Plan Review Details - Permit 07100254
Plan Review Stops For Permit 07100254
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-25 Cont ID  
Sent By rmcdouga Date 2008-03-25 Time 12:23 Rev Time 0.00
Received By rmcdouga Date 2008-03-25 Time 12:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-03-20 Cont ID  
Sent By rmcdouga Date 2008-03-20 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2008-03-19 Time 17:27 Sent To  
Notes
2008-03-20 08:14:01STATUS WILL BE CHANGED TO P WHEN PLANS HAVE BEEN
 STAMPED BY PALM BEACH COUNTY FOR IMPACT FEES AND PAID
 RECIEPT IS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-25 Cont ID  
Sent By rmcdouga Date 2008-02-25 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2008-02-25 Time 12:29 Sent To  
Notes
2008-02-25 12:45:392004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ONE WALL IS LESS THAN 6 FEET FROM THE PROPERTY LINE.
 IT IS NOTED FROM THE ARCHITECT'S RESPONSE THAT THE WALL
 HAS A ONE HOUR FIRE RATING. HOWEVER, NO OPENINGS ARE
 ALLOWED IN THIS WALL PER R302.2 OPENINGS. OPENINGS
 SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF A
 DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE. IF THERE ARE NO STRUCTURES LOCATED
 ON THE ADJACENT PROPERTY WITH WALLS WITHIN SIX FEET OF
 THE ADDITION, THEN COMPLIANCE WITH R302.1 AND R302.2
 HAS BEEN MEET. PROVIDE A SURVEY OR SITE PLAN INDICATING
 THE REQUIRED SEPARATION DISTANCE.
  
 4) SPECIFY THE SIZE OF THE ATTIC VENTS SPECIFIED ON
 A-2. SHOW COMPLIANCE WITH R806.2. THE TOTAL NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN 1 TO 150 OF THE
 AREA OF THE SPACE VENTILATED.
  
 5) THE 1X BUCKS SHOWN IN DETAILS ON S-1 ARE NOT DRAWN
 THE SAME WIDTH AS THE WINDOW AND DOOR FRAMES SUCH THAT
 FULL SUPPORT OF THE FRAMES IS PROVIDED. SEE FBC
 R613.6.1.1
  
 6) THE SIMPSON HTS CONNECTORS ARE SPECIFIED IN THE
 SCHEDULE ON S-2 WITH (20) - 10D X 1-1/2" FASTENERS. THE
 SIMPSON CATALOG REQUIRES (24) - 10D X 1-1/2" FASTENERS
 TO ACHIEVE THE 1450 UPLIFT. PLEASE CORRECT.
  
 7)SUBMIT PRODUCT APPROVALS FOR THE NEW FRONT AND SIDE
 METAL DOORS (#8 IN THE SCHEDULE ON A-1). FAC RULE
 9B-72. NOTE: PRODUCT APPROVALS ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PER FBC 106.3* CITY AMENDMENTS.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF COVERING
 MATERIALS. SPECIFY THE APPROVED ASSEMBLY, FASTENING
 OPTION AND DESIGN PRESSURES. SUBMIT RAS 117
 CALCULATIONS FOR ENHANCED FASTENING.
  
 9) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 THE ANCHORS, ANCHOR SPACING, EDGE DISTANCE, GLASS
 SEPARATION DISTANCE, SPANS, ETC. SEE THE ATTACHED
 SAMPLE FORM.
  
 10)THE PRODUCT APPROVALS SUBMITTED FOR THE VINYL
 SOFFIT HAS DESIGN PRESSURES WHICH ARE TOO LOW. SEE FBC
 TABLE 1609.6C FOR COMPONENTS AND CLADDING AT
 OVERHANGS.
  
 11)THE WALL SECTION ON SHEET A-2 OF THE PLANS
 SPECIFIES A STUCCO SOFFIT. HOWEVER, PRODUCT APPROVALS
 WERE SUBMITTED FOR VINYL SOFFIT. PLEASE CLARIFY.
  
 12) IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE COMMENTS HAS
 BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-17 Cont ID  
Sent By rmcdouga Date 2008-01-17 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2008-01-17 Time 16:04 Sent To  
Notes
2008-01-17 16:35:462004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ONE WALL OF THE ADDITION IS LESS THAN 6 FEET FROM
 THE PROPERTY LINE. SHOW COMPLIANCE WITH R302.1 EXTERIOR
 WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
  
 4) SHOW COMPLIANCE WITH R806.1 AND R806.2 FOR ROOF
 VENTILATION.
  
