Plan Review Details - Permit 07100247
Plan Review Stops For Permit 07100247
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-22 Cont ID  
Sent By jgomez Date 2008-01-22 Time 11:08 Rev Time 0.00
Received By jgomez Date 2008-01-22 Time 11:08 Sent To PC
Notes
2008-01-22 11:38:29RESPONSE TO PROVISO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-11 Cont ID  
Sent By jgomez Date 2008-01-11 Time 15:34 Rev Time 0.00
Received By jgomez Date 2008-01-11 Time 15:34 Sent To PC
Notes
2008-01-11 15:37:22BUILDING REVIEW APPROVED WITH PROVISO:
 1-SHEET #1:ENGINEER TO REVISEDESIGN DATA NOTE #2.
 SEE SEC. R606.4 FOR MINIMUM COMPRESSIVE STRESS
 REQUIRED FOR CONCRETE BLOCK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-04 Cont ID  
Sent By jgomez Date 2008-01-02 Time 17:01 Rev Time 0.00
Received By jgomez Date 2008-01-02 Time 15:56 Sent To PC
Notes
2008-01-02 17:02:01RESIDENTIAL ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1-SECOND FLOOR PLAN SPECIFIES THEGUEST BEDROOM
 CENTER WINDOW AS THE EGRESS WINDOW,WHILE EXTERIOR
 SOUTH ELEVATION SPECIFIES THE SIDE WINDOWS AS THE
 EGRESS WINDOWS.CLARIFY WHICH ONE IS THE EGRESS
 WINDOW.
  
 2- PROVIDE COMPLETE SPECIFICATIONS/DETAILS FOR
 FIREBLOCKING IN THE WALL SECTIONS.FIREBLOCKING IS NOT
 ONLY REQUIRED BETWEEN FIRST AND SECOND FLOOR, BUT
 BETWEEN TOP WALL AND CEILING AS WELL. SEC. R602..1.2 OF
 2004 FLORIDA RESIDENTIAL CODE.PROVIDE INFORMATION AS
 REQUIRED. (REPEAT COMMENT. COMMENT PARTIALLY
 ADDRESSED).
  
 3-SPECIFY CEILING FAN SIZES IN ALL ROOMS AS REQUIRED
 BY TABLE 13-607.1.A.1 FBC 2004 SINCE ENERGY
 CALCULATIONS ARE TAKEN THE CEILING FANS CREDIT. (REPEAT
 COMMENT).
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) OPERABLEWINDOWS FOR DOUBLE AND SINGLE CASEMENT
 WINDOWS AS SHOWN ON PLANS.PRODUCT APPROVALNOA
 07-0524.06 SUBMITTED DOESN'T COVER THESE WINDOWS.
 B) EXTERIORSWING DOOR AT MUD ROOM AS SHOWN ON
 EXTERIOR SOUTH ELEVATION. ONLY PRODUCT APPROVAL FOR
 FRENCH DOORS WAS SUBMITTED.
 C) ALL SIMPSON STRUCTURAL CONNECTORS. PROVIDE 2
 COPIES ONLY ONE WAS SUBMITTED.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.THERE ARE SOME PRODUCT
 APPROVALS WHICH ONLYONE COPY WAS SIGNED OFF AS
 REVIEWED AND APPROVED.PLEASE RESUBMIT COMPLETE
 PRODUCT APPROVALS PACKAGE.ALSO,WRITE THE NAME OF
 ARCHITECT REVIEWING THE PRODUCT APPROVAL. SEC. 106..3.3
 CITY AMENDMENTS TO FBC 2004.
  
 6- REVISED PLANS SPECIFY ICYNENE INSULATION NOW.
 PROVIDE COMPLETELISTING AND MANUFACTURER'S SPECS TO
 VERIFY COMPLIANCE WITHSECTION R314 OF 2004 FLORIDA
 RESIDENTIAL CODE. AND TO VERIFY COMPLIANCE WITH
 SPECIFIED R-VALUE OF R-30. ALSO, ARCHITECT TO
 COORDINATE WITH ENERGY CALCULATIONS PRIOR TO
 SUBMITTAL.
  
 7-SHEET 7:REVISE EMBEDMENT SPECIFIED FOR 5" ANCHOR
 BOLTS THRU 3X8 LEDGER.IT CAN'T BE 3 1/2" EMBEDMENT.
  
