Plan Review Details - Permit 07100001
Plan Review Stops For Permit 07100001
Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2009-12-01 Cont ID  
Sent By jwitmer Date 2009-12-01 Time 11:25 Rev Time 1.33
Received By jwitmer Date 2009-12-01 Time 10:30 Sent To  
Notes
2009-12-01 12:24:59BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADD: 1501 N AUSTRALIAN AVE
 CONT: BRADANNA INC.
 TEL: (561)722-1425
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW OF THE EXISTING NORTH WING
 DATED 10-12-09
  
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) SHEET LS-100, A-101 & A-700 INDICATE A REVISION IN
 DOORS 6, 8,9,10 & 35 ALL BEING REVISED TO NEW 45 MINUTE
 DOORS, THE ISSUE IS THEY ARE EXISTING 2'-6" WIDE.
 PLEASE REVIEW SECTION 11-4.6(1)(B)IF EXISTING ELEMENTS,
 SPACES, OR COMMON AREAS ARE ALTERED, THEN EACH SUCH
 ALTERED ELEMENT, SPACE, FEATURE, OR AREA SHALL COMPLY
 WITH THE APPLICABLE PROVISIONS OF SECTION 11-4.1.1 TO
 SECTION 11-4.1.3, MINIMUM REQUIREMENTS FOR NEW
 CONSTRUCTION. IF THE APPLICABLE PROVISION FOR NEW
 CONSTRUCTION REQUIRES THAT AN ELEMENT, SPACE, OR COMMON
 AREA BE ON AN ACCESSIBLE ROUTE, THE ALTERED ELEMENT,
 SPACE, OR COMMON AREA IS NOT REQUIRED TO BE ON AN
 ACCESSIBLE ROUTE EXCEPT AS PROVIDED IN SECTION
 11-4.1.6(2), ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION.
  
 11-4.1 MINIMUM REQUIREMENTS.
 11-4.1.1 APPLICATION.
 (1) GENERAL. THIS CODE ESTABLISHES THE MINIMUM
 STANDARDS FOR THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN THE STATE.
 (B) REMOVAL OF ARCHITECTURAL BARRIERS FROM BUILDINGS,
 STRUCTURES, OR FACILITIES SHALL COMPLY WITH SECTION
 11-4.1.8 OF THIS CODE UNLESS COMPLIANCE WOULD RENDER
 THE REMOVAL NOT READILY ACHIEVABLE. IN NO INSTANCE
 SHALL THE REMOVAL OF AN ARCHITECTURAL BARRIER CREATE A
 SIGNIFICANT RISK TO THE HEALTH OR SAFETY OF AN
 INDIVIDUAL WITH A DISABILITY OR OTHERS.
  
 11-4.1.3 ACCESSIBLE BUILDINGS: NEW CONSTRUCTION.
 THIS EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES, OR FACILITIES WHICH WERE EITHER UNDER
 CONSTRUCTION OR UNDER CONTRACT FOR CONSTRUCTION ON (OR
 BEFORE) OCTOBER 1, 1997.
 (1) AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR
 FACILITY ENTRANCES WITH ALL ACCESSIBLE SPACES AND
 ELEMENTS WITHIN THE BUILDING OR FACILITY.
  
 ARCHITECTURAL SHEETS SUBMITTED:
 LS-1
 A-101
 A-102
 A-700
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2009-10-26 Cont ID  
Sent By jwitmer Date 2009-10-26 Time 12:15 Rev Time 0.75
Received By jwitmer Date 2009-10-26 Time 11:30 Sent To  
Notes
2009-10-26 11:58:59I-LAG 750 SD SELF TAPPING FASTENER
 INTERIOR METAL FRAMING SHOP DRAWINGS
 PRE-CAST COLUMN SHOP DRAWINGS & PRODUCT DATA

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status F Date 2009-10-07 Cont ID  
Sent By jwitmer Date 2009-10-07 Time 11:07 Rev Time 0.77
Received By jwitmer Date 2009-10-07 Time 11:07 Sent To  
Notes
2009-10-07 11:25:49BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: BRADANNA
 TEL: (239)455-8891
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 OCT. 7/ 2009
 ACTION: DENIED
  
 1) SUBMITTAL OCT 1/2009 IS NOT A SUBMITTAL BUT A
 REVISION WIWTH FEES, ($170.00) SIGNED AND SEALED PLANS
 CAN NOT HAVE WHITEOUT SHEET S-1 HAS WHITE OUT ON ALL
 THREE SHEETS, THIS IS ALSO THE SHEET THAT THE DESIGNER
 OF RECORD AFFIXED THEIR STAMP OF APPROVAL PLEASE
 PROVIDE 3 NEW S-1 SHEETS WITH-OUT WHITE OUTAND HAVE
 BEEN REVIEWED BY THE DESSIGNER OF RECORD. 106.1.1*.
  
 .
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2009-09-29 Time 16:31 Sent To  
Notes
2009-09-29 16:33:14REVISIONS:
 A-104 REVISION# 11 6-11-09
 A-601
 ENERGY CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status F Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 08:50 Rev Time 1.00
Received By jwitmer Date 2009-09-08 Time 08:00 Sent To  
Notes
2009-09-08 08:57:30BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: BRADANNA
 TEL: (239)455-8891
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 SEPT. 8/ 2009
 ACTION: DENIED
  
 ENERGY CALCS/ A-104 & A-601
  
 PLEASE SEE SHEET A-601 DETAIL# 11 TAPERED ROOF
 INSULATION AT ROOF DRAIN INDICATES A TAPER TO NO
 INSULATION 13-404.1 ABCD.1 REQUIRES A MINIMUM OF R-10
 EVEN AT THE ROOF DRAIN SUMP.
  
 BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 NOVEMBER 18,2008
 5TH REVIEW- MAJOR WORKING DRAWING REVIEW
 ACTION: DENIED

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2009-08-27 Cont ID  
Sent By jwitmer Date 2009-08-27 Time 15:43 Rev Time 0.50
Received By jwitmer Date 2009-08-27 Time 15:03 Sent To  
Notes
2009-08-27 15:36:24ROOFING REVISIONS:
 PRODUCT APPROVALS;
 FIBERTITE SINGLE PLY ROOF SYSTEMS
 CELLUCRETE ROOF PLAN
 DYPLAST PRODUCT DATA
 ENGINEERED CALCS
 ENGLERT SERIES 1300
 CALCS
 SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2009-08-20 Cont ID  
Sent By jwitmer Date 2009-08-20 Time 11:08 Rev Time 0.50
Received By jwitmer Date 2009-08-20 Time 11:08 Sent To  
Notes
2009-08-20 11:27:138X11 REVISIONS 16 K BAR JOIST ADDITIONAL SUPPORT DETAIL
 FOR 1 SEMCO FV-3000 ERV
  
 8X11 REVISION SOFFIT DETAIL FOR CURVED METAL ROOF

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2009-07-08 Cont ID  
Sent By jwitmer Date 2009-07-08 Time 11:59 Rev Time 1.00
Received By jwitmer Date 2009-07-08 Time 11:00 Sent To  
Notes
2009-07-08 11:56:53REVIEWED: A-102,A-103, A-200, A-201, A-300, A-301,
 A-401, A-602 & A-603 & A-606

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2009-06-17 Cont ID  
Sent By jwitmer Date 2009-06-17 Time 13:45 Rev Time 0.77
Received By jwitmer Date 2009-06-17 Time 13:01 Sent To PC
Notes
2009-06-17 13:19:46BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :BRADANNA
 TEL: (561) 722-1425 BILL LYNCH
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 JUNE 17/ 2009
  
 ACTION: REVIEWED
  
 1) STRUCTURAL RESPONSE TO RFI NO 70
  
 2) STRUCTURAL RESPONSE TO RFI NO 71
  
 3) STRUCTURAL RESPONSE TO RFI NO 72
  
 4) STRUCTURAL RESPONSE TO RFI NO 73
  
 5) STRUCTURAL RESPONSE TO RFI NO 74
  
 6) REVISED S-2 REV13, & S-4.3 REV 13.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2009-06-02 Cont ID  
Sent By jwitmer Date 2009-06-02 Time 15:55 Rev Time 0.45
Received By jwitmer Date 2009-06-02 Time 15:30 Sent To  
Notes
2009-06-02 15:45:59BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :BRADANNA
 TEL: (561) 722-1425 BILL LYNCH
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 MAY 29/2009
  
 ACTION: REVIEWED
  
 1) SHORING PLAN -
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2009-05-29 Cont ID  
Sent By jwitmer Date 2009-05-29 Time 11:38 Rev Time 0.77
Received By jwitmer Date 2009-05-29 Time 11:38 Sent To  
Notes
2009-05-29 11:41:38BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :BRADANNA
 TEL: (561) 722-1425 BILL LYNCH
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 MAY 29/2009
  
 ACTION: DENIED
  
 1) SHORING PLAN - FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2009-05-11 Cont ID  
Sent By jwitmer Date 2009-05-11 Time 12:25 Rev Time 2.00
Received By jwitmer Date 2009-05-11 Time 10:25 Sent To  
Notes
2009-05-11 11:01:25STRUCTURAL STEEL SHOP DRAWINGS: ALPROJAM WELDING
 A/8,E1,E2,E3, 1,2& 3MARCH 29 FINAL TO GC
 ENGINEERS LETTER ON RE-USE OF JOIST SUPPORT CLIP,
 PRODUCED BY THE ENGINEER OF RECORD.
 STRUCTURAL STEEL CALCULATIONS FOR STEEL JOIST DESIGN
 SUBMITTAL # 34R2 STOREFRONT SHOP DRAWINGS/
 NOAYKK06-1026.08

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2009-04-29 Cont ID  
Sent By jwitmer Date 2009-04-29 Time 14:47 Rev Time 0.66
Received By jwitmer Date 2009-04-29 Time 14:07 Sent To PC
Notes
2009-04-29 14:49:13REVISION # 12 S-2, S3.3 & S-4.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-04-08 Cont ID  
Sent By jwitmer Date 2009-04-08 Time 15:44 Rev Time 2.22
Received By jwitmer Date 2009-04-08 Time 15:44 Sent To PC
Notes
2009-04-08 15:46:07REVISION# 11 STRUCTURAL ROOF REVISIONS, AS BUILTS
 S1.1
 S1.2
 S2.0
 S3.1
 S3.3
 S4.1
 S4.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-04-07 Cont ID  
Sent By jwitmer Date 2009-04-07 Time 16:33 Rev Time 1.33
Received By jwitmer Date 2009-04-07 Time 16:33 Sent To  
Notes
2009-04-07 16:37:42REVISONS:
 R#12, A-104 2/25/09
 R# 12, A-601 2/25/09
 R# 10, S-5.1 3/10/09
 R# 10, S-5.2 3/10/09
 R#10, S-5.3 3/10/09

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-01-06 Cont ID  
Sent By jwitmer Date 2009-01-06 Time 13:49 Rev Time 3.33
Received By jwitmer Date 2009-01-06 Time 13:49 Sent To PC
Notes
2009-01-06 13:50:07BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 DECEMBER 19 ,2008
 6TH REVIEW-
 ACTION: REVIEWED OK TO ISSUE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-01-05 Cont ID  
Sent By jwitmer Date 2008-12-19 Time 10:25 Rev Time 4.44
Received By jwitmer Date 2008-12-19 Time 10:25 Sent To  
Notes
2008-12-19 13:17:05BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 DECEMBER 19 ,2008
 6TH REVIEW-
 ACTION: DENIED
  
  
 MET WITH ISREL ROZENTAL AIA, ABOUT PLANS,ENERGY CALCS,
 AND ROOFING PRODUCT APPROVALS, ULYSSIS WILL BRING BACK
 EITHER OR NEW ENERGY CALCS, PLANS AND ADDITIONAL
 INFORMATION AS TO WHICH SUB-SYSTEM TO BE INSTALLED ON
 THE FLAT ROOF. BY THE FIRST OF NEXT WEEK 12-22 OR
 12-23, REVIEW IS ON HOLD.
  