 5) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 6) SHOW COMPLIANCE WITH R319.1 LOCATION REQUIRED. IN
 AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY TABLE
 R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE THE
 USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS. 5. WOOD SIDING, SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING HAVING A
 CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE
 GROUND.
  
 7) SHOW COMPLIANCE WITH SECTION 704
 INSPECTION FOR TERMITES
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 8) SPECIFY THE SOFFIT COVERING MATERIAL ON THE PLANS.
 IF IT IS VINYL OR ALUMINUM, SUBMIT PRODUCT APPROVALS
 WITH ADEQUATE DESIGN PRESSURES. FBC 106.1.2 CITY
 AMENDMENTS
  
 9) R613.6.1.1 UNLESS OTHERWISE TESTED, BUCKS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED.
 THE WINDOW AND EXTERIOR JAMB DETAILS ON S-1 DO NOT SHOW
 THE BUCKS FULLY SUPPORTING THE WINDOW AND DOOR FRAMES.
 PLEASE CORRECT.
  
 10) THE HTS CONNECTORS ON SHEET S-2OF THE SIMPSON
 CONNECTOR SCHEDULE HAS THE WRONG NUMBER OF FASTENERS
 SPECIFIED. THE SIMPSON CATALOG SPECIFIES 24- 10D X
 1-1/2" NAILS OR 20- 10D NAILS TO ACHIEVE THE 1450
 UPLIFT. PLEASE CORRECT.
  
 11) NOTE: SOME OF THE UPLIFTS SPECIFIED FOR THE TRUSSES
 ON THE ROOF FRAMING PLAN ON SHEET S-2 ARE LESS THAN
 SPECIFIED ON THE TRUSS DRAWINGS, HOWEVER, THE SPECIFIED
 CONNECTORS ARE ADEQUATE.
  
 12)THE NEW TRUSS LAYOUT IS REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. FBC R106.1.3.
  
 13) SHOW COMPLIANCE WITH R308.4 FOR SAFETY GLAZING IN
 THE BATHROOM WINDOW.
  
 14)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE SINGLE OUTSWING
 FRONT AND SIDE DOORS ( NUMBER 8 ON THE DOOR SCHEDULE).
 FAC RULE 9B-72.
  
 16) THE PRODUCT APPROVALS SUBMITTED FOR THE TRACO
 SINGLE HUNG WINDOWS ARE EXPIRED (SEE NOA
 NO.05-0729.03).PLEASE SUBMIT CURRENT PRODUCT
 APPROVALS AS REQUIRED BY FAC RULE 9B-72.
  
 17) SUBMIT PRODUCT APPROVALS FOR THE FLAT AND SLOPE
 ROOF COVERING MATERIALS ( APPROVED IN WRITING BY THE
 DESIGNER) . SPECIFY THE APPROVED ASSEMBLY, FASTENING
 OPTION AND DESIGN PRESSURE FOR THE FLAT ROOF WITH RAS
 117 CALCULATIONS FOR ENHANCED FASTENING.
  
 18) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 THE ANCHORS, THE ANCHOR SPACING, THE EDGE DISTANCE,
 GLASS SEPARATION, SPANS, ETC. SEE ATTACHED SAMPLE.
  
 19) SHOW COMPLIANCE WITH R310.4 THE TEMPORARY
 INSTALLATION OR CLOSURE OF STORM SHUTTERS, PANELS, AND
 OTHER APPROVED HURRICANE PROTECTION DEVICES SHALL BE
 PERMITTED ON EMERGENCY ESCAPE AND RESCUE OPENINGS
 DURING THE THREAT OF A STORM. SUCH DEVICES SHALL NOT BE
 REQUIRED TO COMPLY WITH THE OPERATIONAL CONSTRAINTS OF
 SECTION R310.1.4 . WHILE SUCH PROTECTION IS PROVIDED,
 AT LEAST ONE MEANS OF ESCAPE FROM THE DWELLING OR
 DWELLING UNIT SHALL BE PROVIDED. THE MEANS OF ESCAPE
 SHALL BE WITHIN THE FIRST FLOOR OF THE DWELLING OR
 DWELLING UNIT AND SHALL NOT BE LOCATED WITHIN A GARAGE
 WITHOUT A SIDE HINGED DOOR LEADING DIRECTLY TO THE
 EXTERIOR. OCCUPANTS IN ANY PART OF THE DWELLING OR
 DWELLING UNIT SHALL BE ABLE TO ACCESS THE MEANS OF
 ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT
 UNDER THEIR CONTROL.
  
 20) SHEET CVR-1 SPECIFIES REFERENCES FROM FBC
 RESIDENTIAL CHAPTER 44 WHICH APPLIES TO THE
 HIGH-VELOCITY HURRICANE ZONE. THEY DO NOT APPLY TO THE
 CITY OF WEST PALM BEACH, WHICH IS NOT LOCATED IN THIS
 ZONE. PLEASE CORRECT.
 THERE ARE FEES THAT ARE OWED ON THIS PERMIT WHICH MUST
 BE PAID BEFORE THE PLANS CAN BE PICKED UP.
  
 21) IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE COMMENTS HAS
 BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-31 Cont ID  
Sent By rmcdouga Date 2007-10-31 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2007-10-31 Time 09:39 Sent To  
Notes
2007-10-31 13:30:352004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ONE WALL OF THE ADDITION IS LESS THAN 6 FEET FROM
 THE PROPERTY LINE. SHOW COMPLIANCE WITH R302.1 EXTERIOR
 WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
  
 4) SHOW COMPLIANCE WITH R806.1 AND R806.2 FOR ROOF
 VENTILATION.
  
 5) SPECIFY THE STUD SPACING AT THE EXTERIOR WALLS. FBC
 106.1.2 CITY AMENDMENTS AND R602.2.2.
  
 6) SHOW COMPLIANCE WITH R403.1.4 MINIMUM DEPTH. ALL
 EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 INCHES
 (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
  
 7) SHOW COMPLIANCE WITH R319.1 LOCATION REQUIRED. IN
 AREAS SUBJECT TO DECAY DAMAGE AS ESTABLISHED BY TABLE
 R301.2(1) , THE FOLLOWING LOCATIONS SHALL REQUIRE THE
 USE OF AN APPROVED SPECIES AND GRADE OF LUMBER,
 PRESSURE TREATED IN ACCORDANCE WITH AWPA C1, C2, C3,
 C4, C9, C15, C18, C22, C23, C24, C28, C31, C33, P1, P2
 AND P3, OR DECAY-RESISTANT HEARTWOOD OF REDWOOD, BLACK
 LOCUST, OR CEDARS. 5. WOOD SIDING, SHEATHING AND WALL
 FRAMING ON THE EXTERIOR OF A BUILDING HAVING A
 CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE
 GROUND.
  
 8) SHOW COMPLIANCE WITH SECTION 704
 INSPECTION FOR TERMITES
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 9) SPECIFY THE SOFFIT COVERING MATERIAL ON THE PLANS.
 IF IT IS VINYL OR ALUMINUM, SUBMIT PRODUCT APPROVALS
 WITH ADEQUATE DESIGN PRESSURES. FBC 106.1.2 CITY
 AMENDMENTS
  
 10) SHOW COMPLIANCE WITH R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 11) R613.6.1.1 UNLESS OTHERWISE TESTED, BUCKS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED.
 THE WINDOW AND EXTERIOR JAMB DETAILS ON S-1 DO NOT SHOW
 THE BUCKS FULLY SUPPORTING THE WINDOW AND DOOR FRAMES.
 PLEASE CORRECT.
  
 12) THE HTS CONNECTORS ON SHEET S-2OF THE SIMPSON
 CONNECTOR SCHEDULE HAS THE WRONG NUMBER OF FASTENERS
 SPECIFIED. THE SIMPSON CATALOG SPECIFIES 24- 10D X
 1-1/2" NAILS OR 20- 10D NAILS TO ACHIEVE THE 1450
 UPLIFT. PLEASE CORRECT.
  
