Plan Review Details - Permit 07100204
Plan Review Stops For Permit 07100204
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-05 Cont ID  
Sent By shill Date 2008-02-05 Time 14:20 Rev Time 0.00
Received By shill Date 2008-02-05 Time 14:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-19 Cont ID  
Sent By shill Date 2007-11-19 Time 09:33 Rev Time 0.00
Received By shill Date 2007-11-19 Time 09:33 Sent To  
Notes
2007-11-19 09:34:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE A SLAB DETAIL WITHOUT THE COUNTY STAMPS ON
 IT.
  
 2.THE COMPANY NAME AT THE TOP OF THE SLAB DETAIL IS
 ILLEGIBLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 10:50 Rev Time 0.00
Received By shill Date 2007-10-29 Time 10:48 Sent To  
Notes
2007-10-29 10:51:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1..)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL
 DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB
 SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER. FBC
 R301
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-29 Cont ID  
Sent By btrobaug Date 2008-01-29 Time 16:48 Rev Time 0.00
Received By btrobaug Date 2008-01-29 Time 16:32 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-08 Cont ID  
Sent By btrobaug Date 2007-11-08 Time 15:37 Rev Time 0.00
Received By btrobaug Date 2007-11-08 Time 14:48 Sent To P
Notes
2007-11-08 15:37:36 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 1} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC ANDPROVIDE A PANEL
 SCHEDULE FOR THE GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED. LOAD CALCULATIONS AND PANEL SCHEDULES WERE
 SUBMITTED FOR TWO PANELS, CLARIFY THE PANEL THE
 GENERATOR WILL FEED. SEE SCHEDULES AND RISER DIAGRAM. *
 THE GENERATOR SPECS HAVE THE OUTPUT AT 75 AMPS. BOTH
 PANEL SCHEDULES/ LOAD CALCS, ARE HIGHER AMPERAGE THAN
 TH OUTPUT OF THE GENSET. IT IS THE DETERMINATION OF
 THIS OFFICE THAT LOADS BEING TRANSFERRED AUTOMATICALLY
 ARE THE LOADS SELECTED UNDER ARTICLE 702.5. UTILITY
 POWER CAN BE DISRUPTED AT ANY TIME, POSSIBLY IN THE
 OWNERS ABSENCE. THEREFORE ALL CONNECTED LOADS WILL BE
 ENERGIZED AS THERE IS NO ONE TO "SELECT" WHICH CIRCUITS
 WILL BE ENERGIZED. HOW ARE LOADS BEING SHED. THERE ARE
 STILL NO GENERATOR PANELS SUBMITTED AIS SHOWN ON THE
 RISER DIAGRAM
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.* ONLY THE
 GENERATOR IS ON THE SITE PLAN.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES
 * COULD NOT FIND THE SETBACK RECOMMENDATIONS IN THE
 DOCUMENTS SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By btrobaug Date 2007-10-24 Time 11:56 Rev Time 0.00
Received By btrobaug Date 2007-10-24 Time 11:41 Sent To M
Notes
2007-10-24 11:56:52 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC ANDPROVIDE A PANEL
 SCHEDULE FOR THE GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED. LOAD CALCULATIONS AND PANEL SCHEDULES WERE
 SUBMITTED FOR TWO PANELS, CLARIFY THE PANEL THE
 GENERATOR WILL FEED. SEE SCHEDULES AND RISER DIAGRAM.
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-03-21 Cont ID  
Sent By mperson Date 2008-03-21 Time 10:24 Rev Time 0.00
Received By mperson Date 2008-03-21 Time 10:24 Sent To PC
Notes
2008-03-21 10:25:31REVISION: CHANGED 2 PSI GAS SYSTEM TO 0.5 PSI.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2008-02-01 Cont ID  
Sent By mperson Date 2008-02-01 Time 09:01 Rev Time 0.00
Received By mperson Date 2008-02-01 Time 09:01 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-11-14 Cont ID  
Sent By mperson Date 2007-11-14 Time 07:47 Rev Time 0.00
Received By mperson Date 2007-11-14 Time 07:47 Sent To M
Notes
2007-11-14 08:41:30PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. OK,PREVIOUS COMMENT ADDRESSED.
  
 2. NO, PRIVIOUS COMMENT NOT ADDRESSED.
 **SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NOTE: CORRESPONDING LENGTHS ARE NOT INDICATED ON ALL
 CUT SECTIONS OF PIPE.
  
 3. OK, PREVIOUS COMMENT ADDRESSED.
  
 4. OK, PREVIOUS COMMENT ADDRESSED.
  
 5. NO, PREVIOUS COMMENT NOT ADDRESSED.
 **BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **NOTE: THIS INCLUDES THE EXISTING BTU LOAD AS WELL AS
 THE PROPOSED BTU LOAD OF GENERATOR. PLEASE REFERENCE
 THE PERMIT INFORMATION ATTACHED TO THE GAS COMMENTS
 INDICATING EXISTING GAS TO SAID RESIDENCE.
  