 1-02-09 CALLED KEN HAWKINS, KEN IS SUPPOSE TO BRING IN
 NEW A-104 & A-601 SHEETS MONDAY 1-05-09 BY 10:00AM.
  
  
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-11-18 Cont ID  
Sent By jwitmer Date 2008-11-18 Time 14:45 Rev Time 4.44
Received By jwitmer Date 2008-11-18 Time 14:45 Sent To  
Notes
2008-11-18 16:25:59BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 NOVEMBER 18,2008
 5TH REVIEW- MAJOR WORKING DRAWING REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT.
  
 1B-E)COMPLIED.
  
 217) COMPLIED
  
 18) 3RD REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF ALL PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
  
 G) ROOF ASSEMBLIES-NOA 05-1220.07 FIBERTITE SINGLE PLY,
 SUB-SYSTEM PAGE 19, DECK TYPE 4: LIGHTWEIGHT CONCRETE,
 NON-INSULATED PLEASE SEE A-602 DETAIL# 1 AS WELL AS THE
 ENERGY CALCULATION INPUT DATA SHEETS BOTH INDICATING
 THERE TO BE A MINIMUM OF 6" OF INSULATION. PLEASE
 PROVIDE THE RIGHT SUB-SYSTEM (INSULATED )INDICATING A
 MINIMUM OF -89 FOR ZONE 3 OR ENHANCED FASTENING BY
 EITHER A ARCHITECT OR ENGINEEER.
  
 H) ENGLERT 2000 SERIES METAL ROOF PANEL OVER STEEL
 DECKDECK TYPE NOT INDICATED DECK TYPE A-1 MAXIMUM
 PRESSURE OF 62.5 PSF, 18 INCH PANELS, DECK TYPE A-2 A
 14" WIDE PANEL MAXIMUM UPLIFT -144.25
 NEITHER THE DETAIL# 1 ON A-602 NOR DETAIL2 0N A-603
 INDICATE THE THICKNESS OF THE RIGID FOAM INSULATION.
 THE ENGLERT PRODUCT APPROVAL DOES REQUIRE A PRODUCT
 APPROVAL FOR THE RIGID BOARD INSULATION PLEASE SEE
 INSULATION OPTIONAL REQUIREMENTS.
  
 19-20) COMPLIED.
  
  
 21) SEE 18G ABOVE.2ND REQUEST,
  
 22-23) COMPLIED.
  
 24) 3RD REQUEST, ARCHITECTURAL PLANS ARE DEFICIENT IN
 INFORMATION FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 24A) COMPLIED.
  
 24B) SHEET A-700 FLOOR FINISHES INDICATES 2730 SQ FT OF
 FLOOR THAT DOES NOT HAVE CARPET AND PADDING AS A
 INSULATOR BUT DOES NOT SHOW UP ONT THE ENERGY
 CALCULATION. NOT ALSO THE GENERATOR ROOM AND ELECTRIC
 ROOM FLOORS WILL NOT HAVE CARPET AND PADDING INSULATED
 VALUE WAS TAKEN. 13-405.2ABENERGY CALCS DATED 11-14-08
  
  
  
  
  
 24C)2ND REQUEST, ZONE AC-3 WINDOWS ARE MISSING THE
 CLERESTORY WINDOWS NORTH ELEVATION SEE A-201, WINDOW
 SIZES (1) 26'-6"X3'-6" AND (2) 16'-2"X3'-6". WINDOWS
 25,26 & 27. 13-401.2AB.2
  
 24D) HEADING OF DOORS IN THE ENERGY CALCULATIONS
 INDICATE IIN ZONE 1 SOLID CORE DOORS (2.25) WHERE AS
 THE PLANS CALL OUT FOR DOOR TYPE A & B TO BE HOLLOW
 CORE METAL DOORS.
  
 24E)PLEASE SEE 18 G& H, ROOF INSULATION, PLANS DOES
 CALL OUT THE ACTUAL THICKNESS OF INSULATION NOR THE
 TYPE OF INSULATION TO BE INSTALLED. THE ROOFING NOAS
 HAS BEEN PROVIDED, IN THIS REVIEW THE SUB-SYSTEM HAS
 NOT BEEN IDENTIFIED WHERE AS IN THE LAST REVIEW THE
 SUB-SYSTEM WAS CIRCLED. THE UNKNWON ROOFING SUB-SYSTEM
 AND INSULATION TYPE WILL MAKE IT IMPOSSIBLE TO VERIFY
 THE ASSUMPTIONS PROVIDED IN THE ENERGY INPUT DATA
 REPORT. A-602.SECTION 13-404.1AB.1/ 13-404.2AB.3.
  
 25) COMPLIED.
  
 RENOVATIONS TO THE EXISTING NORTH WING
  
 26A) COMPLIED.
  
 26B) COMPLIED.
  
 26C) COMPLIED.
  
 27-29) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-10-09 Cont ID  
Sent By jwitmer Date 2008-10-09 Time 13:12 Rev Time 3.55
Received By jwitmer Date 2008-10-09 Time 09:16 Sent To  
Notes
2008-10-09 09:38:33BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADDRESS: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE: I-B
 OCTOBER 09,2008
 4TH REVIEW- MAJOR WORKING DRAWING REVIEW
 ACTION: DENIED
  
 1A) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
  
 1B) MULTIPLE REQUEST, PLEASE SUBMIT 3 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
 THIS PROJECT WILL REQUIRE 3 SETS OF ALL DOCUMENTS SINCE
 IT WILL REQUIRE A RESIDENT INSPECTOR , 109.3.6*.
  