 13) NOTE: SOME OF THE UPLIFTS SPECIFIED FOR THE TRUSSES
 ON THE ROOF FRAMING PLAN ON SHEET S-2 ARE LESS THAN
 SPECIFIED ON THE TRUSS DRAWINGS, HOWEVER, THE SPECIFIED
 CONNECTORS ARE ADEQUATE.
  
 14) THE COVERSHEET FOR THE TRUSS DRAWINGS INCORRECTLY
 SPECIFIES THE 2001 FBC. THE APPLICABLE CODE FOR THIS
 PROJECT IS THE 2004 FBC. PLEASE CORRECT.
  
 15) SHOW COMPLIANCE WITH R308.4 FOR SAFETY GLAZING IN
 THE BATHROOM WINDOW.
  
 16) PLEASE CLARIFY IF THE WINDOWS AND DOORS IN THE
 EXISTING STRUCTURE ARE BEING REPLACED. IF SO THEN
 SUBMIT PRODUCT APPROVALS FOR THE FRONT DOOR AND WINDOWS
 IF DIFFERENT FROM THOSE SUBMITTED FOR THE ADDITION. FBC
 106.1.1 CITY AMENDMENTS
  
 17) THE PRODUCT APPROVALS SUBMITTED FOR THE TRACO
 SINGLE HUNG WINDOWS ARE EXPIRED (SEE NOA
 NO.05-0729.03).PLEASE SUBMIT CURRENT PRODUCT
 APPROVALS AS REQUIRED BY FAC RULE 9B-72.
  
 18) SUBMIT PRODUCT APPROVALS FOR THE FLAT AND SLOPE
 ROOF COVERING MATERIALS ( APPROVED IN WRITING BY THE
 DESIGNER) . SPECIFY THE APPROVED ASSEMBLY, FASTENING
 OPTION AND DESIGN PRESSURE FOR THE FLAT ROOF WITH RAS
 117 CALCULATIONS FOR ENHANCED FASTENING.
  
 19) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 THE ANCHORS, THE ANCHOR SPACING, THE EDGE DISTANCE,
 GLASS SEPARATION, SPANS, ETC. SEE ATTACHED SAMPLE.
  
 20) SHOW COMPLIANCE WITH R310.4 THE TEMPORARY
 INSTALLATION OR CLOSURE OF STORM SHUTTERS, PANELS, AND
 OTHER APPROVED HURRICANE PROTECTION DEVICES SHALL BE
 PERMITTED ON EMERGENCY ESCAPE AND RESCUE OPENINGS
 DURING THE THREAT OF A STORM. SUCH DEVICES SHALL NOT BE
 REQUIRED TO COMPLY WITH THE OPERATIONAL CONSTRAINTS OF
 SECTION R310.1.4 . WHILE SUCH PROTECTION IS PROVIDED,
 AT LEAST ONE MEANS OF ESCAPE FROM THE DWELLING OR
 DWELLING UNIT SHALL BE PROVIDED. THE MEANS OF ESCAPE
 SHALL BE WITHIN THE FIRST FLOOR OF THE DWELLING OR
 DWELLING UNIT AND SHALL NOT BE LOCATED WITHIN A GARAGE
 WITHOUT A SIDE HINGED DOOR LEADING DIRECTLY TO THE
 EXTERIOR. OCCUPANTS IN ANY PART OF THE DWELLING OR
 DWELLING UNIT SHALL BE ABLE TO ACCESS THE MEANS OF
 ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT
 UNDER THEIR CONTROL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2008-03-14 Cont ID  
Sent By btrobaug Date 2008-03-14 Time 10:26 Rev Time 0.00
Received By btrobaug Date 2008-03-14 Time 07:46 Sent To B
Notes
2008-03-14 10:25:57 
 PROVISO
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING. IF SUBMITTING PAGES THAT
 PREVIOULY PASSED REVIEW, INCORPORATE THEM WITH THE SET
 BEING SUBMITTED FOR THE NEXT REVIEW. ONLY SUBMIT SETS
 FROM THE LAST REVIEW, NOT ONES FROM TWO OR MORE PAST
 REVIEWS.106.3.1 FBC AS AMMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-02-20 Cont ID  
Sent By btrobaug Date 2008-02-20 Time 16:06 Rev Time 0.00
Received By btrobaug Date 2008-02-19 Time 07:06 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-09 Cont ID  
Sent By btrobaug Date 2008-01-09 Time 10:29 Rev Time 0.00
Received By btrobaug Date 2008-01-09 Time 07:10 Sent To P
Notes
2008-01-09 10:30:19 
  