 6. NO, PREVIOUS COMMENTS NOT ADDRESSED.
 **SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NOTE: THIS INCLUDES THE EXISTING GAS SYSTEMS LONGEST
 LENGTH. AS STATED IN COMMENT #5, PLEASE REFERENCE THE
 PERMIT INFORMATION ATTACHED TO THE GAS COMMENTS
 INDICATING EXISTING GAS TO SAID RESIDENCE.
  
 7. OK, PREVIOUS COMMENT ADDRESSED.
  
 8. NO, PREVIOUS COMMENT NOT ADDRESSED.
 **SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: THE RESUBMITTED GAS DRAWINGS IS INDICATING THE
 GAS DELIVERY PRESSURE AS 2 PSI. PLEASE SUBMIT TWO
 COPIES OF MANUFACTURER'S SPECIFICATION SHEETS OF THE MP
 REGULATOR INDICATING THE MAKE, MODEL NUMBER, BTU LOAD
 CAPACITY, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY.
  
 9. OK, N/A.
  
 10. OK, N/A.
  
 11. OK, PREVIOUS COMMENT ADDRESSED.
  
 **THE FOLLOWING ARE NEW COMMENTS:
  
 12. A SHUT OFF VALVE IS REQUIRED BEFORE THE MP
 REGULATOR.A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP
 REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By mperson Date 2007-10-26 Time 09:50 Rev Time 0.00
Received By mperson Date 2007-10-26 Time 09:50 Sent To B
Notes
2007-10-26 10:22:11DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE SUBMIT TWO COPIES OF A SITE PLAN INDICATING
 THE PROPOSED GENERATOR LOCATION INDICATING ALL
 DIMENTIONS FROM PROPERTY LINES AND DWELLINGS ON THE
 RESUBMITTAL.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 4. TYPE OF GAS, (LP OR NATURAL)
  
 5. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM, PLEASE
 REFERENCE THE PERMIT INFORMATION ATTACHED TO THE GAS
 COMMENTS INDICATING EXISTING GAS TO SAID RESIDENCE.
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NOTE: THIS INCLUDES THE EXISTING GAS SYSTEMS LONGEST
 LENGTH.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: IF GAS DELIVERY PRESSURE IS 2 PSI OR GREATER
 PLEASE SUBMIT TWO COPIES OF MANUFACTURE SPECIFICATION
 SHEETS OF THE MP REGULATOR INDICATING THE MAKE, MODEL
 NUMBER, BTU LOAD CAPACITY, AND A LISTING FROM A
 NATIONALLY RECOGIZED TESTING LABORATORY.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 11. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-20 Cont ID  
Sent By adarroug Date 2008-03-20 Time 15:04 Rev Time 0.00
Received By adarroug Date 2008-03-20 Time 15:04 Sent To P
Notes
2008-03-20 15:04:39TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 11:42 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 11:42 Sent To E
Notes
2008-01-23 11:43:20TO " BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 08:33 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 08:33 Sent To E
Notes
2007-11-08 08:34:51TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 10:51 Rev Time 0.00
Received By shill Date 2007-10-05 Time 16:06 Sent To  
Notes
2007-10-05 16:07:02TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-14 Cont ID  
Sent By tgordon Date 2007-11-14 Time 09:43 Rev Time 0.25
Received By tgordon Date 2007-11-14 Time 09:43 Sent To B
Notes
2007-11-14 09:46:06*** PROVISO ***
 PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT PERMANENTLY
 INSTALLED EQUIPMENT POWERED BY INTERNALCOMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE WITH
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By tgordon Date 2007-10-25 Time 09:32 Rev Time 0.25
Received By tgordon Date 2007-10-25 Time 09:32 Sent To G
Notes
2007-10-25 09:35:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHOWING REQUIRED CLEARANCES FOR GENERATOR,
 SEE NFPA 37 (4.1.4).
  
 2) PLEASE STATE WHAT THE BUILDING IS MADE OF AND IF
 COMBUSTIBLE, SEE NFPA 37 (4.1.4).
  
 *** NOTE ***
 PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT PERMANENTLY
 INSTALLED EQUIPMENT POWERED BY INTERNALCOMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE WITH
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS)
 LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS
 IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING
 COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED
 WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-10-11 Cont ID  
Sent By choops Date 2007-10-11 Time 12:19 Rev Time 0.00
Received By choops Date 2007-10-11 Time 12:19 Sent To E
Notes
2007-10-11 12:20:34PROVISO:GENERATOR MAY NOT BE CLOSER THAN 3.5' TO THE
 NE SIDE PROPERTY LINE.
  
 NOTE:IBIS HOA MAY REQUIRE SCREENING.
  
 ***APPROVED***
  
 SENT TO "E" - GEN. BOX