| 2007-11-06 15:46:44 | RESIDENTIAL ADDITION BUILDING REVIEW CHECKLIST. REVIEW |
| | UNDER EXISTING BUILDING CODE 2004,FLORIDA RESIDENTIAL |
| | CODE 2004 AND FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTYAT 2300 N. JOG RD. |
| | TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 2- NOTICE OF COMMENCEMENT WAS SIGNEDBY THE |
| | CONTRACTOR. THIS SPACE IS TO BE SIGNED BY THE OWNER. |
| | OTHERWISE PROVIDE LEGAL DOCUMENTATION SHOWING THE |
| | CONTRACTOR AS THE OWNER'S AUTHORIZED |
| | OFFICER/DIRECTOR/PARTNER/MANAGER. PROVIDE REVISED AND |
| | RE-RECORDED NOTICE OF COMMENCEMENT AS REQUIRED. |
| | |
| | 3- PLANS TO SPECIFY AREA TABULATION, INCLUDING THE |
| | LOGGIA AREA TO PROPERLY EVALUATE THE BUILDING PERMIT |
| | VALUE AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 4- NORTH WALL OF PROPOSED ADDITION IS LESS THAN 6'-0" |
| | FROM THE PROPERTY LINE, THEREFORE NEED TO SPECIFY ONE |
| | HOUR FIRE RATED WALL(FROM INSIDE AND OUTSIDE) AS |
| | REQUIRED BY SEC. R302.1 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 5- OPENINGS IN NORTH WALL ARE NOT ALLOWED AS REQUIRED |
| | BY SEC. R302.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO |
| | THE MUD ROOM TO COMPLY WITHSEC. R309.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 7- REVISE ROOF SHEATHING FASTENING SPACING FOR FLAT |
| | ROOF AT ZONE 3AND SECOND FLOOR ROOF AT ZONE 3 |
| | SHEATHING AS REQUIRED BY SEC. R803.2.3.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE.NAILS TO BE 4"O.C. |
| | MINIMUM. |
| | |
| | 8- PROVIDE COMPLETESPECIFICATIONS FOR NAILING OF 2X6 |
| | TONGUE AND GROVE ROOF SHEATHING IN LOGGIA ROOF TO |
| | VERIFY COMPLIANCEWITH CALCULATED UPLIFT LOADS.SEC. |
| | R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- ARCHITECTURAL PLANS NEED TO SPECIFY TYPE OF WINDOWS |
| | AND SIZES.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO |
| | VERIFY COMPLIANCE WITH EGRESS REQUIREMENTS AND ENERGY |
| | CALCULATIONS AS REQUIRED CHAPTER 13 OF FBC 2004. |
| | |
| | 10- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED |
| | BY SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 11- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR |
| | FIREBLOCKING SHOWING COMPLIANCE WITH SEC. R602.1.2 AND |
| | SEC. R602.1.2.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | PROVIDE INFORMATION IN ALL WALL SECTIONS AND STAIRS. |
| | |
| | 12- ENERGY CALCULATIONS: |
| | A) NEED TO COMPLETE REVISED FORM 600A-2004R. |
| | |
| | B) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| | |
| | C) REVISE OVERHANG LENGTH AND OVERHANG HEIGHT.IT |
| | CAN'T BE ZERO. SEE PLANS AND REVISE AS REQUIRED. SEE |
| | SEC. R601.1.ABC.3 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | D) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS |
| | NEED TO PROVIDEALL HIS INFORMATION AS REQUIRED BY |
| | SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | E) ARCHITECT TO PROVIDE HIS INFORMATION AND SEAL AS |
| | REQUIRED BY SEC. 61G1-16.003 OF FLORIDA ADMINISTRATIVE |
| | CODE. |
| | |
| | 13- IF ENERGY CALCULATIONS ARE TAKING THE CEILING FAN |
| | CREDIT, THEN DRAWINGS NEED TO SHOW CEILING FAN SIZE IN |
| | ALL ROOMS. SEE TABLE 13-607.1.A.1 FBC 2004 FOR MINIMUM |
| | SIZE OF CEILING FAN REQUIRED. |
| | |
| | 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | ***ONLY PRODUCT APPROVAL FOR ROOF TILE AND ROOF TILE |
| | ADHESIVE WAS SUBMITTED. |
| | |
| | A) ALL FIXED AND OPERABLE WINDOWS AS SHOWN ON |
| | PLANS. |
| | |
| | B) ALL EXTERIOR DOORS AS SHOWN ON PLANS. FRENCH |
| | DOORS AND SWING DOOR AT MUD ROOM. |
| | |
| | C) WINDOW MULLIONS. |
| | |
| | D) FLAT ROOF.AND PROVIDE THE FOLLOWING |
| | INFORMATION: |
| | * IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED. |
| | ** CHECK IF SELECTED ASSEMBLY IS LIMTED BY GENERAL |
| | LIMITATION #7 OR #9. IF LIMITED BY GENERAL LIMITATION |
| | #9, THEN IT CAN'T BE USED IN THIS AREA. IF LIMITED BY |
| | GENERAL LIMTATION #7, THEN PROVIDE THE RAS 117 |
| | CALCULATIONS TO ENHANCE NAIL FASTENING AT PERIMETER AND |
| | CORNER AREAS. SEE GENERAL LIMITATION #7. IF |
| | CALCULATIONS ARE REQUIRED TO BE BY ARCHITECT, ENGINEER |
| | OR REGISTERED ROOF CONSULTANT, THEN ONLY ONE OF THOSE |
| | PROFESSIONALS CAN PROVIDE THE CALCULATIONS. |
| | |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. PROVIDE PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIC CONNECTOR ONLY. |
| | |
| | F) PRECAST CONCRETE LINTELS. |
| | |
| | G) STORM SHUTTERS IF WINDOWS AND DOORS DON'T HAVE |
| | IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. |
| | |
| | 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 16- SPECIFY ROOF CROSS VENTILATION FOR FLAT AND PITCHED |
| | ROOFS AS REQUIRED BYSEC. R806 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 17- WINDOWS NEXT TO FRENCH DOORS IN FAMILY AREA AND |
| | WINDOW NEXT TO THE BATH TUB IN SECOND FLOOR REQUIRE |
| | SAFETY GLASS AS REQUIRED BY SEC. R308.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 18- SPECIFY FLAT ROOF SLOPE TO VERIFY COMPLIANCE WITH |
| | SEC. R905.9.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 19- SHEET 7: SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR |
| | J BOLTS AT BOTTOM PLATE OF STEEL COLUMN AND FOR ANCHOR |
| | BOLTS AT 3X8 LEDGERIN SECTION 1/7.SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 20- SHEET 8: SPECIFY HEADROOM CLEARANCE IN SECTION 1/8 |
| | TO VERIFY COMPLIANCE WITH SEC. R311.5.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | ***NOTE: SEE THIS CODE SECTIONTO CHECK HOW DIMENSION |
| | SHALL BE MEASURED. |
| | |
| | 21- SHEET 10: |
| | A) REVISE DESIGN DATA NOTE #2. SEE SEC. R606.4 FOR |
| | MINIMUM COMPRESSIVE STRESS REQUIRED FOR CONCRETE |
| | BLOCK. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |