Plan Review Details - Permit 07100215
Plan Review Stops For Permit 07100215
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-01 Cont ID  
Sent By shill Date 2007-12-01 Time 15:43 Rev Time 0.00
Received By shill Date 2007-12-01 Time 15:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 09:45 Rev Time 0.00
Received By shill Date 2007-10-29 Time 09:45 Sent To  
Notes
2007-10-29 09:45:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.TWO ORIGINAL COLLATED SETS REQUIRED FOR PERMIT
 ISSUANCE, FBC*106.ONLY ONE ORIGINAL ENGINEERING
 SUBMITTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-16 Cont ID  
Sent By btrobaug Date 2007-11-16 Time 13:01 Rev Time 0.00
Received By btrobaug Date 2007-11-16 Time 12:37 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By btrobaug Date 2007-10-24 Time 12:15 Rev Time 0.00
Received By btrobaug Date 2007-10-24 Time 12:00 Sent To M
Notes
2007-10-24 12:15:22 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE RISER DIAGRAM WOULD INDICATE THE GENERATOR
 BACKFEEDING THE ENTIRE ELECTRICAL SYSTEM WITH 3#4 AND
 1#10 AS DRAWN. PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS AMENDED.
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-11-28 Cont ID  
Sent By mperson Date 2007-11-28 Time 11:56 Rev Time 0.00
Received By mperson Date 2007-11-28 Time 11:56 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By mperson Date 2007-10-26 Time 10:58 Rev Time 0.00
Received By mperson Date 2007-10-26 Time 10:58 Sent To B
Notes
2007-10-26 13:35:59DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PROVIDE TWO COPIES OF A SITE PLAN OR SURVEY THAT
 CLEARLY INDICATES THE PROPOSED LOCATION OF THE
 GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES
 AND DISTANCES FROM ADJACENT DWELLING STRUCTURES.
  
 2. PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 PROPOSED GENERATOR INDICATING RECOMMENDED SET BACKS
 FROM STRUCTURES.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: THE ONLY CORRESPONDING LENGTH INDICATED ON THE
 DRAWING IS FOR THE 25' OF UNDERGROUND 1/2" PE PIPING.
 WHAT ARE THE CORRESPONDING LENGTHS TO THE ABOVE GROUND
 PIPING? WHERE IS THE 1ST STAGE REGULATOR AT THE TANK
 AND ITS MODEL NUMBER ON THE ISOMETRIC DRAWING? PLEASE
 CLEARLY INDICATE THESE ITEMS ON THE RESUBMITTED
 ISOMETRIC.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 **NOTE: THE ONLY PIPING MATERIAL INDICATED ON THE
 DRAWING IS FOR THE UNDERGROUND PE PIPING. WHAT IS THE
 PIPING MATERIAL FOR THE ABOVE GROUNDGAS PIPE? PLEASE
 CLEARLY INDICATE THIS ON THE RESUBMITTED ISOMETRIC.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: THE SUBMITTED MANUFACTURER SPECIFICATION SHEETS
 FOR THE 2ND STAGE REGULATOR DOES NOT INDIDATE THE MAKE,
 MODEL NUMBER DOES NOT MATCH REGULATOR ON DRAWING, AND
 DOES NOT INDICATE A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY. PLEASE INDICATE THESE
 REQUIREMENTS ON THE RESUBMITTAL AS WELL AS FOR THE
 REQUIRED 1ST STAGE REGULATOR AT THE TANK.
  
 6. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 **NOTE: THE SUBMITTED SURVEY ARE NOT LEGIBLE, PLEASE
 PROVIDE TWO (2) COPIES OF A CURRENT, LEGIBLE SURVEY OR
 SITE PLAN SHOWING THE LOCATION OF THE PROPOSED 500 GAL
 U/G LP TANK CLEARLY INDICATING THE ABOVE REQUIRED
 INFORMATION. PER 106.1.2, ADDITIONAL INFORMATION
 REQUIRED.
  
 7. INDICATE HOW THE U/G TANK SHALL BE SECURLY ANCHORED
 PER NFPA 58 SECTION 6.6.1.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-13 Cont ID  
Sent By adarroug Date 2007-11-13 Time 10:46 Rev Time 0.00
Received By adarroug Date 2007-11-13 Time 10:46 Sent To Z
Notes
2007-11-13 10:46:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 09:45 Rev Time 0.00
Received By shill Date 2007-10-09 Time 11:00 Sent To  
Notes
2007-10-09 11:01:07TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-16 Cont ID  
Sent By tgordon Date 2007-11-16 Time 16:23 Rev Time 0.20
Received By tgordon Date 2007-11-16 Time 16:23 Sent To G
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 09:53 Rev Time 0.15
Received By tgordon Date 2007-10-25 Time 09:53 Sent To G
Notes
2007-10-25 09:54:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-15 Cont ID  
Sent By choops Date 2007-11-15 Time 10:33 Rev Time 0.00
Received By choops Date 2007-11-15 Time 10:33 Sent To E
Notes
2007-11-15 10:34:12***APPROVED - RESUB #1***
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By choops Date 2007-10-11 Time 15:32 Rev Time 0.00
Received By choops Date 2007-10-11 Time 15:32 Sent To E
Notes
2007-10-11 15:35:27***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT,
 LEGIBLE, CLEAR SURVEY SHOWING THE LOCATION OF THE
 PROPOSED GENERATOR WITH SETBACK DIMENSIONS TO ALL
 PROPERTY LINES.
  
 NOTE:PURSUANT TO SECTION 94-305(B)(4) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS:MECHANICAL
 EQUIPEMENT MAY NOT PROJECT MORE THAN 4' INTO ANY
 REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720