 8-SHEET 8: REVISE HEADROOM CLEARANCE IN SECTION 1/8.
 SEE SEC.R311.5.2 OF 2004 FLORIDA RESIDENTIAL CODE TO
 CHECK PROPER WAY OF PROVIDING DIMENSION.ANDPROVIDE
 DIMENSION INFEET AND INCHES.
  
 9- SHEET 10: REVISE DESIGN DATA NOTE #2. SEE SEC.
 R606.4 FOR MINIMUM COMPRESSIVE STRESS REQUIRED FOR
 CONCRETE BLOCK.(REPEAT COMMENT).ENGINEER CAN'T
 LOWER THE MINIMUMCOMPRESSIVE STRESS REQUIRED BY THE
 CODE. REVISE AS REQUIRED.
  
 10- NOTICE OF COMMENCEMENT WAS NOT SUBMITTED THIS TIME.
 THIS LEGAL DOCUMENT NEEDS TO BE SIGNED BY THE OWNER.
 OTHERWISE, PROVIDE LEGAL DOCUMENTATION AND FLORIDA
 STATUTE SECTIONTHAT ALLOWS THE CONTRACTOR TO SIGN IT
 ON BEHALF OF THE OWNER.
  
 11- PERMIT APPLICATION IS MISSING THE SECOND PAGE.
 PROVIDECOMPLETE PERMIT APPLICATION.
  
 12-PERMIT VALUATION WAS UPDATED ONCE THAT AREA
 TABULATION WAS PROVIDED IN THE PLANS. OWES $934.73 FOR
 PERMIT VALUATION AND RADON FEES AS REQUIRED BY SEC.
 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-11-06 Cont ID  
Sent By jgomez Date 2007-11-06 Time 15:07 Rev Time 0.00
Received By jgomez Date 2007-11-06 Time 07:36 Sent To PC
Notes
2007-11-06 15:46:44RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW
 UNDER EXISTING BUILDING CODE 2004,FLORIDA RESIDENTIAL
 CODE 2004 AND FBC 2004 WITH 2007 REVISIONS.
  
 1- BRING PLANS TO PALM BEACH COUNTYAT 2300 N. JOG RD.
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 2- NOTICE OF COMMENCEMENT WAS SIGNEDBY THE
 CONTRACTOR. THIS SPACE IS TO BE SIGNED BY THE OWNER.
 OTHERWISE PROVIDE LEGAL DOCUMENTATION SHOWING THE
 CONTRACTOR AS THE OWNER'S AUTHORIZED
 OFFICER/DIRECTOR/PARTNER/MANAGER. PROVIDE REVISED AND
 RE-RECORDED NOTICE OF COMMENCEMENT AS REQUIRED.
  
 3- PLANS TO SPECIFY AREA TABULATION, INCLUDING THE
 LOGGIA AREA TO PROPERLY EVALUATE THE BUILDING PERMIT
 VALUE AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC
 2004.
  
 4- NORTH WALL OF PROPOSED ADDITION IS LESS THAN 6'-0"
 FROM THE PROPERTY LINE, THEREFORE NEED TO SPECIFY ONE
 HOUR FIRE RATED WALL(FROM INSIDE AND OUTSIDE) AS
 REQUIRED BY SEC. R302.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 5- OPENINGS IN NORTH WALL ARE NOT ALLOWED AS REQUIRED
 BY SEC. R302.2 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 6- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO
 THE MUD ROOM TO COMPLY WITHSEC. R309.1 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 7- REVISE ROOF SHEATHING FASTENING SPACING FOR FLAT
 ROOF AT ZONE 3AND SECOND FLOOR ROOF AT ZONE 3
 SHEATHING AS REQUIRED BY SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE.NAILS TO BE 4"O.C.
 MINIMUM.
  
 8- PROVIDE COMPLETESPECIFICATIONS FOR NAILING OF 2X6
 TONGUE AND GROVE ROOF SHEATHING IN LOGGIA ROOF TO
 VERIFY COMPLIANCEWITH CALCULATED UPLIFT LOADS.SEC.
 R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 9- ARCHITECTURAL PLANS NEED TO SPECIFY TYPE OF WINDOWS
 AND SIZES.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH EGRESS REQUIREMENTS AND ENERGY
 CALCULATIONS AS REQUIRED CHAPTER 13 OF FBC 2004.
  