 PLANS SUBMITTED THIS REVIEW:
 (2) SET OF NEW CONSTRUCTION PLANS FOR COMMUNITY CENTER
 (2) SETS OF PLANS FOR RENOVATIONS OF NORTH WING
 (2) SETS OF PRODUCT APPROVALS
 (2) SETS SOILS REPORT
 (2) ENERGY CALCULATIONS
 (2) SETS STORM WATER MANAGEMENT SYSTEM CALCULATIONS
 (2) SETS OF RESPONCE COMMENTS FROM WHAT APPEARS TO BE
 2ND & 3RD ROUND COMMENT
  
  
  
 1C) COMPLIED.
  
 1D) COMPLIED.
  
 1E) COMPLIED
  
 2) COMPLIED
  
 3-4) COMPLIED.
  
 5A) COMPLIED.
  
 5B) 3RD REQUEST, WHILE MEETING WITH JEFF HALVERSON
 ABOUT THE TYPE BUILDING AND AMOUNT OF OCCUPANCY WE
 ASCERTAINED THIS TO MEET THE REQUIREMENTS FOR A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR FL S
 S 553.71(7). THE FOLLOWING DEFINITION AND REQUIREMENTS
 WILL NEED TO BE MET. FORMS FOR A THRESHOLD INSPECTOR
 WERE PROVIDED TO MR. HALVERSON . NOTE THE FOUNDATION
 PERMIT IS A AT RISK, STAND ALONE PERMIT AND THE PROPER
 FORMS FOR THE THRESHOLD BUIULDING PERMIT WILL ALSO NEED
 TO BE SUPPLIED:
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTOR: MEETING HAS ALREADY TAKEN PLACE.
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
  
 6-12) COMPLIED.
  
 13) 4TH REQUEST, SEMI-COMPLIED. SHEET A-1 DOES INDICATE
 WALL TAGS INDICATING WALLS BUT THE PLANS DO NOT PROVIDE
 OPENING PROTECTIVES IN THE RATED WALLS TO THE
 MULTIPURPOSE ROOM. SHEET A101
 INDICATES THE DOUBLE DOORS AS DOOR# 98 AND DOOR # 42.
 SEE 715.3.SEE SHEET A-7.00
  
 14) FIRST REVIEW STATED THAT A THOROUGH REVIEW CAN NOT
 BE MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
 THERE ARE STILL SOME ISSUES OUTSTANDING AS LISTED
 BELOW.
  
 15) COMMENT FROM FIRST REVIEW, SEMI-COMPLIED, THERE ARE
 NUMEROUS A-SHEETS THAT HAVE ARCHITECTURAL DETAILS BUT
 THERE IS NO WRITTEN INFORMATION PROVIDED, PLANS ARE
 INCOMPLETE.106.3.5.1.1(4) SEE FIRE RESISTANCE
 CONSTRUCTION REQUIREMENTS.PLANS FAIL TO INDICATE FIRE
 RESISTANCERATING OF BAR JOIST SYSTEM TABLE 601 BAR
 JOIST 2 HR FOOTNOTE "B" ALLOWS FOR A 1 HOUR REDUCTION.
 SEE SHEET A602.
  
 16-17) COMPLIED.
  
 18) 3RD REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF ALL PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
  
 G) ROOF ASSEMBLIES- FIBERTITE SINGLE PLY, SUB-SYSTEM
 NOT IDENTIFIED
 H) TRUSS ANCHORS SEE COMMENT #22
  
 NOTE PLANS WILL CALL OUT FOR CERTAIN TYPES OF PRODUCTS
 (NOA'S) BUT THE ACTUAL REPORTS ARE REQUIRED TO SEE
 LIMITATIONS AND OR MULTIPLE GLAZING SYSTEMS WITH
 VARYING PRESSURES. CONTRACTOR IS TO CIRCLE THE SPECIFIC
 GLAZING SYSTEM, ROOFING SUB-SYSTEM TO BE INSTALLED AS A
 COMPENENT OF THIS BUILDING.
  
 19) COMPLIED.
  
  
 20) COMPLIED.
  
 21) 2ND REQUEST, THIS ROOF IS MISSING PRODUCT
 COMPLIANCE REPORTS WITH THE FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES
 LIMITATION# 9, NO ENHANCED FASTENING ALLOWED.
  
 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS
 ASSEMBLY AND NOA'S:
 USP C88 NOA 07-0306.06
 USP RT7 NOA07-0306.10
 USPKCB88 FL 822.149
 ALL THREE OF THE LISTED ABOVE WILL NEED TO MEET THE
 REQUIREMENTS OF 18-20.
  
 23) COMPLIED.
  
 24) 3RD REQUEST, ARCHITECTURAL PLANS ARE DEFICIENT IN
 INFORMATION FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 24A) 2ND REQUEST, THE TOTAL SQUARE FOOTAGE OF THE
 BUILDING DOES NOT CALCULATE, THE TOTAL GROSS AREA TAKEN
 FROM LS1.0 EQUALLS 11,159 SQ FT NOT THE 9854 LISTED.
 SHEET A-700 ROOM FINISHES LIST 9540 SQ FT. PLEASE SEE
 THE TOTAL AREA ON THE ENERGY CALCULATION AS 8913 SQUARE
 FEET. PLEASE SEE 13-413-05.2AB.2 GROSS FLOOR AREA. THE
 GROSS FLOOR ASSEMBLIES OVER OUTSIDE OR UNCONDITIONED
 SPACES CONSEST OF THE TOTAL FLOOR ASSEMBLY EXPOSED TO
 OUTSIDE AIR OR UNCONDITIONED SPACE. THE FLOOR ASWSEMBLY
 SHALL INCLUDE ALL FLOOR COMPONENTS THROUGH WHICH HEAT
 MAY FLOW BETWEEN INDOOR AND OUTDOOR OR UNCONDITIONED
 SPACE ENVIROMENTS. PLEASE CORRECT THE SQUARE FLOOR AREA
 TO REFLECT THE TOTAL GROSS AREA. STATE RADON FEES WILL
 NOT BE ESSESSED UNTIL SQUARE FOOTAGE IS RESOLVED.
  
