Plan Review Details - Permit 07100208
Plan Review Stops For Permit 07100208
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By shill Date 2007-11-19 Time 18:35 Rev Time 0.00
Received By shill Date 2007-11-19 Time 18:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-06 Cont ID  
Sent By shill Date 2007-11-06 Time 10:25 Rev Time 0.00
Received By shill Date 2007-11-06 Time 10:25 Sent To  
Notes
2007-11-06 10:28:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR SCHEDULE; IN THIS CASE, C1 THROUGH C5.
  
  
 2.ANCHOR TYPE IS TO BE SPECIFIC.THE 12" SPACING ON
 THE INSTALLATION SCHEDULE IS NOT COMPLIANT FOR ANY OF
 THE CONNECTION TYPES FOR ITW TAPCON, AND NOT COMPLIANT
 FOR SOME CONNECTION TYPES FOR THE OTHER TAPCONS.SEE
 SHEET 8.
  
 3.PLEASE NOTE THAT SUBSTRATE ON THE INSTALLATION
 SCHEDULE IS TO BE SUBSTRATE OF THE OPENING, TOP AND
 BOTTOM, NOT CONSTRUCTION OF THE BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By shill Date 2007-10-26 Time 09:04 Rev Time 0.00
Received By shill Date 2007-10-26 Time 09:04 Sent To  
Notes
2007-10-26 09:07:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 1COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED.
  
 2.PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS
 WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH
 THE INSTALLATION SCHEDULE, ITEM 3 ABOVE.
  
 3.DECLARE OCCUPANCY CLASSIFICATION FBC CHAPTER 3.
 PROPERTY APPRAISER SHOWS THIS AS A RESTAURANT; IS THIS
 CORRECT?SEE FBC1003.6, MEANS OF EGRESS CONTINUITY.
 THE PATH OF EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL
 NOT BE INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A
 MEANS OF EGRESS COMPONENT AS SPECIFIED IN CHAPTER 10.
 THE APPLICATION STATES THAT YOU ARE INSTALLING A
 HURRICANE SHUTTER OVER THE FRONT DOOR.THIS IS NOT
 ALLOWED FBC1003.6.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 11:04 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 11:04 Sent To B
Notes
2007-11-15 11:05:14TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 15:59 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 15:59 Sent To B
Notes
2007-10-31 16:00:06TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-26 Cont ID  
Sent By shill Date 2007-10-26 Time 09:07 Rev Time 0.00
Received By shill Date 2007-10-09 Time 09:52 Sent To  
Notes
2007-10-09 09:52:39TO "MISC" BOX#1