 10- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 11- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR
 FIREBLOCKING SHOWING COMPLIANCE WITH SEC. R602.1.2 AND
 SEC. R602.1.2.1 OF 2004 FLORIDA RESIDENTIAL CODE.
 PROVIDE INFORMATION IN ALL WALL SECTIONS AND STAIRS.
  
 12- ENERGY CALCULATIONS:
 A) NEED TO COMPLETE REVISED FORM 600A-2004R.
  
 B) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 C) REVISE OVERHANG LENGTH AND OVERHANG HEIGHT.IT
 CAN'T BE ZERO. SEE PLANS AND REVISE AS REQUIRED. SEE
 SEC. R601.1.ABC.3 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 D) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS
 NEED TO PROVIDEALL HIS INFORMATION AS REQUIRED BY
 SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 E) ARCHITECT TO PROVIDE HIS INFORMATION AND SEAL AS
 REQUIRED BY SEC. 61G1-16.003 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 13- IF ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT, THEN DRAWINGS NEED TO SHOW CEILING FAN SIZE IN
 ALL ROOMS. SEE TABLE 13-607.1.A.1 FBC 2004 FOR MINIMUM
 SIZE OF CEILING FAN REQUIRED.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 ***ONLY PRODUCT APPROVAL FOR ROOF TILE AND ROOF TILE
 ADHESIVE WAS SUBMITTED.
  
 A) ALL FIXED AND OPERABLE WINDOWS AS SHOWN ON
 PLANS.
  
 B) ALL EXTERIOR DOORS AS SHOWN ON PLANS. FRENCH
 DOORS AND SWING DOOR AT MUD ROOM.
  
 C) WINDOW MULLIONS.
  
 D) FLAT ROOF.AND PROVIDE THE FOLLOWING
 INFORMATION:
 * IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED.
 ** CHECK IF SELECTED ASSEMBLY IS LIMTED BY GENERAL
 LIMITATION #7 OR #9. IF LIMITED BY GENERAL LIMITATION
 #9, THEN IT CAN'T BE USED IN THIS AREA. IF LIMITED BY
 GENERAL LIMTATION #7, THEN PROVIDE THE RAS 117
 CALCULATIONS TO ENHANCE NAIL FASTENING AT PERIMETER AND
 CORNER AREAS. SEE GENERAL LIMITATION #7. IF
 CALCULATIONS ARE REQUIRED TO BE BY ARCHITECT, ENGINEER
 OR REGISTERED ROOF CONSULTANT, THEN ONLY ONE OF THOSE
 PROFESSIONALS CAN PROVIDE THE CALCULATIONS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. PROVIDE PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIC CONNECTOR ONLY.
  
 F) PRECAST CONCRETE LINTELS.
  
 G) STORM SHUTTERS IF WINDOWS AND DOORS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 16- SPECIFY ROOF CROSS VENTILATION FOR FLAT AND PITCHED
 ROOFS AS REQUIRED BYSEC. R806 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 17- WINDOWS NEXT TO FRENCH DOORS IN FAMILY AREA AND
 WINDOW NEXT TO THE BATH TUB IN SECOND FLOOR REQUIRE
 SAFETY GLASS AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 18- SPECIFY FLAT ROOF SLOPE TO VERIFY COMPLIANCE WITH
 SEC. R905.9.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 19- SHEET 7: SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR
 J BOLTS AT BOTTOM PLATE OF STEEL COLUMN AND FOR ANCHOR
 BOLTS AT 3X8 LEDGERIN SECTION 1/7.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 20- SHEET 8: SPECIFY HEADROOM CLEARANCE IN SECTION 1/8
 TO VERIFY COMPLIANCE WITH SEC. R311.5.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 ***NOTE: SEE THIS CODE SECTIONTO CHECK HOW DIMENSION
 SHALL BE MEASURED.
  
 21- SHEET 10:
 A) REVISE DESIGN DATA NOTE #2. SEE SEC. R606.4 FOR
 MINIMUM COMPRESSIVE STRESS REQUIRED FOR CONCRETE
 BLOCK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-22 Cont ID  
Sent By btrobaug Date 2008-04-22 Time 11:50 Rev Time 0.00
Received By btrobaug Date 2008-04-22 Time 10:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-10 Cont ID  
Sent By btrobaug Date 2008-01-10 Time 12:50 Rev Time 0.00
Received By btrobaug Date 2008-01-10 Time 12:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-12-26 Cont ID  
Sent By btrobaug Date 2007-12-26 Time 07:56 Rev Time 0.00
Received By btrobaug Date 2007-12-26 Time 06:48 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By btrobaug Date 2007-10-12 Time 14:21 Rev Time 0.00
Received By btrobaug Date 2007-10-12 Time 12:03 Sent To M
Notes
2007-10-12 14:21:44 
  
 APPLICATION #07100247
 ELECTRICAL PLAN REVIEW
 165 ELWA PL
 10/12/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET 11, UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} 230.2 ALLOWS ONLY ONE SERVICE TO A BUILDING.
 INDICATE WHICH EXCEPTION, IF ANY, ALLOWS TWO SERVICES
 TO THIS RESIDENCE.
  