 24B) SHEET A-700 FLOOR FINISHES INDICATES 2730 SQ FT OF
 FLOOR THAT DOES NOT HAVE CARPET AND PADDING AS A
 INSULATOR BUT DOES NOT SHOW UP ONT THE ENERGY
 CALCULATION. NOT ALSO THE GENERATOR ROOM AND ELECTRIC
 ROOM FLOORS WILL NOT HAVE CARPET AND PADDING INSULATED
 VALUE WAS TAKEN. 13-405.2AB
  
 24C) ZONE AC-3 WINDOWS ARE MISSING THE CLERESTORY
 WINDOWS (1) 26'-6"X3'-6" AND (2) 16'-2"X3'-6". WINDOWS
 25,26 & 27. 13-401.2AB.2
  
 24D) HEADING OF DOORS IN THE ENERGY CALCULATIONS
 INDICATE IIN ZONE 1 SOLID CORE DOORS WHEREAS THE PLANS
 CALL OUT FOR DOOR TYPE A & B TO BE HOLLOW CORE METAL
 DOORS.
  
 24E) ROOF INSULATION, PLANS DOES CALL OUT THE ACTUAL
 THICKNESS OF INSULATION NOR THE TYPE OF INSULATION TO
 BE INSTALLED. THE ROOFING NOAS HAS BEEN PROVIDED, IN
 THIS REVIEW THE SUB-SYSTEM HAS NOT BEEN IDENTIFIED
 WHERE AS IN THE LAST REVIEW THE SUB-SYSTEM WAS CIRCLED.
 THE UNKNWON ROOFING SUB-SYSTEM AND INSULATION TYPE WILL
 MAKE IT IMPOSSIBLE TO VERIFY THE ASSUMPTIONS PROVIDED
 IN THE ENERGY INPUT DATA REPORT. A-602.SECTION
 13-404.1AB.1/ 13-404.2AB.3.
  
 25) COMPLIED.
  
 RENOVATIONS TO THE EXISTING NORTH WING
  
 26A) COMPLIED.
  
 26B) COMPLIED.
  
 26C) COMPLIED.
  
 27-29) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-15 Cont ID  
Sent By jwitmer Date 2008-07-15 Time 16:06 Rev Time 12.22
Received By jwitmer Date 2008-07-15 Time 16:06 Sent To  
Notes
2008-07-15 16:57:51BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADD: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 15,2008
 3RD REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL,WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 3 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. YOUR PROJECT IS A THRESHOLD BUILDING
 REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE SETS OF
 ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
 THIS PROJECT WILL REQUIRE 3 SETS OF ALL DOCUMENTS SINCE
 IT WILL REQUIRE A RESIDENT INSPECTOR , 109.3.6*.
  
 1C) COMPLIED.
  
 1D) COMPLIED.
  
 1E) COMPLIED
  
 2) COMPLIED
  
 3-4) COMPLIED.
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST, WHILE MEETING WITH JEFF HALVERSON
 ABOUT THE TYPE BUILDING AND AMOUNT OF OCCUPANCY WE
 ASCERTAINED THIS TO MEET THE REQUIREMENTS FOR A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR FL S
 S 553.71(7). THE FOLLOWING DEFINITION AND REQUIREMENTS
 WILL NEED TO BE MET. FORMS FOR A THRESHOLD INSPECTOR
 WERE PROVIDED TO MR. HALVERSON AT THE END OF THE
 MEETING.
  
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 THRESHOLD INSPECTOR:
 WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE
 THE PERMIT MAY BE ISSUED.
  
 THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
  
 6-12) COMPLIED.
  
 13) 3RD REQUEST, SEMI-REPLIED. SHEET A-1 DOES INDICATE
 WALL TAGS INDICATING WALLS BUT THE PLANS DO NOT PROVIDE
 OPENING PROTECTIVES IN THE RATED WALLS SEE 715.3.
 NOTE SHEET A101 CLASSROOMS AND THE STORAGE CLOSETS
 WITHIN THE CLASSROOMS ARE NOT MARKED OR MISS MARKED ON
 THE DOOR SCHEDULE SHEET A-700.
  
 14) SEMI-COMPLIED, PLANS ARE INCOMPLETE AND A THROUGH
 REVIEW CAN NOT BE COMPLETED AT THIS TIME.
 106.3.5 WILL PROVIDE THE MINIMUM CRITERIA AND DOCUMENTS
 REQUIRED FOR REVIEW.
  
 15) SEMI-COMPLIED.
  
 16-17) COMPLIED.
  
 18) 3RD REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF ALL PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
 A) WINDOWS FIXED: STOREFRONT , CURTAIN WALL
 B) WINDOWS OPERABLE WINDOWS: SINGLE HUNG, CASEMENT C)
 MULLIONS
 D) GLASS BLOCK
 E) GLAZED SWING DOORS
 F) AUTOMATIC SLIDING DOORS
 G) HOLLOW METAL DOORS EXTERIOR (INSULATED)
 H) OVERHEAD DOORS
 I) TRUSS ANCHORS
 J) ROOF HATCHES
 K) ROOF ASSEMBLIES
 L) PRE-ENGINEERED A/C STANDS
  
 NOTE PLANS WILL CALL OUT FOR CERTAIN TYPES OF PRODUCTS
 (NOA'S) BUT THE ACTUAL REPORTS ARE REQUIRED TO SEE
 LIMITATIONS AND OR MULTIPLE GLAZING SYSTEMS WITH
 VARYING PRESSURES. CONTRACTOR IS TO CIRCLE THE SPECIFIC
 GLAZING SYSTEM, ROOFING SUB-SYSTEM TO BE INSTALLED AS A
 COMPENENT OF THIS BUILDING.
  
