Plan Review Details - Permit 07100024
Plan Review Stops For Permit 07100024
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By mjacobs Date 2007-10-10 Time 11:17 Rev Time 0.00
Received By mjacobs Date 2007-10-10 Time 07:15 Sent To  
Notes
2007-10-10 11:17:00 
 BUILDING PLAN REVIEW
 PERMIT: 07100024
 ADD: 3201 ELECTRONIC WAY.
 CONT: M.A.C. CONSTRUCTION INC.
 TEL: (305)598-4317
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS
 & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING A) THE EDITION OF
 THE CODE UNDER WHICH THE PROJECT IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 . -------------------------------------
  
 4)106.1.2 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY
 REQUIRE DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND
 OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION OR
 INSTALLATION AND THE BASIS OF CALCULATION. THE PLANS
 SUBMITTED REQUIRE MORE INFORMATION ON THE AREA FOR THE
 PROJECT. THE SQUARE FOOTAGE OF ROOM SHALL BE INDICATED
 ON THE PLANS. SUBMIT THE NORTH/ SOUTH/ EAST AND WEST
 ELEVATION DRAWINGS OF THE ROOM WHERE THE NEW OFFICES
 WILL BE INSTALLED.
  
 5)FBC 505.2 MEZZANINES SHALL NOT EXCEED ONE-THIRD OF
 THE AREA OF THE ROOM OR SPACE IN WHICH THEY ARE
 LOCATED. PROVIDE DRAWING WHICH MEET THE REQUIREMENTS OF
 FBC 505.
  
 6)INDICATE THE OCCUPANT LOAD OF THE MEZZANINE AND
 SHOW THE MEANS OF EGRESS. A LIFE SAFETY SHALL ALSO BE
 SUBMITTED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-06 Cont ID  
Sent By dpalmer Date 2007-10-06 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2007-10-05 Time 16:59 Sent To  
Notes
2007-10-06 13:50:05 
 *** DENIED ***
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE INDICATE THE REQUIRED AUTOMATED
 LIGHTING CONTROLS FOR NEW SWITCHING DEVICES BEING
 INSTALLED PER 13-415.1.ABC.1.1, .1.2.
 PLEASE BE SURE TO STATE THE MAXIMUM TIMES ON DEVICES.
 PLEASE EXPLAIN HOW IT IS ENERGY CALCULATIONS ARE BEING
 SUBMITTED UNDER METHOD *A* WHEN THE SCOPE OF WORK BEING
 DONE IS NOT FOR WHOLE BUILDING?
 METHOD *A* MAY NOT BE USED AND PLEASE SEE MECHANICAL
 REVIEW COMMENTS.
 THIS REVIEWER ONLY NEEDS LIGHTING PERFORMANCE LEVELS
 PER 13-415.2, TABLE B OR C.
 PLEASE CALL TO GO OVER ANY OF THIS.
  
 3) NOTE: PLEASE SEE THE NEW STAIRS BEING INSTALLED ARE
 NOT SHOWING ANY LIGHTING WHICH IS REQUIRED PER NFPA-101
 7.8 AND 7.9.
 PLEASE SUBMIT AND SHOW THE MINIMUM PHOTO-METRIC LEVELS
 UNDER NORMAL AND EMERGENCY CONDITIONS FOR NEW STAIRS.
 7.8.1.3, 7.9.2.2
 EVEN AS PLANS MENTIONS THESE STAIRS ARE NOT PART OF THE
 *REQUIRED EGRESS*, THESE WILL STILL BE SUED FOR EGRESS
 IN ANY EVENT AND LIGHTING LEVELS ARE REQUIRED WHETHER
 OR NOT PART OF THE *REQUIRED EGRESS STAIRS*,
 FAC 61G15-33.004.
 FBC 106.1.2.
  
 4) NOTE: PLEASE SHOW THE TOTAL LOADS ON PANEL NLA.
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%.
 220, 215.5, 230.42 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 5) NOTE: PLEASE KNOW EVEN AS THE FIRE ALARM DEVICES ARE
 REQUIRED TO BE UNDER SEPARATE PERMITS, THE BASE BUILD
 OUT/REMODEL PLANS WILL STILL BE REQUIRED TO SHOW
 LOCATIONS FOR ADA COMPLIANCE ALONG WITH THE MINIMUM
 REQUIRED LEVELS PER FBC 11-4.28.1,.2 AND .3(4).
 PLEASE DO NOT QUOTE THE CODE AS THE REQUIRED MINIMUM
 LOCATIONS AND LEVELS ARE NEEDED ON PLANS.
  
  
 ** PLEASE KNOW AS NO LIGHTING OR INFORMATION WAS
 SUBMITTED FOR NEW STAIRS, THERE ARE ITEMS WHICH CAN NOT
 BE REVIEWED AT THIS TIME AND THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER DIRECTLY.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By mawillia Date 2007-10-15 Time 16:44 Rev Time 0.00
Received By mawillia Date 2007-10-15 Time 15:56 Sent To  
Notes
2007-10-15 16:44:07*****DENIED*****
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE
 HANDRAILS/GUARDRAILS.
  
 5.THE NEW STAIRS SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 6.THESE OUTSIDE STAIRS SHALL BE DESIGNED TO MINIMIZE
 WATER ACCUMULATION ON THEIR SURFACES.
  
 7.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THIS PREFAB OFFICE IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF
 CLASS I OR CLASS II.
  
 8.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 MODIFICATION TO THE FIRE SPRINKLER AND/OR FIRE ALARM
 SYSTEM.AS PER WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT, SUB-PERMITS SHALL NOT BE REVIEWED AND
 ATTAINED UNTIL SUCH TIME THAT THE MASTER PERMIT HAS
 BEEN ISSUED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-15 Cont ID  
Sent By mawillia Date 2007-10-15 Time 15:56 Rev Time 0.00
Received By mawillia Date 2007-10-02 Time 16:57 Sent To  
Notes
2007-10-05 15:26:31TO "BOB"#18
2007-10-02 16:57:18WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-10-15 Cont ID  
Sent By tgordon Date 2007-10-15 Time 11:01 Rev Time 0.25
Received By tgordon Date 2007-10-15 Time 11:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-10-10 Cont ID  
Sent By choops Date 2007-10-10 Time 15:11 Rev Time 0.00
Received By choops Date 2007-10-10 Time 15:11 Sent To  
Notes
2007-10-10 15:12:05*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.