Plan Review Details - Permit 07100050
Plan Review Stops For Permit 07100050
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By mjacobs Date 2007-10-12 Time 15:04 Rev Time 0.00
Received By mjacobs Date 2007-10-12 Time 08:57 Sent To  
Notes
2007-10-12 15:03:55 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07100050
 ADD: 5600 N. FLAGLER DR. #2409
 CONT: WILLIAM BELL CONST. INC.
 TEL: (561)741-8655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 10/12/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLEASE SUBMIT 2 SETS OF, PLANS, REPORTS, REVISIONS,
 PRODUCT APPROVALS AND OR SUBMITTALS FOR REVIEW FOR
 PERMIT. IF YOUR PROJECT WILL REQUIRE A RESIDENT
 INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD BUILDING
 REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE SETS OF
 ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH 2006
 REVISIONS.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 E) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 -------------------------
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
  
 5)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE PRODUCT APPROVALS FOR
 THE ?SLIDING GLASS DOORS? ALONG WITH THE DESIGN
 PRESSURE CALCULATIONS FROM AN ENGINEER.
  
 6)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, ARCHITECTURAL AND DESIGN FEES AND OVERHEAD AND
 PROFIT; EXCLUDING LAND. OUR
  
 7)FBC TABLE 803.5 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY.
  
 8)PROVIDE A FRAMING DETAIL FOR THE ?SOFFITS AND THE
 NEW SHOWER SEAT?.SUBMIT THE UL NUMBER FOR THE NEW
 FIRE RATED PARTITION/ PARTY WALL.
  
 9) FBC 106.1 SUBMIT TWO COMPLETE SETS OF PLANS PREPARED
 BY A DESIGN PROFESSIONAL WITH HIS/HER ?LEGIBLE?
 OFFICIAL SEAL, SIGNATURE, DATE AND THE PRINTED NAME AND
 NUMBER OR THE PERSON RESPONSIBLE FOR SIGNING THE PLANS
 PRE FLORIDA STATUTES 471 AND 481. ONE SET OF THE PLANS
 IS MISSING THE SEAL AND ORIGINAL SIGNATURE OF THE
 DESIGN PROFESSIONAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-10-11 Cont ID  
Sent By btrobaug Date 2007-10-11 Time 16:10 Rev Time 0.00
Received By btrobaug Date 2007-10-11 Time 15:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mawillia Date 2007-10-22 Time 14:58 Rev Time 0.00
Received By mawillia Date 2007-10-22 Time 14:29 Sent To  
Notes
2007-10-22 14:50:41*****UNSAT*****
  
  
 1.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED. SEE SHEET A-1 IN GENERAL NOTE #1.
  
 2.ON SHEET E-1, CHANGE SMOKE DETECTORS (SD) TO SMOKE
 ALARMS (SA).PLEASE BE ADVISED THAT SMOKE DETECTORS
 ARE TIED INTO THE BUILDING'S FIRE ALARM SYSTEM, WHEREAS
 SMOKE ALARMS ALERT THE OCCUPANTS OF THE SAID TENANT
 SPACE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-22 Cont ID  
Sent By mawillia Date 2007-10-22 Time 14:29 Rev Time 0.00
Received By mawillia Date 2007-10-03 Time 14:50 Sent To  
Notes
2007-10-09 15:37:14TO "BOB"#4
2007-10-03 14:54:28WAITING FOR "BOB"

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By jleech Date 2007-10-22 Time 09:20 Rev Time 0.00
Received By jleech Date 2007-10-22 Time 09:20 Sent To  
Notes
2007-10-22 09:22:00ONLY ONE SET OF PLANS SEALED. PLUMBING OK FIXTURE
 CHANGE OUT ONLY.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-10 Cont ID  
Sent By choops Date 2007-10-10 Time 15:16 Rev Time 0.00
Received By choops Date 2007-10-10 Time 15:16 Sent To  
Notes
2007-10-10 15:16:23*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.