Plan Review Stops For Permit 07100028
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-30 Cont ID  
Sent By btrobaug Date 2007-10-30 Time 10:14 Rev Time 0.00
Received By btrobaug Date 2007-10-30 Time 10:14 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By btrobaug Date 2007-10-09 Time 16:00 Rev Time 0.00
Received By btrobaug Date 2007-10-09 Time 15:26 Sent To I
Notes
2007-10-09 16:00:17 
  
 APPLICATION #07100028
 ELECTRICAL PLAN REVIEW
 3900 GEORGIA AVENUE
 10/9/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PROPERTY FOR WHICH THIS APPLICATION WAS
 SUBMITTED HAS MORE THAN ONE BUILDING. PROVIDE A SITE
 PLAN INDICATING WHICH BUILDING AND THE LOCATION THE
 PROPOSED SERVICE IS TO BE INSTALLED. ALSO NOTE 230.2
 AND INDICATE COMPLIANCE WITH SAME.
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 3} INDICATE COMPLIANCE WITH ARTICLE 230.70(A)(1), THE
 AHJ HAS DETERMINED THAT ?NEAREST POINT OF ENTRANCE?
 SHALL BE NO FARTHER THAN 8? OF UNPROTECTED CONDUCTORS.
 INDICATE COMPLIANCE WITH THIS ARTICLE ON THE PLAN.
  
 4} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66 AND 250.50. INDICATE COMPLIANCE ON THE RISER
 DIAGRAM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-30 Cont ID  
Sent By btrobaug Date 2007-10-30 Time 10:15 Rev Time 0.00
Received By btrobaug Date 2007-10-02 Time 12:49 Sent To PC
Notes
2007-10-02 12:49:19TO "E" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved