| Plan Review Stops For Permit 07100253 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-10 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-10 |
Time |
13:21 |
Sent To |
I |
|
| Notes |
| 2007-10-10 13:22:42 | | | | | | | | | | PROVISO | | | | | | 230.70 GENERAL. | | | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN | | | A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE | | | CONDUCTORSTHE AHJ HAS DETERMINED THAT "NEAREST POINT OF | | | ENTRANCE" SHALL BE NO FARTHER THAN 8' OF UNPROTECTED | | | CONDUCTORS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-10 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-10 |
Time |
09:36 |
Sent To |
PC |
|
| Notes |
| 2007-10-10 09:36:39 | TO "E" BOX |
|
|
|