| Plan Review Stops For Permit 07100112 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-12-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-31 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-31 |
Time |
08:33 |
Sent To |
M |
|
| Notes |
| 2007-12-31 08:44:21 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-10 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-10 |
Time |
14:58 |
Sent To |
M |
|
| Notes |
| 2007-10-10 15:00:43 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED | | | WITH THE APPLICATION. SHOW THE LOCATION OF THE A/C | | | EQUIPMENT ON THE PLAN. ALSO SHOW COMPLIANCE WITH THE | | | REQUIRED DISCONNECT PER 440.14,RECEPTACLE PER | | | 210.63, | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-12-21 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-12-21 |
Time |
16:17 |
Sent To |
Z |
|
| Notes |
| 2007-12-21 16:18:04 | TO CHRIS HOOPS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-10-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-04 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2007-10-04 11:46:31 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-12-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-31 |
Time |
09:39 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-12-31 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2007-12-31 09:41:51 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SEE ZONING AND ELECTRICAL REVIEW NOTES, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-18 |
Time |
11:04 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-10-18 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2007-10-18 11:12:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT. | | | | | | 2) STATE ON PLAN WHAT THE TOTAL LENGTH OF THE COPPER | | | REFRIGERANT LINES WILL BE AS A RESULT OF THE | | | RELOCATION. IF OVER 100 FT PROVIDEMANUFACTURER'S | | | SPECIFICATION'S REGARDING COPPER LINE SIZES AND | | | LENGTHS, SEE FBC/R M1401.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-27 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-27 |
Time |
08:09 |
Sent To |
E |
|
| Notes |
| 2007-12-27 08:28:45 | ***FAILED - RESUB #1*** | | | | | | | | | REPEAT COMMENT: | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C | | | EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION | | | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.THERE IS | | | A REQUIRED FRONT SETBACK OF 20' TO THE FRONT GARAGE, | | | THE MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4' | | | INTO THIS SETBACK, THIS DIMENSION NEEDS TO BE SHOWN ON | | | THE SURVEYS. | | | | | | NOTE: YOU ARE REMOVING THE A/C EQUIPMENT FROM THE BACK | | | YARD BEHIND A WALL, AND MOVING IT TO THE FRONT YARD IN | | | THE OPEN.I WOULD SUGGEST BUFFERING THE EQUIPMENT WITH | | | SOME TYPE OF LANDSCAPING OR SCREENING. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-10-09 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-10-09 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-10-09 |
Time |
17:44 |
Sent To |
E |
|
| Notes |
| 2007-10-09 17:47:40 | ***FAILED*** | | | | | | | | | 1)PURSUANT TO THE DEVELOPMENT GUIDLINES FOR BEAR | | | ISLAND PLANNED DEVELOPMENT, A HOA APPROVAL LETTER SHALL | | | BE SUBMITTED. | | | | | | 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED | | | MECHANICAL EQUIPMENT TO THE PROPERTY LINES. | | | | | | NOTE:PURSUANT TO SECTION 94-305(B)(4) OF THE CITY OF | | | WEST PALM BEACH ZONING AND LAND DEVELOPMENT | | | REGULATIONS:MECHANICAL EQUIPMENT MAY PROJECT 4' INTO | | | A REQUIRED SETBACK. | | | | | | NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|