Plan Review Details - Permit 07100112
Plan Review Stops For Permit 07100112
Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-31 Cont ID  
Sent By btrobaug Date 2007-12-31 Time 08:44 Rev Time 0.00
Received By btrobaug Date 2007-12-31 Time 08:33 Sent To M
Notes
2007-12-31 08:44:21 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By btrobaug Date 2007-10-10 Time 15:00 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 14:58 Sent To M
Notes
2007-10-10 15:00:43 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED
 WITH THE APPLICATION. SHOW THE LOCATION OF THE A/C
 EQUIPMENT ON THE PLAN. ALSO SHOW COMPLIANCE WITH THE
 REQUIRED DISCONNECT PER 440.14,RECEPTACLE PER
 210.63,
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-12-21 Cont ID  
Sent By spalmer Date 2007-12-21 Time 16:17 Rev Time 0.00
Received By spalmer Date 2007-12-21 Time 16:17 Sent To Z
Notes
2007-12-21 16:18:04TO CHRIS HOOPS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-10-18 Time   Rev Time 0.00
Received By adarroug Date 2007-10-04 Time 11:45 Sent To  
Notes
2007-10-04 11:46:31TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-31 Cont ID  
Sent By tgordon Date 2007-12-31 Time 09:39 Rev Time 0.20
Received By tgordon Date 2007-12-31 Time 09:39 Sent To  
Notes
2007-12-31 09:41:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING AND ELECTRICAL REVIEW NOTES, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 11:04 Rev Time 0.20
Received By tgordon Date 2007-10-18 Time 11:04 Sent To  
Notes
2007-10-18 11:12:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 2) STATE ON PLAN WHAT THE TOTAL LENGTH OF THE COPPER
 REFRIGERANT LINES WILL BE AS A RESULT OF THE
 RELOCATION. IF OVER 100 FT PROVIDEMANUFACTURER'S
 SPECIFICATION'S REGARDING COPPER LINE SIZES AND
 LENGTHS, SEE FBC/R M1401.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2007-12-27 Cont ID  
Sent By choops Date 2007-12-27 Time 08:09 Rev Time 0.00
Received By choops Date 2007-12-27 Time 08:09 Sent To E
Notes
2007-12-27 08:28:45***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.THERE IS
 A REQUIRED FRONT SETBACK OF 20' TO THE FRONT GARAGE,
 THE MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4'
 INTO THIS SETBACK, THIS DIMENSION NEEDS TO BE SHOWN ON
 THE SURVEYS.
  
 NOTE: YOU ARE REMOVING THE A/C EQUIPMENT FROM THE BACK
 YARD BEHIND A WALL, AND MOVING IT TO THE FRONT YARD IN
 THE OPEN.I WOULD SUGGEST BUFFERING THE EQUIPMENT WITH
 SOME TYPE OF LANDSCAPING OR SCREENING.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By choops Date 2007-10-09 Time 17:44 Rev Time 0.00
Received By choops Date 2007-10-09 Time 17:44 Sent To E
Notes
2007-10-09 17:47:40***FAILED***
  
  
 1)PURSUANT TO THE DEVELOPMENT GUIDLINES FOR BEAR
 ISLAND PLANNED DEVELOPMENT, A HOA APPROVAL LETTER SHALL
 BE SUBMITTED.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 MECHANICAL EQUIPMENT TO THE PROPERTY LINES.
  
 NOTE:PURSUANT TO SECTION 94-305(B)(4) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS:MECHANICAL EQUIPMENT MAY PROJECT 4' INTO
 A REQUIRED SETBACK.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720