  
 19) 2ND REQUEST, 106.3 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 20) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) 2ND REQUEST, THIS ROOF IS MISSING PRODUCT
 COMPLIANCE REPORTS WITH THE FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES
 LIMITATION# 9, NO ENHANCED FASTENING ALLOWED.
  
 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS
 ASSEMBLY AND NOA'S:
 USP C88 NOA 07-0306.06
 USP RT7 NOA07-0306.10
 USPKCB88 FL 822.149
 ALL THREE OF THE LISTED ABOVE WILL NEED TO MEET THE
 REQUIREMENTS OF 18-20.
  
 23) COMPLIED.
  
 24) 3RD REQUEST, ARCHITECTURAL PLANS ARE DEFICIENT IN
 INFORMATION FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 24A) THE TOTAL SQUARE FOOTAGE OF THE BUILDING DOES NOT
 CALCULATE, THE TOTAL GROSS AREA TAKEN FROM LS1.0
 EQUALLS 11,159 SQ FT NOT THE 9854 LISTED. SHEET A-700
 ROOM FINISHES LIST 9540 SQ FT. PLEASE SEE THE TOTAL
 AREA ON THE ENERGY CALCULATION AS 8913 SQUARE FEET.
 PLEASE SEE 13-413-05.2AB.2 GROSS FLOOR AREA. THE GROSS
 FLOOR ASSEMBLIES OVER OUTSIDE OR UNCONDITIONED SPACES
 CONSEST OF THE TOTAL FLOOR ASSEMBLY EXPOSED TO OUTSIDE
 AIR OR UNCONDITIONED SPACE. THE FLOOR ASWSEMBLY SHALL
 INCLUDE ALL FLOOR COMPONENTS THROUGH WHICH HEAT MAY
 FLOW BETWEEN INDOOR AND OUTDOOR OR UNCONDITIONED SPACE
 ENVIROMENTS. PLEASE CORRECT THE SQUARE FLOOR AREA TO
 REFLECT THE TOTAL GROSS AREA.
  
 24B) SHEET A-700 FLOOR FINISHES INDICATES 2730 SQ FT OF
 FLOOR THAT DOES NOT HAVE CARPET AND PADDING AS A
 INSULATOR BUT DOES NOT SHOW UP ONT THE ENERGY
 CALCULATION. NOT ALSO THE GENERATOR ROOM AND ELECTRIC
 ROOM FLOORS WILL NOT HAVE CARPET AND PADDING INSULATED
 VALUE WAS TAKEN. 13-405.2AB
  
 24C) ZONE AC-3 WINDOWS ARE MISSING THE CLERESTORY
 WINDOWS (1) 26'-6"X3'-6" AND (2) 16'-2"X3'-6". WINDOWS
 25,26 & 27. 13-401.2AB.2
  
 24D) HEADING OF DOORS IN THE ENERGY CALCULATIONS
 INDICATE IIN ZONE 1 SOLID CORE DOORS WHEREAS THE PLANS
 CALL OUT FOR DOOR TYPE A & B TO BE HOLLOW CORE METAL
 DOORS.
  
 24E) ROOF INSULATION, PLANS DO NOT CALL OUT THE ACTUAL
 THICKNESS OF INSULATION NOR THE TYPE OF INSULATION TO
 BE INSTALLED. NOR HAS THE ROFING NOAS BENN PROVIDED AND
 SUB-SYSTEMS CIRCLED INDICATING THE TYPE OF ROOFING AND
 APPROPRIATE INSULATION PROVIDED. SEE A-602.
 13-404.1AB.1/ 13-404.2AB.3.
  
 25) COMPLIED.
  
 RENOVATIONS TO THE EXISTING NORTH WING
  
 26A) THE DESIGN TEAM HAS DRAWWN AN ASSUMED PROPERTY
 LINE BETWEEN THE TWO BUILDINGS AND DECLARED THE
 BUILDING WITH RENOVATION TO BE A A-3 OCCUPANCY AND
 BUILDING TYPE III-B WITH ALLOWABLE AREA OF 9500 SQ FT.
 SHEET A-100 PROJECT DATA INDICATES THE FOOTPRINT TO BE
 17, 600 SQ FT EVEN WITH COMPUTING AREA INCREASES WITH
 F/P THE ALLOWABLE INCREASE OF 5903 BRINGS THE ALLOWABLE
 AREA UP TO 15,403. NO AREA INCREASES WERE TAKEN FOR
 FIRE SPRINKLERS, AT A MINIMUM THIS BUILDING WOULD NEED
 TO BE A TYPE III-A SEE TABLE 601AND 602.3. INTERIOR
 BUILDING ELEMENTS ARE OF ANY MATERIAL PERMITTED BY THIS
 CODE.
  
  
 26B) COMPLIED.
  
 26C) COMPLIED.
  
 27-29) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-30 Cont ID  
Sent By jwitmer Date 2008-05-30 Time 09:33 Rev Time 5.55
Received By jwitmer Date 2008-05-30 Time 09:33 Sent To  
Notes
2008-05-30 13:39:15BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADD: 1505 N AUSTRALIAN AVE.
 CONT: :(PLAN REVIEW/ MAJOR WORKING DRAWING)
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 MAY 30,2008
 2NDREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL,WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
 THIS PROJECT WILL REQUIRE 3 SETS OF ALL DOCUMENTS SINCE
 IT WILL REQUIRE A RESIDENT INSPECTOR , 109.3.7*.
  
 1C)COMPLIED.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS. NOTE IF THE PLANS
 SUBMITTED AS A MAJOR WORKING DRAWING HAVE NOT BEEN
 CONVERTED INTO A PERMIT APPLICATION BEFORE OCT. 1,2008
 THE PLANS WILL NEED TO BE REDESIGNED TO THE 2007
 FLORIDA BUILDING CODE.
  
