Plan Review Details - Permit 07100204
| Plan Review Stops For Permit 07100204 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-05 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-05 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-11-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-11-19 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-11-19 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2007-11-19 09:34:52 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.PROVIDE A SLAB DETAIL WITHOUT THE COUNTY STAMPS ON | | | IT. | | | | | | 2.THE COMPANY NAME AT THE TOP OF THE SLAB DETAIL IS | | | ILLEGIBLE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-29 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-29 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2007-10-29 10:51:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1..)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL | | | DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB | | | SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER. FBC | | | R301 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-29 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-29 |
Time |
16:32 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-11-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-11-08 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-11-08 |
Time |
14:48 |
Sent To |
P |
|
| Notes |
| 2007-11-08 15:37:36 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | COMMENTS FROM PREVIOUS REVIEW: | | | | | | 1} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO | | | BE SERVED. 215.5. 702.5, 2005NEC ANDPROVIDE A PANEL | | | SCHEDULE FOR THE GENERATOR PANEL. 106.3.5.4 FBC AS | | | AMENDED. LOAD CALCULATIONS AND PANEL SCHEDULES WERE | | | SUBMITTED FOR TWO PANELS, CLARIFY THE PANEL THE | | | GENERATOR WILL FEED. SEE SCHEDULES AND RISER DIAGRAM. * | | | THE GENERATOR SPECS HAVE THE OUTPUT AT 75 AMPS. BOTH | | | PANEL SCHEDULES/ LOAD CALCS, ARE HIGHER AMPERAGE THAN | | | TH OUTPUT OF THE GENSET. IT IS THE DETERMINATION OF | | | THIS OFFICE THAT LOADS BEING TRANSFERRED AUTOMATICALLY | | | ARE THE LOADS SELECTED UNDER ARTICLE 702.5. UTILITY | | | POWER CAN BE DISRUPTED AT ANY TIME, POSSIBLY IN THE | | | OWNERS ABSENCE. THEREFORE ALL CONNECTED LOADS WILL BE | | | ENERGIZED AS THERE IS NO ONE TO "SELECT" WHICH CIRCUITS | | | WILL BE ENERGIZED. HOW ARE LOADS BEING SHED. THERE ARE | | | STILL NO GENERATOR PANELS SUBMITTED AIS SHOWN ON THE | | | RISER DIAGRAM | | | | | | 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, | | | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH | | | ARTICLES 225 AND 230 CAN BE REVIEWED.* ONLY THE | | | GENERATOR IS ON THE SITE PLAN. | | | | | | 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | | GENERATOR INDICATING RECOMMENDED SETBACKS FROM | | | STRUCTURES | | | * COULD NOT FIND THE SETBACK RECOMMENDATIONS IN THE | | | DOCUMENTS SUBMITTED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-10-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-24 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-24 |
Time |
11:41 |
Sent To |
M |
|
| Notes |
| 2007-10-24 11:56:52 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO | | | BE SERVED. 215.5. 702.5, 2005NEC ANDPROVIDE A PANEL | | | SCHEDULE FOR THE GENERATOR PANEL. 106.3.5.4 FBC AS | | | AMENDED. LOAD CALCULATIONS AND PANEL SCHEDULES WERE | | | SUBMITTED FOR TWO PANELS, CLARIFY THE PANEL THE | | | GENERATOR WILL FEED. SEE SCHEDULES AND RISER DIAGRAM. | | | | | | 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, | | | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH | | | ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | | GENERATOR INDICATING RECOMMENDED SETBACKS FROM | | | STRUCTURES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-21 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-21 |
Time |
10:24 |
Sent To |
PC |
|
| Notes |
| 2008-03-21 10:25:31 | REVISION: CHANGED 2 PSI GAS SYSTEM TO 0.5 PSI. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2008-02-01 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-02-01 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-02-01 |
Time |
09:01 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-11-14 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-11-14 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-11-14 |
Time |
07:47 |
Sent To |
M |
|
| Notes |
| 2007-11-14 08:41:30 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS | | | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | GAS PLAN REVIEW: | | | DENIED 2ND TIME: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. OK,PREVIOUS COMMENT ADDRESSED. | | | | | | 2. NO, PRIVIOUS COMMENT NOT ADDRESSED. | | | **SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | **NOTE: CORRESPONDING LENGTHS ARE NOT INDICATED ON ALL | | | CUT SECTIONS OF PIPE. | | | | | | 3. OK, PREVIOUS COMMENT ADDRESSED. | | | | | | 4. OK, PREVIOUS COMMENT ADDRESSED. | | | | | | 5. NO, PREVIOUS COMMENT NOT ADDRESSED. | | | **BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | **NOTE: THIS INCLUDES THE EXISTING BTU LOAD AS WELL AS | | | THE PROPOSED BTU LOAD OF GENERATOR. PLEASE REFERENCE | | | THE PERMIT INFORMATION ATTACHED TO THE GAS COMMENTS | | | INDICATING EXISTING GAS TO SAID RESIDENCE. | | | | | | 6. NO, PREVIOUS COMMENTS NOT ADDRESSED. | | | **SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | **NOTE: THIS INCLUDES THE EXISTING GAS SYSTEMS LONGEST | | | LENGTH. AS STATED IN COMMENT #5, PLEASE REFERENCE THE | | | PERMIT INFORMATION ATTACHED TO THE GAS COMMENTS | | | INDICATING EXISTING GAS TO SAID RESIDENCE. | | | | | | 7. OK, PREVIOUS COMMENT ADDRESSED. | | | | | | 8. NO, PREVIOUS COMMENT NOT ADDRESSED. | | | **SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | **NOTE: THE RESUBMITTED GAS DRAWINGS IS INDICATING THE | | | GAS DELIVERY PRESSURE AS 2 PSI. PLEASE SUBMIT TWO | | | COPIES OF MANUFACTURER'S SPECIFICATION SHEETS OF THE MP | | | REGULATOR INDICATING THE MAKE, MODEL NUMBER, BTU LOAD | | | CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED | | | TESTING LABORATORY. | | | | | | 9. OK, N/A. | | | | | | 10. OK, N/A. | | | | | | 11. OK, PREVIOUS COMMENT ADDRESSED. | | | | | | **THE FOLLOWING ARE NEW COMMENTS: | | | | | | 12. A SHUT OFF VALVE IS REQUIRED BEFORE THE MP | | | REGULATOR.A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP | | | REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE | | | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-10-26 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-10-26 |
