Plan Review Details - Permit 07100100
Plan Review Stops For Permit 07100100
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-10-30 Cont ID  
Sent By shill Date 2007-10-30 Time 17:00 Rev Time 0.00
Received By shill Date 2007-10-30 Time 17:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-26 Cont ID  
Sent By shill Date 2007-10-26 Time 09:47 Rev Time 0.00
Received By shill Date 2007-10-26 Time 09:47 Sent To  
Notes
2007-10-26 09:49:22****CORRECTIONS****
 ***RESUB SUBMITTED BY EMAIL***
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ENGINEER SPECIFIES A SYSTEM WHICH REFERS TO GENERAL
 LIMITATION #9.SEE NOA, NO ENHANCED FASTENING ALLOWED;
 THE SYSTEM IS LIMITED TO -52.5. (NOT ADDRESSED)
  
 2.ENGINEER HAS SPECIFIED 9 FASTENERS FOR ZONE 3 AND
 ZONE 1.IF 9 IS THE NUMBER NEEDED FOR -52.5 PSF, HOW
 COULD THAT BE SUFFICIENT FOR -114.9PSF? (REVISED, OK)
  
 3.ENGINEER HAS SPECIFIED 9 FASTENERS FOR ZONE 1.THE
 NOA STATES THAT THERE SHOULD BE ONE PER 3.2 SQUARE
 FEET.FOR A 32SF BOARD, THAT SHOULD BE 10 FASTENERS
 (32/3.2=10), NOT 9.WHEN RESUBMITTING, PLEASE SUBMIT
 CALCULATIONS TO SHOW HOW YOU HAVE ARRIVED AT THE
 FASTENING PATTERNS FOR ZONES 1 AND 3.IT IS UNCLEAR
 HOW YOU HAVE DETERMINED THE FASTENING WHICH IS IN
 CONFLICT WITH THE NOA. (REVISED, OK)
  
 4.ADDRESSED
  
 A SET HAS BEEN RETAINED.WHEN RESUBMITTING, PLEASE
 SUBMIT TWO COMPLETE SETS OF PERMIT DOCUMENTS (INCLUDING
 TWO NOAS).
  
 PLEASE PROVIDE TWO COMPLETE SIGNED, SEALED, ORIGINALS
 WITH TWO NOAS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-24 Cont ID  
Sent By shill Date 2007-10-24 Time 07:43 Rev Time 0.00
Received By shill Date 2007-10-24 Time 07:43 Sent To  
Notes
2007-10-24 07:51:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ENGINEER SPECIFIES A SYSTEM WHICH REFERS TO GENERAL
 LIMITATION #9.SEE NOA, NO ENHANCED FASTENING ALLOWED;
 THE SYSTEM IS LIMITED TO -52.5.
  
 2.ENGINEER HAS SPECIFIED 9 FASTENERS FOR ZONE 3 AND
 ZONE 1.IF 9 IS THE NUMBER NEEDED FOR -52.5 PSF, HOW
 COULD THAT BE SUFFICIENT FOR -114.9PSF?
  
 3.ENGINEER HAS SPECIFIED 9 FASTENERS FOR ZONE 1.THE
 NOA STATES THAT THERE SHOULD BE ONE PER 3.2 SQUARE
 FEET.FOR A 32SF BOARD, THAT SHOULD BE 10 FASTENERS
 (32/3.2=10), NOT 9.WHEN RESUBMITTING, PLEASE SUBMIT
 CALCULATIONS TO SHOW HOW YOU HAVE ARRIVED AT THE
 FASTENING PATTERNS FOR ZONES 1 AND 3.IT IS UNCLEAR
 HOW YOU HAVE DETERMINED THE FASTENING WHICH IS IN
 CONFLICT WITH THE NOA.
  
 4.WHEN RESUBMITTING, ENGINEER IS TO PROVIDE AN
 EXPLANATION AS TO HOW HE HAD ARRIVED AT DESIGN
 PRESSURES FROM FIRST REVIEW AND FASTENING PATTERNS FROM
 SECOND REVIEW (JUSTIFICATION FOR SIGNED, SEALED, DATED
 ENGINEERING CALCULATIONS SUBMITTED).
  
 A SET HAS BEEN RETAINED.WHEN RESUBMITTING, PLEASE
 SUBMIT TWO COMPLETE SETS OF PERMIT DOCUMENTS (INCLUDING
 TWO NOAS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By shill Date 2007-10-16 Time 15:08 Rev Time 0.00
Received By shill Date 2007-10-16 Time 15:08 Sent To  
Notes
2007-10-16 16:16:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE SHEET S2.1 OF THE BUILDING PLAN.ROOF
 COMPONENT & CLADDING DESIGN PRESSURES OF -35.3, -59.2,
 AND -89.1 REQUIRED FOR ZONES 1, 2, AND 3 RESPECTIVELY.
 EITHER REVISE THE BUILDING PLAN OR REVISE ROOF ENHANCED
 FASTENING DESIGN PRESSURES TO MEET THE DESIGN PRESSURES
 REQUIRED BY THE ENGINEER OF RECORD.IT IS ACCEPTABLE
 TO USE PRESSURES MORE CONSERVATIVE THAN THOSE SPECIFIED
 BY ENGINEER OF RECORD, BUT NOT LESS.IN THIS CASE, YOU
 ARE SPECIFYING PRESSURES HALF OF THE DESIGN PRESSURES
 REQUIRED BY THE EOR.
  
 2.)IF THE BUILDING PLAN IS REVISED TO REFLECT THE
 DESIGN PRESSURES SPECIFIED BY THE ROOF ENGINEER MARK DE
 STEFANO; -29.5, 39.8, AND -45.9 FOR ZONES 1, 2, AND 3
 CALCULATIONS WILL BE REQUIRED AS THE PRESSURES ARE
 SIGNIFICANTLY LESS THAN FBC TABLE 1609.6.2.1(2).IT IS
 THE OPINION OF THE FBPE INVESTIGATOR THAT ASCE7 IS MORE
 CONSERVATIVE THAN THE TABLE.ALTHOUGH I AM NOT AN
 ENGINEER AND DO NOT ATTEMPT TO PERFORM ENGINEERING, IF
 THE STATEMENT BY FBPE REPRESENTATIVE IS TRUE, LOGIC
 WOULD DICTATE THAT DESIGN PRESSURES FROM ASCE7 SHOULD
 BE AT LEAST NEARLY EQUIVALENT TO THE TABLE.IN THIS
 CASE, IT LESS THAN HALF.
  
 3.)THE ROOFING ENGINEER HAS DECLARED A DESIGN
 CRITERIA OF 145MPH, 2' PARAPET WALL, EXPOSURE B,
 FBC2004 WITH 2006 AMENDMENTS.EPR DECLARED 140MPH,
 EXPOSURE B, FBC2004 GOVERNING CODE.NOTE THE
 FOLLOWING:
  
 A.SEE ASCE7-02, FIGURE 17, NOTE 7.A 3' PARAPET WALL
 IS TO BE PROVIDED AROUND THE PERIMETER OF THE BUILDING
 IN ORDER TO USE ZONE 2 PRESSURES FOR ZONE 3.THE
 BUILDING PLAN SHOWS A 4' PARAPET WALL IN SOME AREAS BUT
 LESS THAN 2' IN OTHERS.NOTE THAT THE REQUIREMENT IS
 3' AROUND THE ENTIRE PERIMETER.IN OUR TELEPHONE
 CONVERSATION MR. DE STEFANO STATED THAT THE PRESSURES
 WERE REDUCED DUE TO THE PARAPET WALL.
  
 B.IF THE PARAPET WALL IS ACTUALLY NOT BUILT ACCORDING
 TO PLAN AND IS A MINIMUM OF 3' HIGH, PLEASE SEE FBC
 TABLE 1609.6.2.1(2).140MPH, 10SF, ZONE 2 REQUIRES A
 PRESSURE OF -59.2, 150MPH REQUIRES 67.9.USING
 INTERPOLATION, THE REQUIRED DESIGN PRESSURE FOR ZONE 2
 WOULD BE APPROXIMATELY 63.6 IF THE TABLE WAS USED.THE
 PRESSURE CALCULATED BY MR. DE STEFANO USING ASCE7,
 -45.9, IS SIGNIFICANTLY LESS.AS STATED ABOVE, IF THIS
 PRESSURE IS USED, CALCULATIONS WILL BE REQUIRED.
  
 C.MR. DE STEFANO STATED IN A TELEPHONE CONVERSATION
 THAT EXPOSURE C IS NEAR THE WATER.PLEASE NOTE THAT
 THE DEFINITION FOR EXPOSURE C HAS CHANGED EFFECTIVE
 DECEMBER 8, 2006.PLEASES SEE FBC1609.6.2.1(2),
 FBC1609.4.MR. DE STEFANO HAS DECLARED GOVERNING CODE
 AS FBC2004 WITH 2006 AMENDMENTS.IF THIS IS USED, IT
 APPEARS THAT THERE MAY BE OVER 600 FEET OF OPEN SPACE
 IN ONE OF THE QUADRANTS.HOWEVER, THE BUILDING WAS
 PERMITTED UNDER FBC2004 (NO AMENDMENTS; PRIOR TO
 DECEMBER 8, 2006) AND THIS APPLICATION CAN BE GOVERNED
 BY THE SAME CODE AS THIS IS A SUB PERMIT.THE
 GOVERNING CODE ON THE ROOF ENGINEERING MAY BE REVISED.
 IF YOU CHOOSE TO DESIGN UNDER GOVERNING CODE AT THE
 TIME OF ROOF PERMIT APPLICATION, THIS IS ACCEPTABLE BUT
 MUST SHOW EVIDENCE THAT THIS IS INDEED STILL EXPOSURE B
 (USING AERIALS OR A SITE PLAN), AND ALSO MUST INCLUDE
 2007 AMENDMENTS WHICH BECAME EFFECTIVE JULY 1, 2007.
  
 4.)THE NOA REVIEWED AND APPROVED BY ARCHITECT OF
 RECORD AND SUBMITTED BY ROOF CONTRACTOR WAS 03-0827.01.
 ROOF ENGINEERING REFERS TO NOA 04-0527.01.IF YOU ARE
 CHANGING PRODUCTS, DESIGNER OF RECORD IS TO REVIEW THE
 PRODUCT APPROVALS FBC*106.3.3.SUBMIT AS A REVISION TO
 THE MASTER PERMIT (BUILDING PERMIT).
  
 5.)AS IT IS NOT CLEAR WHAT PRODUCT IS BEING USED, OR
 WHAT THE DESIGN PRESSURES ARE, ENHANCED FASTENING FOR
 THE INSULATION BOARD RAS117 HAS NOT BEEN REVIEWED.
  
 6.)SEE FAC61G15-23.002 (WWW.FBPE.ORG).THE
 CERTIFICATE OF AUTHORIZATION IS REQUIRED ON EACH
 SHEET.
  
 7.)IF AN INDEX SHEET IS NOT USED, ALL INFORMATION
 REQUIRED BY FAC61G15-23.002 IS REQUIRED ON EACH SHEET
 AND EACH SHEET IS TO BE SIGNED, SEALED, AND DATED.
 NOTE THAT THIS REQUIREMENT APPLIES TO CALCULATIONS,
 SPECIFICATIONS, AND PLANS (BUT NOT REPORTS).AS THIS
 WOULD BE CONSIDERED EITHER A CALCULATION OR
 SPECIFICATION, PLEASE PROVIDE REQUIRED INFORMATION AND
 SEAL ON ALL SHEETS (OR PROVIDE AN INDEX SHEET IN
 ACCORDANCE WITH FAC61G15).
  
 8.)FROM PREVIOUS CORRECTION LIST, INDICATE WHICH
 ASSEMBLY IS BEING USED.THE ASSEMBLY ON PAGE 24, NOA
 03-0827.01 WAS SPECIFIED AND REVIEWED BY ARCHITECT WITH
 THE BUILDING PERMIT.IF THIS IS NOT THE ASSEMBLY BEING
 USED, THIS SHOULD BE SUBMITTED AS A REVISION.THE
 ENGINEER SHOULD REFER TO THE ASSEMBLY AS WELL AS THE
 NOA ON THE RAS117 CALCULATION.
  
 9.)THE BUILDING PERMIT INCLUDED A WEATHERGUARD
 UNDERLAYMENT AND MONIER TILE FOR THE MANSARD.PLEASE
 INCLUDE THESE PRODUCT APPROVALS WHEN RESUBMITTING.
  
 10.)FOR THE TILE, PLEASE CIRCLE WHICH METHOD OF
 ATTACHMENT YOU ARE USING.IF YOU ARE USING A FOAM
 ADHESIVE, PROVIDE THAT PRODUCT APPROVAL AS WELL,
 FAC9B72.
  
 IF THE ENGINEER DISAGREES WITH ANY OF THE COMMENTS,
 PLEASE EITHER CONTACT ME TO DISCUSS OR RESPOND IN
 WRITING WHEN RESUBMITTING.A SET HAS BEEN RETAINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-04 Cont ID  
Sent By shill Date 2007-10-04 Time 16:15 Rev Time 0.00
Received By shill Date 2007-10-04 Time 16:15 Sent To  
Notes
2007-10-04 16:16:46****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD (ARCHITECT OR ENGINEER), EITHER WITH
 A SHOP DRAWING REVIEW STAMP OR LETTER, FBC*106.3.3.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO
 BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED
 ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB
 SHEET).
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 _XX_ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  