 1E) 2ND REQUEST,THE MAJOR WORKING DRAWING REVIEW
 UNDER SCOPE OF PROJECT INDICATES A 10,000 SQ FT
 MULTIPURPOSE BUILDING, PLEASE ADD THE RENOVATION TO THE
 EXISTING BUILDING TO THE APPLICATION.
  
 2) DESIGN PROFESSIONAL REQUIREMENTS:
  
 2A)PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 IN BOTH SETS OF PLANS FOR THE NEW GAINES PARK COMMUNITY
 CENTER AND THE NORTHWEST WING RENOVATIONS THE
 COVERSHEETS ARE NOTSIGNED, SEALED OR DATED.
  
  
 2B) 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
 LANDSCAPE ARCHITECT
 BA ARCHITECTURAL
 PLEASE PROVIDE DOCUMENTATION FROM THE DEPARTMENT OF
 BUSSINESS AND PROFESSIONAL REGULATION OF YOUR
 CERTIFICATE OF AUTHORIZATION, I CAN NOT FIND IT ON THE
 WEBSITE.
  
 2C)COMPLIED.
  
 3) 2ND REQUEST, NEW BUILDING CONSTRUCTION. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.A THOROUGH REVIEW CAN
 NOT BE MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
  
 3A) 10.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
  
 PLEASE SEE SHEET A-100 PROJECT CRITERIA DOES NOT
 INDICATE TO WHAT CODE THIS BUILDING IS DESIGNED TOO.
 PLEASE SEE STRUCTURAL SHEET S-3.1 STILL INDICATES THE
 2004 FBC WITH 2006 AMENDMENTS. THE 2007 AMENDMENTS
 CLEARLY ARE AFFECTED BY WIND.
  
 B) COMPLIED.
 C) 2ND REQUEST,THE TYPE OF CONSTRUCTION AS DEFINED IN
 CHAPTER 5 & 6, TABLE 503 & 601. 106.3.5(3) MINIMUM TYPE
 OF CONSTRUCTION SEE TABLE 503 PLANS INDICATE TYPE I
 CONSTRUCTIONTHERE IS NO CONFIRMATION AS TO TYPE 1A 3HR
 FIRE RATINGS OR TYPE 1B 2HR FIRE RATINGS,NOTE SEE
 TABLE 601 FOR FIRE RATINGS.
  
 D) COMPLIED.
  
 E)2ND REQUEST, IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED NEITHER SHEET G-100 THE INDEX OF DRAWINGS,
 LS-1.0 NOR A-100 PROJECT CRITERIA LIST THE REQUIRED
 FIRE SPRINKLER PLANS NOR THE INSTALATION OF A NFPA 13
 SYSTEM. SECTION 903.2.1.3 (2) REQUIRES A SPRINKLER
 SYSTEM WHEN IN A A-3 OCCUPANCYWHEN THERE IS A
 OCCUPANCY EQUAL TO OR GREATER THAN 300. THIS IS A
 REQUIRED SYSTEM.
 F)2ND REQUESTWHETHER THE SPRINKLER SYSTEM IS
 REQUIRED. SEE SECTION 903.2.1.3(2).
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) COMPLIED.
  
 3B) 2ND REQUEST, THE S-3.1 INDICATES THE WIND DESIGN
 FROM ASCE 7-02FOR THE BUILDING, PLEASE REVIEW THE
 BUILDINGS CATEGORY AND IMPORTANCE FACTOR. PLEASE REVIEW
 SHEET A-101 & A-102 FOR OCCUPANCY. AS INDICATED THESE
 SHEETS INDICATE THE CAPABILITY OF 300 PEOPLE WITH THE
 ACTUAL OCCUPANT LOAD BEING QUIET HIGHER. PLEASE SEE
 ASCE 7-02 TABLE 1-1 BUILDING CATEGORY III,WITH A
 IMPORTANCE FACOR OF 1.15 BUILDINGS AND OTHER STRUCTURES
 WHERE MORE THAN 300 PEOPLE CONGREGATE IN ONE AREA.
 PLEASE REVISE THE BUILDING CATEGORY AND IMPORTANCE
 FACTOR. SEE UPPER LEFT HAND PORTION OF THE SHEET STILL
 INDICATES 1.0 IMPORTANCE FACTOR.
  
 3C) COMPLIED.
  
 4) 2ND REQUEST, THE LIFE SAFETY SHEET LS-100 INDICATES
 FOR THE MULTI-PURPOSE ROOM THE USE OF 15 NET. TABLE
 1004.1.2 ESTABLISHES THE MINIMUM OCCUPANT LOAD FOR
 WHICH THE EGRESS FACILITIES MUST BE DESIGNED. THE
 FACTORS ARE NOT BASED ON THE NORMAL OCCUPANCY, BUT , ON
 THE MAXIMUM OCCUPANT LOAD SCENARIO, A WORST CASE
 PROBABILITY. IT SHOULD ALSO BE NOTED THE FACTORS ARE
 NOT BASED ON THE OCCUPANCY CLASS OF THE BUILDING, BUT ,
 ON THE USE OF THE AREA OR SPACE. PLEASE RECALCULATE THE
 EGRESS CAPACITIES FOR THE MULTI-PURPOSE ROOM AT THE
 WORST CASE SCENARIO @ 5 AND ASSOCIATED EXITS.
  
 5A) COMPLIED.
  
 5B)2ND REQUEST, AT THIS TIME BECAUSE OF THE UNKNOWN
 BUILDING FACTORS THIS COMMENT MAY OR MAY NOT APPLY IN
 FUTURE REVIEWS:FBC* 109.3.7RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO
 HAROLD PISKURA, DIRECTOR OF THE RESIDENT INSPECTOR
 PROGRAM. A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 XXX - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS XXX - STRUCTURES IN
 WHICH THE CONCRETEDESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI - PILE DRIVING
 COLUMNS, WALLS, BEAMS 4,000 PSI S-3.1.
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 FORMS FOR THE RESIDENT INSPECTOR WILL BE ATTACHED AND
 WILL NEED TO BE FILED OUT AND RETURNED TO HAROLD
 PISKURA DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.
  