 2} THERE IS NO GROUNDING ELECTRODE CONDUCTOR SHOWN FOR
 THE SECOND SERVICE IF ALLOWED. 250.66.
  
 3} IF ALLOWED, THE SECOND DISCONNECTING MEANS MUST
 COMPLY WITH 110.9 AND 110.10: OBTAIN THE AVAILABLE
 FAULT CURRENT AT THE UTILITY AND CALCULATE THE SAME AT
 THE EQUIPMENT. INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN THE AVAILABLE
 FAULT.
  
 4} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. THE
 COUNTERTOP SPACING DOES NOT COMPLY.
  
 5} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63.
  
 6} SHEET #12. THE RECEPTACLE SPACING IN THE GUEST BATH
 MUST MEET 210.52(D). ONE NEEDS TO BE ADDED OR
 RELOCATED.
  
 7} THERE IS A NOTE REGARDING A PUMP RECEPTACLE. IF FOR
 A WHIRLPOOL OR JACUZZI, THERE IS NONE LISTED ON THE
 SCHEDULES. ALSO SEE 210.23(A)(2) FOR LOADING ON THE
 BATH CIRCUIT.
  
 8} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. THERE IS
 NONE SHOWN ON THE FIRST FLOOR AT THE STAIR. THIS
 APPLIES TO THE ALARMS IN THE ENTIRE RESIDENCE AS IT IS
 A SINGLE FAMILY DWELLING. A NOTE ALONG THOSE LINES,
 ALTHOUGH NOT AN ISSUE WITH THE NEC, ZONING MAY NOT
 ALLOW A SECOND KITCHEN IN A SINGLE FAMILY RESIDENCE.
  
 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
  
 ANSWER REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-09-08 Cont ID  
Sent By adarroug Date 2008-09-08 Time 11:32 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 11:32 Sent To M
Notes
2008-09-08 11:33:03TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-07-14 Cont ID  
Sent By adarroug Date 2008-07-14 Time 16:41 Rev Time 0.00
Received By adarroug Date 2008-07-14 Time 16:41 Sent To M
Notes
2008-07-14 16:41:43TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-22 Cont ID  
Sent By adarroug Date 2008-05-22 Time 11:45 Rev Time 0.00
Received By adarroug Date 2008-05-22 Time 11:45 Sent To M
Notes
2008-05-22 11:46:10TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-21 Cont ID  
Sent By adarroug Date 2008-04-21 Time 08:50 Rev Time 0.00
Received By adarroug Date 2008-04-21 Time 08:50 Sent To E
Notes
2008-04-21 08:52:10TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 14:20 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 14:20 Sent To B
Notes
2008-01-15 14:20:58TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-08 Cont ID  
Sent By adarroug Date 2008-01-08 Time 16:00 Rev Time 0.00
Received By adarroug Date 2008-01-08 Time 16:00 Sent To Z
Notes
2008-01-08 16:00:44TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 17:24 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 17:23 Sent To Z
Notes
2007-12-19 17:24:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-06 Cont ID  
Sent By jgomez Date 2007-11-06 Time 15:46 Rev Time 0.00
Received By jgomez Date 2007-10-10 Time 08:55 Sent To  
Notes
2007-10-10 08:57:37TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-09-09 Cont ID  
Sent By tgordon Date 2008-09-09 Time 11:33 Rev Time 0.45
Received By tgordon Date 2008-09-09 Time 11:33 Sent To  
Notes
2008-09-09 11:36:48RECIVED SIGNED AND SEALED LETTER FROM THE ENGINEER
 ARNOLD I. CHANE REMOVING HIMSELF FROM THE MECHANICAL
 DESIGN.
 REVISION TO MECH. PLANS, ENERGY CAL'S AND COOLING LOAD
 CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-07-15 Cont ID  
Sent By tgordon Date 2008-07-15 Time 11:46 Rev Time 1.00
Received By tgordon Date 2008-07-15 Time 11:46 Sent To  
Notes
2008-07-15 12:15:12PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE LETTER FROM THE ENGINEER NEEDS TO BE THE
 ORIGINAL WITH THE RAISED SEAL AND SIGNATURE, NOT A COPY
 PER 2004 FAC 61G15-23.002. PLEASE HAVE THE PERMIT
 NUMBER MENTIONED IN THE LETTER ALSO.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 3) PLEASE SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS,
 AS ONLY ONE WAS SUBMITTED.
  
 4) THE ENGINEER'S NAME AND INFORMATION MUST NOT APPEAR
 ON THE REVISED PLANS AS HE IS REMOVING HIMSELF FROM THE
 PROJECT.
  
 5) SHOW THE LOCATION OF THE A/C CONDENSER UNITS ON THE
 REVISED MECHANICAL PLAN, PER 2004 FBC/R M1307.
  
 6) SHOW THE SIZE OR THE RETURN AIR TRANSFER DUCTS
 (FLEX) TO THE MUDROOM (SEE YELLOW HIGH LIGHT ON PAGE 1)
 PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-26 Cont ID  
Sent By tgordon Date 2007-12-26 Time 08:38 Rev Time 0.30
Received By tgordon Date 2007-12-26 Time 08:38 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By tgordon Date 2007-10-16 Time 13:34 Rev Time 0.30
Received By tgordon Date 2007-10-16 Time 13:34 Sent To P
Notes
2007-10-16 13:41:30PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04R,
 SEE 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1.
  
 3) SHOW THE LOCATION OF THE CONDENSER UNITS ON THE
 MECHANICAL PLANS.
  
 4) SHOW THE BATHROOM EXHAUST FANS AND CFM'S. ON THE
 MECHANICAL PLANS, SEE 2004 FBC/R 303.3 EXCEPT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-31 Cont ID  
Sent By jleech Date 2007-12-31 Time 08:51 Rev Time 0.00
Received By jleech Date 2007-12-31 Time 08:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By jleech Date 2007-10-29 Time 07:38 Rev Time 0.00
Received By jleech Date 2007-10-29 Time 07:31 Sent To B
Notes
2007-10-29 07:37:43DENIED;
 1. SHOW LOCATION, SIZE AND TYPE, OF ENERGY USED, WATER
 HEATER.
 2. KITCHEN SINK MISSING FROM SANITARY RISER DIAGRAM.
 3. AUTOMATIC CLOTHES WASHERS BRANCH DRAINS SHALL BE 3"
 SEE FBC PLUMBING SECTION 406.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-09 Cont ID  
Sent By choops Date 2008-01-09 Time 09:28 Rev Time 0.00
Received By choops Date 2008-01-09 Time 09:28 Sent To E
Notes
2008-01-09 09:29:21***APPROVED - RESUB #2***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-21 Cont ID  
Sent By choops Date 2007-12-21 Time 15:45 Rev Time 0.00
Received By choops Date 2007-12-21 Time 15:45 Sent To E
Notes
2007-12-21 15:46:57***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 NEW COMMENTS:
  
 1)INDICATE HEIGHT DIMENSION ON THE ELEVATIONS OF THE
 PROPOSED ADDITION.DIMENSIONS SHALL BE SHOWN FROM
 GRADE TO THE MIDPOINT OF THE ROOF'S PITCH AND SHALL NOT
 EXCEED 30'.
  
 2)PROVIDE A FLOOR PLAN SHOWING THE EXISTING
 STRUCTURE AND THE CORRELATION BETWEEN THE NEW AND OLD
 STRUCURE.WHERE IS THE OLD KITCHEN?
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By choops Date 2007-10-11 Time 09:26 Rev Time 0.00
Received By choops Date 2007-10-11 Time 09:26 Sent To B
Notes
2007-10-11 09:31:04***FAILED***
  
  
 1)***THE CITY COMMISSION HAS ISSUED A "ZONING IN
 PROGRESS" (ZIP) FOR LOTS FACING FLAGLER DRIVE.THIS
 PREVENTS THE ISSUANCE OF DEVELOPMENT APPROVALS AT THIS
 TIME.***
  
 OTHER COMMENTS FYI:
  
 2)INDICATE SETBACK DIMENSIONS FROM ANY PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720