| 2007-10-18 15:11:02 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. NOTE: THE MASTER PERMIT #06090447 REFERENCED IS A 2 |
| | STORY 4 UNITS A,B,C, AND D (R-2). THE SUBMITTED PERMIT |
| | APPLICATION SHOULD CLEARLY INDICATE THIS, AND THE |
| | RESUBMITTED GAS DRAWINGS SHOULD CLEARLY CORRELATE THE |
| | UNITS WITH THE GAS RISER PER THE FOLOWING, FBC-2004 |
| | W/O6, REV. FUEL GAS, CODE SECTION, 401.1 SCOPE. THIS |
| | CHAPTER SHALL GOVERN DESIGN. |
| | |
| | A} THE SUBMITTED GAS DRAWINGS ONLY INDICATE TWO GAS |
| | RISERS, THERE ARE FOUR UNITS PER THE REFERENCED MASTER |
| | #06090447. PLEASE CLARIFY THIS ON THE RESUBMITTAL. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL |
| | DOCUMENTS. CONSTRUCTION |
| | DOCUMENTS, SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION FOR A |
| | PERMIT. |
| | NOTE: ONLY ONE SET OF WATER HEATER MANUFACTURER |
| | SPECIFICATIONS WERE SUBMITTED. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: THE SUBMITTED MANUFACTURER SPECIFICATION SHEETS |
| | FOR THE RANGE DO NOT HAVE A LISTING FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY. PLEASE SUPPLY THIS ON |
| | THE RESUBMITTAL. |
| | |
| | 4. THE VALUE FOR THE JOB SEEMS LOW PER FBC-2004, |
| | CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | NOTE: PROVIDE A COPY OF THE SIGNED CONTRACT FOR THE JOB |
| | TO VERIFY THE VALUE ON THE PERMIT APPLICATION IN THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |