:04:06PROJECT: 854 CONNISTON ROAD/# 07100262
  
 PROJECT SCOPE:
  
 CHANGE OF OCCUPANCY: CHURCH TO THEATER
 REMOVE CHURCH PEWS AND INSTALL NEW SEATING,FLOORING,
 THEATER CURTAINS.
  
 CODE REVIEW:
  
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH ADMINISTRATION AMENDMENTS,
 CHAPTER 1, 2004 EDITION
  
 STATUS: FAILED
  
 COMMENTS:
  
 ****PLEASE REVISE PROJECT DETAIL ON THE PERMIT
 APPLICATION TO REFLECT ACTUAL WORK COMPLETED.*****
  
 1) PLEASE INDICATE THE LEVEL OF ALTERATION:
  
 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 2)AS PER THE FBC 106.3.5, PLEASE PROVIDE THE
 FOLLOWING DATA:
  
 A) BUILDING CONSTRUCTION TYPE
 B) OCCUPANCY LOAD
 C) OCCUPANCY GROUP
 D) SPRINKLERED OR NON-SPRINKLERED.
  
 3) PLEASE SHOW THE DIMENSIONS OF THE BUILDING AND FLOOR
 AREA.
  
 4) PLEASE INDICATE THE SLOPE OF THE AISLES.
  
 5) PLEASE INDICATE THE CLEAR WIDTH DIMENSION OF THE
 AISLE ACCESSWAY:
  
 1024.10 AISLE ACCESSWAYS.
  
 THE AISLE ACCESSWAY BETWEEN ROWS OF SEATING SHALL HAVE
 A CLEAR WIDTH OF NOT LESS THAN 12 INCHES (305 MM), AND
 THE MINIMUM WIDTH SHALL BE INCREASED IN ACCORDANCE WITH
 SECTIONS 1024.10.2 FOR SEATING NOT AT TABLES AND
 SECTION 1024.10.2.2 FOR SEATING AT TABLES. THE WIDTH OF
 AISLE ACCESS-WAYS SHALL BE THE CLEAR HORIZONTAL
 DISTANCE FROM THE BACK OF THE ROW AHEAD AND THE NEAREST
 PROJECTION OF THE ROW BEHIND. WHERE CHAIRS HAVE
 AUTOMATIC OR SELF-RISING SEATS THAT COMPLY WITH ASTM F
 851, TEST METHOD FOR SELF-RISING SEAT MECHANISMS, THE
 MEASUREMENT SHALL BE MADE WITH SEATS IN THE RAISED
 POSITION. WHERE ANY CHAIR IN THE ROW DOES NOT HAVE AN
 AUTOMATIC OR SELF-RISING SEAT, THE MEASUREMENTS SHALL
 BE MADE WITH THE SEAT IN THE DOWN POSITION. FOR SEATS
 WITH FOLDING TABLET ARMS, ROW SPACING SHALL BE
 DETERMINED WITH THE TABLET IN THE USEABLE POSITION.
 EXCEPTION: WHEN NOT MORE THAN FOUR PERSONS ARE SERVED,
 THERE SHALL BE NO MINIMUM CLEAR WIDTH REQUIREMENT FOR
 THE PORTION OF THE AISLE ACCESSWAY HAVING A LENGTH NOT
 EXCEEDING 6 FEET (1.8 M) MEASURED FROM THE CENTER OF
 THE SEAT FARTHEST FROM THE AISLE.
  
 6) PLEASE INDICATE THE EGRESS TRAVEL DISTANCE TO THE
 EXIT DOORS, COMMON PATH OF TRAVEL,
 EXIT LIGHTS: PROVIDE LIFE SAFETY PLAN AS PER THE
 FOLLOWING:
  
 FLORIDA EXISTING BUILDING CODE
  
 812.4FIRE AND LIFE SAFETY.
 THE FIRE AND LIFE SAFETY PROVISIONS OF THIS SECTION
 SHALL BE APPLICABLE TO BUILDINGS OR PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 7) PLEASE INDICATE THE ACCESSIBLE PARKING AND THE
 ACCESSIBLE ROUTE:
  
 806.1GENERAL.
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 8) PLEASE PROVIDE
 CLASSIFICATIONS/SPECIFICATIONS/TESTING RESULTS FOR THE
 WALL AND CEILLING INTERIOR FINISHES. ALL MATERIALS
 SHALL COMPLY WITH THE FOLLOWING:
  
 FLORIDA EXISTING BUILDING CODE
  
 812.3.1MINIMUM REQUIREMENTS.
 REGARDLESS OF T HE OCCUPANCY GROUP INVOLVED, THE
 FOLLOWING REQUIREMENTS SHALL BE MET:
 1. THE CAPACITY OF THE MEANS OF EGRESS SHALL
 COMPLY WITH FLORIDA BUILDING CODE, BUILDING.
 2. THE INTERIOR FINISH OF WALLS AND CEILINGS SHALL
 COMPLY WITH THE REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, BUILDING FOR THE NEW OCCUPANCY GROUP.
 3. COMPLIANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 FLORIDA BUILDING CODE
  
 803.1 GENERAL.
  
 INTERIOR WALL AND CEILING FINISHES SHALL BE
 CLASSIFIED IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR
 FINISH MATERIALS SHALL BE GROUPED IN THE FOLLOWING
 CLASSES IN ACCORDANCE WITH
 THEIR FLAME SPREAD AND SMOKE-DEVELOPED INDEX.
  