 TO JOHNS DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By btrobaug Date 2007-10-12 Time 08:38 Rev Time 0.00
Received By btrobaug Date 2007-10-12 Time 07:22 Sent To M
Notes
2007-10-12 08:38:53 
  
  
 APPLICATION #07100254
 ELECTRICAL PLAN REVIEW
 623 47TH STREET
 10/12/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET A-1, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 1} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 2} THE 50 AMP OCP FOR THE AHU IN THE PANEL DOES NOT
 CORRELATE WITH THE MAXIMUM FUSE SIZE GIVEN FOR THAT
 UNIT ON SHEET M-1, 45 AMPS.
  
 3} THE PANEL LOCATION IS IN VIOLATION OF 110.26
 CLEARANCE REQUIREMENTS (3?), WITH REGARD TO THE WASHER
 AND POSSIBLY THE WATER HEATER.
  
 4} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A)(1). THE PANEL IS LISTED AS MLO. THE AHJ HAS
 DETERMINED THAT ?NEAREST POINT OF ENTRANCE? SHALL BE NO
 FARTHER THAN 8? OF UNPROTECTED CONDUCTORS.
  
 5} THE APPLICATION INDICATES A DINING ROOM IS TO BE
 ADDED, THAT ROOM IS NOT SHOWN ON THE FLOOR PLAN AND
 WOULD BE SUBJECT TO 210.52(B)(1), SMALL APPLIANCE
 CIRCUIT. CORRELATE THE SCOPE ON THE APPLICATION WITH
 THE PLANS, 106.1.1 FBC AS AMENDED.
  
 6} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THIS
 INCLUDES THE COUNTER BETWEEN THE RANGE AND
 REFRIGERATOR.
  
 7} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), THERE IS NO BATH CIRCUIT LISTED ON
 THE PANEL SCHEDULE.
  
 8} A RECEPTACLE PER 210.63 IS REQUIRED FOR THE A/C
 CONDENSER.
  
 9} THE LOCATION SHOWN FOR THE DISCONNECTING MEANS FOR
 THE CONDENSER IS IN VIOLATION OF 110.26.
  
 10} THE STATE OF FLORIDA PER 553 FS HAS ADOPTED THE
 2004 FBC AND ALL REFERENCED MATERIAL. PLEASE CHANGE ALL
 NOTES TO REFLECT THIS CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 08:56 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 08:56 Sent To Z
Notes
2008-03-11 08:56:37TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-14 Cont ID  
Sent By adarroug Date 2008-02-14 Time 09:19 Rev Time 0.00
Received By adarroug Date 2008-02-14 Time 09:19 Sent To Z
Notes
2008-02-14 09:20:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-07 Cont ID  
Sent By adarroug Date 2008-01-07 Time 08:26 Rev Time 0.00
Received By adarroug Date 2008-01-07 Time 08:26 Sent To Z
Notes
2008-01-07 08:27:08TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-31 Cont ID  
Sent By rmcdouga Date 2007-10-31 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2007-10-10 Time 10:35 Sent To  
Notes
2007-10-10 10:35:45TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-22 Cont ID  
Sent By tgordon Date 2008-02-22 Time 10:32 Rev Time 0.30
Received By tgordon Date 2008-02-22 Time 10:32 Sent To B
Notes
2008-02-22 10:33:50REVIEWED AND STAMPED ON 1-10-08.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-10 Cont ID  
Sent By tgordon Date 2008-01-10 Time 10:55 Rev Time 0.30
Received By tgordon Date 2008-01-10 Time 10:55 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By tgordon Date 2007-10-16 Time 11:41 Rev Time 0.30
Received By tgordon Date 2007-10-16 Time 11:41 Sent To P
Notes
2007-10-16 11:51:31PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN PAGE M-1. THE SITTING ROOM WILL
 REQUIRE RETURN AIR, SEE 2004 FBC/R M1602.4.
  
 2) MECHANICAL PLAN PAGE M-1. THE ARCHITECT NEEDS TO
 SHOW THE DATE WERE HE SIGNED AND SEALED THE PLAN, SEE
 FAC 61G1-16.004 (5).
  
