Plan Review Details - Permit 07100177
Plan Review Stops For Permit 07100177
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-10-25 Cont ID  
Sent By mperson Date 2007-10-25 Time 14:42 Rev Time 0.00
Received By mperson Date 2007-10-25 Time 14:42 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By mperson Date 2007-10-18 Time 13:02 Rev Time 0.00
Received By mperson Date 2007-10-18 Time 13:02 Sent To PC
Notes
2007-10-18 14:17:01DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: THE MASTER PERMIT #05080077 REFERENCED IS A 2
 STORY 4 UNITS A,B,C, AND D (R-2). THE SUBMITTED PERMIT
 APPLICATION SHOULD CLEARLY INDICATE THIS, AND THE
 RESUBMITTED GAS DRAWINGS SHOULD CLEARLY CORRELATE THE
 UNITS WITH THE GAS RISER PER THE FOLLOWING FBC-2004 W/
 06, REV. FUEL GAS, CODE SECTION, 401.1 SCOPE. THIS
 CHAPTER SHALL GOVERN THE DESIGN.
  
 A} NOTE: THERE ARE TWO SHEETS WITH GAS RISER DIAGRAMS
 SUBMITTED THAT DO NOT INDICATE WHICH UNITS THEY ARE
 FOR. ONE SHEET HAS RANGES @ 30,000 BTU'S AND WATER
 HEATERS @ 190,000 BTU'S AND THE OTHER SHEET HAS RANGES
 @ 72,000 BTU'S AND WATER HEATERS @ 199,000 BTU'S. THE
 SUBMITTED APPLIANCE MANUFACTURER SHEETS ARE INDICATING
 A 72,000 BTU RANGE AND 150,000 BTU WATER HEATER BEING
 USED. PLEASE CORRELATE AND CLARIFY THIS ON THE
 RESUBMITTAL.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: ONE SHEET OF GAS RISER DIAGRAMS WITH THE 30,000
 BTU RANGE AND 190,000 BTU WATER HEATER DOES NOT
 INDICATE THE CORRESPONDING LENGTHS TO THE CUT SECTIONS
 OF PIPE
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL
 DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
 NOTE: ONLY ONE SET OF WATER HEATER MANUFACTURER
 SPECIFICATIONS WERE SUBMITTED.
  
 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: THE SUBMITTED MANUFACTURER SPECIFICATION SHEETS
 FOR THE RANGE DO NOT HAVE A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY PLEASE SUPPLY THIS ON THE
 RESUBMITTAL.
  
 5. THE VALUE FOR THE JOB SEEMS LOW PER FBC-2004,
 CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 NOTE: PROVIDE A COPY OF THE SIGNED CONTRACT FOR THE JOB
 TO VERIFY THE VALUE ON THE PERMIT APPLICATION IN THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-25 Cont ID  
Sent By adarroug Date 2007-10-25 Time 09:46 Rev Time 0.00
Received By adarroug Date 2007-10-25 Time 09:46 Sent To G
Notes
2007-10-25 09:47:10TO "MPERSON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-18 Cont ID  
Sent By mperson Date 2007-10-18 Time 14:17 Rev Time 0.00
Received By mperson Date 2007-10-05 Time 12:42 Sent To  
Notes
2007-10-05 12:42:26TO "G" BOX