Plan Review Details - Permit 07100044
Plan Review Stops For Permit 07100044
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-25 Cont ID  
Sent By rmcdouga Date 2007-10-25 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2007-10-25 Time 07:05 Sent To  
Notes
2007-10-25 07:50:152004 FBC W/2007 REVISIONS
 INSTALL 1/2 BATH UNDER STAIRS
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROPOSED WORK DOES NOT COMPLY WITH R305.1 MINIMUM
 HEIGHT.
 HABITABLE ROOMS, HALLWAYS, CORRIDORS, BATHROOMS, TOILET
 ROOMS, LAUNDRY ROOMS AND BASEMENTS SHALL HAVE A CEILING
 HEIGHT OF NOT LESS THAN 7 FEET (2134 MM). THE REQUIRED
 HEIGHT SHALL BE MEASURED FROM THE FINISH FLOOR TO THE
 LOWEST PROJECTION FROM THE CEILING EXCEPTIONS: 4.
 BATHROOMS SHALL HAVE A MINIMUM CEILING HEIGHT OF 6 FEET
 8 INCHES (2036 MM) OVER THE FIXTURE AND AT THE FRONT
 CLEARANCE AREA FOR FIXTURES AS SHOWN IN FIGURE R307.2 .
  
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By btrobaug Date 2007-10-10 Time 15:32 Rev Time 0.00
Received By btrobaug Date 2007-10-10 Time 15:25 Sent To M
Notes
2007-10-10 15:31:15 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 422.31(B) FOR PERMANENTLY CONNECTED APPLIANCES RATED
 OVER 300 VOLT-AMPERES OR1/ 8 HP, THE BRANCH-CIRCUIT
 SWITCH OR CIRCUIT BREAKER SHALL BE PERMITTED TO SERVE
 AS THE DISCONNECTING MEANS WHERE THE SWITCH OR CIRCUIT
 BREAKER IS WITHIN SIGHT FROM THE APPLIANCE OR IS
 CAPABLE OF BEING LOCKED IN THE OPEN POSITION. THE
 PROVISION FOR LOCKING OR ADDING A LOCK TO THE
 DISCONNECTING MEANS SHALL BE INSTALLED ON OR AT THE
 SWITCH OR CIRCUIT BREAKER USED AS THE DISCONNECTING
 MEANS AND SHALL REMAIN IN PLACE WITH OR WITHOUT THE
 LOCK INSTALLED. INDICATE LOCATION OF THE DISCONNECTING
 MEANS
  
 2} 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
  
 3} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 COMPLIANCE ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-25 Cont ID  
Sent By rmcdouga Date 2007-10-25 Time 07:51 Rev Time 0.00
Received By rmcdouga Date 2007-10-03 Time 15:01 Sent To  
Notes
2007-10-03 15:01:18TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By tgordon Date 2007-10-16 Time 11:00 Rev Time 0.20
Received By tgordon Date 2007-10-16 Time 11:00 Sent To P
Notes
2007-10-16 11:03:31PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SHOW ON PLAN IF THE EXISTING WATER HEATER IS
 ELECTRIC OR GAS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-24 Cont ID  
Sent By jleech Date 2007-10-24 Time 07:30 Rev Time 0.00
Received By jleech Date 2007-10-24 Time 07:30 Sent To B
Notes
2007-10-24 07:36:06DENIED;
 1. IS WATER HEATER GAS OR ELECTRIC? WATER HEATER IS NOT
 SERVICEABLE AS DRAWN.
 2. IT NOT CLEAR IF CLEARANCES BETWEEN TOILET AND
 LAVATORY AND LAVATORY AND WALL WILL COMPLY WITH
 FBC-2004 PLUMBING SECTION 405.3.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695