 3) MECHANICAL PLAN PAGE M-1. EQUIPMENT SCHEDULE SHOWS
 FUSE SIZE FOR AHU TO BE 45 AMP, ELECTRICAL PLAN SHOWS
 50 AMP, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-03-20 Cont ID  
Sent By jleech Date 2008-03-20 Time 07:36 Rev Time 0.00
Received By jleech Date 2008-03-20 Time 07:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-03-13 Cont ID  
Sent By jleech Date 2008-03-13 Time 07:24 Rev Time 0.00
Received By jleech Date 2008-03-13 Time 07:11 Sent To E
Notes
2008-03-13 07:28:11DENIED;
 PLANS WERE RED LINED THE LAST TIME TRUE, CHANGES WERE
 NOT MADE ON NEW SET OF PLANS. THE AUTOMATIC CLOTHES
 WASHER MUST DISCHARGE DOWN STREAM OF THE BATHROOM
 GROUP. SEE FBC-PLUMBING SECTION 909.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-02-22 Cont ID  
Sent By jleech Date 2008-02-22 Time 07:29 Rev Time 0.00
Received By jleech Date 2008-02-22 Time 07:28 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-10 Cont ID  
Sent By jleech Date 2008-01-10 Time 09:47 Rev Time 0.00
Received By jleech Date 2008-01-10 Time 09:47 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By jleech Date 2007-10-25 Time 13:22 Rev Time 0.00
Received By jleech Date 2007-10-25 Time 13:09 Sent To B
Notes
2007-10-25 13:21:52DENIED;
 1. FLOOR PLANS ON A-1 DO NOT MATCH. ELECTRICAL PLAN
 SHOWS WATER HEATER IN A DIFFERENT LOCATION THAN FLOOR
 PLAN. THIS WILL MAKE A DIFFERANCE WHEN ROUGHING IN THE
 ELECTRIC AND PLUMBING.
 2. THE AUTOMATIC CLOTHES WASHER DISCHARGE IS NOT
 PERMITED TO RUN THRU A BATHROOM GROUP. SEE FBC-PLUMBING
 SECTION 909.1.
 3. W/M BRANCH DRAIN TO BE 3" TO THE WASTE ARM SECTION
 406.3. A CLEANOUT TO BE INSTALLED AT 48" OFF FINISH
 FLOOR.
 4. SIZE ALL PIPES ON RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2008-03-12 Cont ID  
Sent By choops Date 2008-03-12 Time 09:55 Rev Time 0.00
Received By choops Date 2008-03-12 Time 09:55 Sent To P
Notes
2008-03-12 10:04:47***APPROVED - RESUB #3***
  
  
  
  
 SENT TO "P" - JL

Review Stop Z ZONING
Rev No 3 Status F Date 2008-02-15 Cont ID  
Sent By choops Date 2008-02-15 Time 13:55 Rev Time 0.00
Received By choops Date 2008-02-15 Time 13:55 Sent To E
Notes
2008-02-15 13:56:34***FAILED - RESUB #2***
  
  
 REPEAT COMMENT:
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
 AGAIN, NO LANDSCAPE PLAN HAS BEEN SUBMITTED.ALSO, NO
 SITE PLAN WAS SUBMITTED ON THIS SUBMITTAL.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-08 Cont ID  
Sent By choops Date 2008-01-08 Time 08:19 Rev Time 0.00
Received By choops Date 2008-01-08 Time 08:19 Sent To E
Notes
2008-01-08 08:21:57***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
 NEW COMMENT:
  
 1)AS THERE WAS NO SURVEY PROVIDED WITH THIS
 SUBMITTAL, TWO (2) COPIES OF A CURRENT SURVEY SHALL BE
 PROVIDED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By choops Date 2007-10-11 Time 09:45 Rev Time 0.00
Received By choops Date 2007-10-11 Time 09:45 Sent To B
Notes
2007-10-11 09:47:57***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.NOTE:PURSUANT TO
 SECTION 94-305(B)(4) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4' INTO A REQUIRED SETBACK.
  
 2)AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE VALUE OF THE EXISTING STRUCTURE LANDSCAPING SHALL
 BE BROUGHT TO COMPLIANCE WITH SECTION 94-442 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720