Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2007-10-22 Time 08:46 Sent To  
Notes
2007-10-22 09:40:19PLAIN DENIED
 1 - PLEASE PROVIDE NOC.AT TIME OF APPLICATION .
 2 - PLEASE PROVIDE GRILL SIZE AND CFM ON PLANS .
 3 - PLEASE REFER TO TABLE 13-607.1.ABC.3.2A FLORIDA
 ENERGY CODE ( MUST INSTALL 13 SEER UNIT )
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  
  