Time |
09:50 |
Sent To |
B |
|
| Notes |
| 2007-10-26 10:22:11 | DENIED | | | REFERENCE: | | | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | | ** FLORIDA STATUTES (FS). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. PLEASE SUBMIT TWO COPIES OF A SITE PLAN INDICATING | | | THE PROPOSED GENERATOR LOCATION INDICATING ALL | | | DIMENTIONS FROM PROPERTY LINES AND DWELLINGS ON THE | | | RESUBMITTAL. | | | | | | 2. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 3. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | | | | 4. TYPE OF GAS, (LP OR NATURAL) | | | | | | 5. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33). | | | **NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM, PLEASE | | | REFERENCE THE PERMIT INFORMATION ATTACHED TO THE GAS | | | COMMENTS INDICATING EXISTING GAS TO SAID RESIDENCE. | | | | | | 6. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | **NOTE: THIS INCLUDES THE EXISTING GAS SYSTEMS LONGEST | | | LENGTH. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | **NOTE: IF GAS DELIVERY PRESSURE IS 2 PSI OR GREATER | | | PLEASE SUBMIT TWO COPIES OF MANUFACTURE SPECIFICATION | | | SHEETS OF THE MP REGULATOR INDICATING THE MAKE, MODEL | | | NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A | | | NATIONALLY RECOGIZED TESTING LABORATORY. | | | | | | 9. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 10. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | 11. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE DRAWING SHALL CLEARLY PRINT AND SIGN | | | NAME, AND ALSO DATE DRAWING. PLEASE DO | | | THIS PRIOR TO RESUBMITTING. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-03-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-20 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-20 |
Time |
15:04 |
Sent To |
P |
|
| Notes |
| 2008-03-20 15:04:39 | TO "G" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-23 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-23 |
Time |
11:42 |
Sent To |
E |
|
| Notes |
| 2008-01-23 11:43:20 | TO " BTROBAUGH" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-08 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-08 |
Time |
08:33 |
Sent To |
E |
|
| Notes |
| 2007-11-08 08:34:51 | TO "BTROBAUGH" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-29 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-05 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2007-10-05 16:07:02 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-11-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-11-14 |
Time |
09:43 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-11-14 |
Time |
09:43 |
Sent To |
B |
|
| Notes |
| 2007-11-14 09:46:06 | *** PROVISO *** | | | PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT PERMANENTLY | | | INSTALLED EQUIPMENT POWERED BY INTERNALCOMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE WITH | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA 37. | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES | | | (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT | | | FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES | | | HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT | | | REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF | | | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, | | | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 | | | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES | | | OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION | | | INTAKES. | | | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS | | | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE | | | TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF | | | STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL | | | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, | | | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED | | | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. | | | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES | | | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-25 |
Time |
09:32 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-10-25 |
Time |
09:32 |
Sent To |
G |
|
| Notes |
| 2007-10-25 09:35:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT DETAILED MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS SHOWING REQUIRED CLEARANCES FOR GENERATOR, | | | SEE NFPA 37 (4.1.4). | | | | | | 2) PLEASE STATE WHAT THE BUILDING IS MADE OF AND IF | | | COMBUSTIBLE, SEE NFPA 37 (4.1.4). | | | | | | *** NOTE *** | | | PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT PERMANENTLY | | | INSTALLED EQUIPMENT POWERED BY INTERNALCOMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE WITH | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA 37. | | | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION | | | ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS) | | | LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS | | | IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING | | | COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED | | | WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF | | | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, | | | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 | | | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES | | | OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION | | | INTAKES. | | | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS | | | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE | | | TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF | | | STRUCTURE. | | | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL | | | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, | | | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED | | | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. | | | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES | | | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-11 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-11 |
Time |
12:19 |
Sent To |
E |
|
| Notes |
| 2007-10-11 12:20:34 | PROVISO:GENERATOR MAY NOT BE CLOSER THAN 3.5' TO THE | | | NE SIDE PROPERTY LINE. | | | | | | NOTE:IBIS HOA MAY REQUIRE SCREENING. | | | | | | ***APPROVED*** | | | | | | SENT TO "E" - GEN. BOX |
|
|
|