| 2007-10-11 07:36:12 | REROOF CONCRETE TILE TO ASPHALT SHINGLE |
| | 2004 FBC WITH 2007 REVISIONS. |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE FLORIDA PRODUCT APPROVAL COVER SHEET IS FOR A |
| | DIFFERENT SHINGLE THAN THE ONE IN THE NOA THAT WAS |
| | SUBMITTED. PLEASE CORRECT. |
| | |
| | 2) FBC R905.2.2 REQUIRES TWO LAYERS OF UNDERLAYMENT FOR |
| | ROOF SLOPES LESS THAN 4 : 12. SPECIFY ON APPLICATION. |
| | |
| | 3) EFFECTIVE OCTOBER 1, 2007 FLORIDA STATUTE 553.844 |
| | REQUIRES A SECONDARY WATER BARRIER TO BE INSTALLED WHEN |
| | A ROOF ON AN EXISTING SITE-BUILT, SINGLE FAMILY |
| | RESIDENTIAL STRUCTURE IS REPLACED. SPECIFY WHICH ONE OF |
| | THE FOLLOWING REQUIRED METHODS WILL BE INSTALLED.A) |
| | ALL JOINTS IN ROOF SHEATHING OR DECKING SHALL BE |
| | COVERED WITH A MINIMUM 4 IN. WIDE STRIP OF |
| | SELF-ADHERING POLYMER MODIFIED BITUMEN TAPE APPLIED |
| | DIRECTLY TO THE SHEATHING OR DECKING. THE DECK AND SELF |
| | ADHERING POLYMER MODIFIED BITUMEN TAPE SHALL BE COVERED |
| | WITH ONE OF THE UNDERLAYMENT SYSTEMS APPROVED FOR THE |
| | PARTICULAR ROOF COVERING TO BE APPLIED TO THE ROOF. B) |
| | THE ENTIRE ROOF DECK SHALL BE COVERED WITH AN APPROVED |
| | SELF-ADHERING POLYMER MODIFIED BITUMEN CAP SHEET. NO |
| | ADDITIONAL UNDERLAYMENT SHALL BE REQUIRED ON TOP OF |
| | THIS CAP SHEET FOR NEW INSTALLATIONS. EXCEPTIONS: 1. AN |
| | ASPHALT IMPREGNATED 30# FELT UNDERLAYMENT INSTALLED |
| | WITH NAILS AND TIN-TABS AS REQUIRED FOR THE HVHZ AND |
| | COVERED WITH EITHER AN APPROVED SELF-ADHERING POLYMER |
| | MODIFIED BITUMEN CAP SHEET OR AN APPROVED CAP SHEET |
| | APPLIED USING AN APPROVED HOT-MOP APPLICATION SHALL BE |
| | DEEMED TO MEET THE REQUIREMENTS FOR THE SECONDARY WATER |
| | BARRIER. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |