Plan Review Details - Permit 07100053
Plan Review Stops For Permit 07100053
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-25 Cont ID  
Sent By rmcdouga Date 2008-02-25 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2008-02-25 Time 07:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-07 Cont ID  
Sent By rmcdouga Date 2007-11-07 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2007-11-07 Time 18:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By rmcdouga Date 2007-10-25 Time 09:16 Rev Time 0.00
Received By rmcdouga Date 2007-10-25 Time 09:16 Sent To  
Notes
2007-10-25 10:40:402004 FBC W/2007 REVISIONS
 REHAB SFR
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT 2 COPIES OF THE SCOPE OF WORK DESCRIPTION.
 FBC 106.1 CITY AMENDMENTS
  
 3) SUBMIT 2 COPIES OF A FLOOR PLAN WITH A CORRESPONDING
 WINDOW SCHEDULE SHOWING THE LOCATIONS OF THE WINDOWS
 THAT ARE BEING REPLACED. CITY AMENDMENTS FBC 106.1.1
 AND 106.1.2.
  
 4) THE AAMA CERTIFICATION THAT WAS SUBMITTED FOR THE
 H-R SINGLE HUNG WINDDOWS SHOWS THAT IT EXPIRED ON JUNE
 20, 2007. THE REPORT ALSO NOTES THAT ALL CERTIFIED
 WINDOWS MUST BE GLAZED WITH TEMPERED GLASS. PLEASE
 CORRECT. FAC RULE 9B-72
  
 5)SHOW COMPLIANCE WITH FBC EXISTING BUILDING 505.1
 GENERAL.
 MEANS OF EGRESS FOR BUILDINGS UNDERGOING ALTERATION
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 501.1 AND
 THE SCOPING PROVISIONS OF CHAPTER 1 WHERE APPLICABLE.
 EXCEPTION: DOOR AND WINDOW DIMENSIONS. IN RESIDENTIAL
 DWELLINGS AND DWELLING UNITS, A MAXIMUM OF 5 PERCENT
 REDUCTION IN THE CLEAR OPENING DIMENSIONS OF
 REPLACEMENT DOORS AND WINDOWS SHALL BE ALLOWED.
  
 6) FBC 507.3 IF REPLACING MORE THAN 25% OF THE
 AGGREGATE AREA OF THE GLAZED OPENINGS IN THE DWELLING,
 REQUIRES GLAZED OPENINGS TO BE IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING. SUBMIT
 PRODUCT APPROVALS FOR STORM PANELS OR IMPACT WINDOWS.
 IF STORM PANELS WILL BE USED, SUBMIT A KEY PLAN AND
 INSTALLATION SCHEDULE INDICATING THE MOUNT TYPE, ANCHOR
 TYPE AND SPACING, EDGE DISTANCE GLASS SEPARATION, SPANS
 ETC. SEE ATTACHED SAMPLE.
  
 7) SUBMIT THE PRODUCT APPROVALS FOR THE 7 NEW WINDOWS
 THAT THE OWNER HAS. IF THERE ARE NO PRODUCT APPROVALS
 FOR THEM THEY CAN NOT BE INSTALLED. SEE FAC RULE
 9B-72.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-06 Cont ID  
Sent By btrobaug Date 2007-11-06 Time 07:55 Rev Time 0.00
Received By btrobaug Date 2007-11-06 Time 07:48 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By btrobaug Date 2007-10-10 Time 07:55 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 07:33 Sent To M
Notes
2007-10-10 07:55:49 
  
 APPLICATION # 07100053
 ELECTRICAL PLAN REVIEW
 519 41ST STREET
 10/10/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED,
 INCLUDE THE ADDED A/C SYSTEM AND INDICATE THE RATING OF
 THE EXISTING SERVICE. THIS IS TO DETERMINE IF THE
 SERVICE IS ADEQUATE FOR THE ADDED LOAD.
  
 2} PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED
 WITH THE APPLICATION PER 106.1 FBC AS AMENDED. SHOW THE
 LOCATION OF THE A/C EQUIPMENT ON THE PLAN. ALSO SHOW
 COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14,
 RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3). THE
 FLOOR PLAN SHALL ALSO INDICATE THE LOCATION OF ALL
 ELECTRICAL WORK UNDER THE SCOPE OF THIS APPLICATION.
  
 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE
 SAME ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-22 Cont ID  
Sent By adarroug Date 2008-02-22 Time 10:37 Rev Time 0.00
Received By adarroug Date 2008-02-22 Time 10:37 Sent To B
Notes
2008-02-22 10:38:15TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 12:06 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 12:06 Sent To E
Notes
2007-11-05 12:06:57TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-25 Cont ID  
Sent By rmcdouga Date 2007-10-25 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2007-10-03 Time 12:38 Sent To  
Notes
2007-10-03 12:39:27TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-06 Cont ID  
Sent By tgordon Date 2007-11-06 Time 10:43 Rev Time 0.30
Received By tgordon Date 2007-11-06 Time 10:42 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By tgordon Date 2007-10-16 Time 10:50 Rev Time 0.25
Received By tgordon Date 2007-10-16 Time 10:50 Sent To P
Notes
2007-10-16 10:52:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR LICENSE NUMBER, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-10-24 Cont ID  
Sent By jleech Date 2007-10-24 Time 07:18 Rev Time 0.00
Received By jleech Date 2007-10-24 Time 07:18 Sent To B
Notes
2007-10-24 07:19:11NO PLUMBING SHOWN WITH THIS APPLICATION