Plan Review Details - Permit 07100197
Plan Review Stops For Permit 07100197
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 12:51 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 12:51 Sent To P
Notes
2007-11-05 12:51:52TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-17 Cont ID  
Sent By mperson Date 2007-10-17 Time 15:50 Rev Time 0.00
Received By mperson Date 2007-10-05 Time 15:54 Sent To  
Notes
2007-10-05 15:54:21TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-13 Cont ID  
Sent By mperson Date 2007-11-13 Time 09:08 Rev Time 0.00
Received By mperson Date 2007-11-13 Time 09:08 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-17 Cont ID  
Sent By mperson Date 2007-10-17 Time 15:03 Rev Time 0.00
Received By mperson Date 2007-10-17 Time 15:03 Sent To PC
Notes
2007-10-17 15:49:57DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: SHEET 1, OF THE SUBMITTED PLANS HAVE AN
 ARCHITECTURAL TITLE BLOCK FROM EVERETT H JENNER
 AR-0007573, PER FAC-CODE-61G1-16001 ARCHITECT'S AND
 INTERIOR DESIGNER'S SEAL:
 EACH ARCHITECT AND INTERIOR DESIGNER
 SHALL ACQUIRE A SEAL WITH WHICH HE OR
 SHE SHALL IDENTIFY ALL PLANS,
 SPECIFICATIONS OR REPORTS PREPARED OR
 ISSUED BY HIM OR HER AND FILED FOR
 PUBLIC RECORD. THE SEAL SHALL BE OF A
 TYPE WHICH WILL MAKE AN IMPRESSION ON
 THE SURFACE OF PRINTS OR OTHER
 DUPLICATIONS OF DRAWINGS, AND AS
 APPROPRIATE, UPON SPECIFICATION PAGES,
 AND OTHER ARTICLES OF SERVICE.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.1.2 PLEASE
 SUBMIT ADDITIONAL DATA PER THE FOLLOWING FBC-2004 W/
 06, REV. PLUMBING, CODE SECTIONS, 601.1 WATER SUPPLY
 DESIGN (IRRIGATION), 608, POTABLE WATER PTOTECTION, AND
 305.3 STRESS AND STRAIN.
  
 A} 601.1 & 608: CLEARLY INDICATE THE BACKFLOW
 PREVENTER LOCATION ON THE RESUBMITTED PLANS AND PROVIDE
 A SYMBOL FOR IT IN THE IRRIGATION LEGEND.
  
 B} 601.1 & 608: CLEARLY INDICATE IF THE BACKFLOW
 PREVENTER IS EXISTING OR NEW ON THE RESUBMITTED PLANS.
  
  
 C} 305.3: CLEARLY INDICATE ON THE RESUBMITTED PLAN ALL
 REQUIRED SLEEVE LOCATIONS FOR THE IRRIGATION PIPING IN
 PARKING LOTS, AND SIDEWALK AREAS.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  