 CLASS A:
 FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX
 0-450.
 CLASS B:
 FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX
 0-450.
 CLASS C:
 FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX
 0-450.
 EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN
 ACCORDANCE WITH SECTION 803.2.
 803.2INTERIOR WALL OR CEILING FINISHES OTHER THAN
 TEXTILES.
 INTERIOR WALL OR CEILING FINISHES, OTHER THAN
 TEXTILES, SHALL BE PERMITTED TO BE TESTED IN ACCORDANCE
 WITH NFPA 286. FINISHES TESTED IN ACCORDANCE WITH NFPA
 286 SHALL COMPLY
 WITH SECTION 803.2.1.
  
 9) THE PROJECT VALUATION APPEARS TO BE LOW. PLEASE
 PROVIDE DOCUMENTATION TO REFLECT THE ACTUAL REMODEL
 COST.
  
  
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By kconrad Date 2007-10-18 Time 12:09 Rev Time 0.00
Received By kconrad Date 2007-10-18 Time 12:09 Sent To I
Notes
2007-10-18 12:14:37THE EXISTING CHURCH PEWS WERE REMOVED AND REPLACED WITH
 THEATRE SEATING. THE OCCUPANCY CLASSIFICATION WILL
 PROBABLY REMAIN AS AN "A-1". THE WORK COMPLETED IS A
 LEVEL 2 ALTERATION AND WILL REQUIRE A FULL SCOPE OF
 WORK DETAIL AND PLANS INDICATING DIMENSIONS OF EGRESS
 WIDTHS/PATH OF TRAVELS/ACCESIBILITY ROUTES/ACCESSIBLE
 BATHROOMS/FLOOR AND WALL FINISH SPECIFICATIONS ETC.
  
 ALSO, THE VALUATION SHALL BE INCREASED TO REFLECT THE
 DETAILED SCOPE OF WORK.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-11-29 Cont ID  
Sent By mawillia Date 2007-11-29 Time 13:40 Rev Time 0.00
Received By mawillia Date 2007-11-29 Time 10:36 Sent To  
Notes
2007-11-29 13:39:38*****DENIED*****
  
 01.PROVIDE A SITE PLAN SHOWING RELATIONSHIP OF THE
 BUILDING TO STREETS, ROADS, ETC.
  
 02.PLANS HAVE NO POINT OF COMPASS.
  
 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 04.PLEASE LIST THE HAZARD OF CONTENTS OF THE
 STRUCTURE CLASSIFIED AS LOW, ORDINARY, OR HIGH.
  
 05.IS THE BUILDING FIRE SPRINKLERED AND DOES IT HAVE
 A FIRE ALARM SYSTEM.
  
 06.PROVIDE THE OCCUPANT LOAD, AS IN THE NUMBER OF
 PERSONS FOR WHOM MEANS OF EGRESS AND OTHER PROVISIONS
 ARE REQUIRED, THAT ARE CHARACTERISTIC OF THE USE OF THE
 SPACE OR SHALL BE DETERMINED AS THE MAXIMUM PROBABLE
 POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER
 IS GREATER.
  
 07.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PROVIDED WITH PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH SHOWS
 TRAVEL DISTANCE TO THE EXITS.EXITS SHALL BE ARRANGED
 SO THAT THE TOTAL LENGHT OF TRAVEL FROM ANY POINT TO
 REACH AN EXIT SHALL NOT EXCEED 200 FEET OR 250 FEET IF
 THE OCCUPANCY HAS AN APPROVED SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM.
  
 09.SHOW LOCATION OF EXIT LIGHTS,EMERGENCY LIGHTS,
 AND FIRE EXTINGISHERS.
  
 10.PROVIDE INFORMATION ON THE TYPE OF COOKING
 EQUIPMENT TO BE USED IN THE CONCESSION AREA.
  
 11.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN THE CORRIDORS AND LOBBIES IN TERMS OF
 CLASS A, OR CLASS B.
  
 12.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN THE GENERAL ASSEMBLY AREA IN TERMS OF CLASS
 A, CLASS B, OR CLASS C.
  
 13.THEATER SCREENS ON WHICH PICTURES ARE PROJECTED
 SHALL BE CLASS A OR CLASS B.
  
 14.SPECIFY THE INTERIOR FLOOR FINISH IN EXIT
 ENCLOSURE, EXIT ACESS CORRIDORS AND IN OTHER SPACES AS
 CLASS I OR CLASS II.
  
 15.WORKSHOPS, STOREROOMS, PERMANENT DRESSING ROOMS,
 AND OTHER ACCESSORY SPACES CONTIGUOUS TO THE STAGE
 SHALL BE SEPARATED FROM EACH OTHER AND OTHER BUILDINGS
 BY AN 1-HOUR FIRE RESISTANCE-RATED CONSTRUCTION AND
 PROTECTED OPENINGS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-29 Cont ID  
Sent By mawillia Date 2007-11-29 Time 10:39 Rev Time  
Received By mawillia Date   Time   Sent To  
Notes
***NONE***