 6)2ND REQUEST,L-3.0 LANDSCAPE PAVING PLAN PLEASE
 PROVIDE AN ACCESSIBLE ROUTE WITHIN THEBOUNDARY OF THE
 SITE TO PUBLIC TRANSPORTATION, ACCESSIBLE PARKING,
 PASSENGER LOADING ZONES SIDEWALKS TO AN ACCESSIBLE
 ENTRANCE. 11-4.1.2(1)-(5). SHEET A-100 & L-3.0 DO NOT
 REFLECT THE SAME ROUTE FROM THE ACCESSIBLE PARKING TO
 THE NEW BUILDING. A-100 INDICATES A SIDEWALK THAT
 ALLOWS WHEELCHAIRS TO TRAVEL INFRON T OF THE PARKED
 VEHICLES WHILE L-3.0 STILL FORCES THE WHEELCHAIR USER
 TO TRAVEL BEHIND THE PARKED VEHICLE, PLEASE COORDINATE
 PLANS.11-4.6.2.
  
 7) 2ND REQUEST, THE RESPONCE SHEET INDICATED TO REFER
 TO CIVIL AND LANDSCAPE NOTES, WHERE. SHET L-3.0 PAVING
 MATERIALSSCHEDULE DOES NOT INDICATE THE USE OF
 DETECTABLE WARNING TEXTURES11-4.29.2. INDICATE
 COMPLIANCE WITH: 11-4.29.5 DETECTABLE WARNINGS AT
 HAZARDOUS VEHICULAR AREAS.
  
 8)COMPLIED.
  
 9) 2ND REQUEST, RESPONCE SHEET REFERS TO CIVIL SHEET
 C-4 , PLEASE INDICATE COMPLIANCE WITH : PASSENGER
 LOADING ZONES PLEASE PROVIDE ACCESS AISLE FOR PASSENGER
 LOADING ZONE SEE FIGURE 10, AND COMPLIANCE WITH
 11-4.29.5/ 11-4.6.6.
  
 10) SEMI-COMPLIED. SHEET A-1.00 INDICATES A CUT SECTION
 THROUGH THE DISABLED PARKING SPOTS DETAIL# 1 SHEET
 A-603, SHEET IS MISSING. THE RESPONCE SHEET INDICATES
 TO SEE A-605 DETAIL# 1. THE HANDICAPPED SIGNAGE
 INDICATES 2 AREAS TO LOCATE THIS SECTION :
 10A) DETAIL 16 A-603
 10B) DETAIL 5 A-604
 NEITHER OF THESE SECTION PORVIDE THE HANDICAPPED SIGN
 HEIGHTS.
  
 11-12) COMPLIED.
  
 13)2ND REQUEST, SHEET A-1 DOES INDICATE WALL TAGS
 INDICATING WALLS BUT THE PLANS DO NOT PROVIDE A DETAIL
 SHEET IDENTIFYING WALL TYPES, THE INDEX LIST A-600 FOR
 WALL DETAILS , THERE ARE NO WALL DETAILS PROVIDING WALL
 TYPES AND FIRE RATING, PLEASE SEE TABLE 1016.1. FOR
 ASSEMBLY OCCUPANCY AND FIRE RATING OF CORRIDOR.
 ENTRANCE HALLWAY 152 IS THE EXIT ACCESS CORRIDOR FOR
 THE MULTI-PURPOSE ASSEMBLY ROOM 146 , SEE TABLE 1016.1
 REQUIRES A 1 HR RATED CORRIDOR FOR EITHER
 NON-SPRINKLERED OR SPRINKLERED BUILDINGS.
  
 14) SEMI-COMPLIED, PLANS ARE INCOMPLETE AND A THROUGH
 REVIEW CAN NOT BE COMPLETED AT THIS TIME.
 106.3.5 WILL PROVIDE THE MINIMUM CRITERIA AND DOCUMENTS
 REQUIRED FOR REVIEW.
  
 15) SEMI-COMPLIED.
  
 16-17) COMPLIED.
  
 18)2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 3COPIES OF ALL REPORTSFORTHRESHOLD
 OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS
 ,MISSING REPORTS ARE AS FOLLOWS:
 A) WINDOWS FIXED: STOREFRONT , CURTAIN WALL
 B) WINDOWSOPERABLE WINDOWS: SINGLE HUNG, CASEMENT
 C) MULLIONS
 D) GLASS BLOCK
 E) GLAZED SWING DOORS
 F) AUTOMATIC SLIDING DOORS
 G) HOLLOW METAL DOORS EXTERIOR
 H) OVERHEAD DOORS
 I) TRUSS ANCHORS
 J) ROOF HATCHES
 K) ROOF ASSEMBLIES
 L) PRE-ENGINEERED A/C STANDS
  
 19)2ND REQUEST,106.3PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 20) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATEDBY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 21) 2ND REQUEST,THIS ROOF IS MISSING PRODUCT
 COMPLIANCE REPORTS WITH THE FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES
 LIMITATION# 9, NO ENHANCEDFASTENING ALLOWED.
  
 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS
 ASSEMBLY AND NOA'S:
 USP C88 NOA 07-0306.06
 USP RT7 NOA07-0306.10
 USPKCB88 FL 822.149
 ALL THREE OF THE LISTED ABOVE WILL NEED TO MEET THE
 REQUIREMENTS OF 18-20.
  
 23) 2ND REQUEST,A-104 ROOF PLAN FAILS TO IDENTIFY
 ROOF DRAINAGE SYSTEM AND OR DETAILS, THE ROOF DRAIN
 SIZE IS NOT PROVIDED, WHAT TYPE OF SECONDARY DRAINAGE
 AND VERTICAL CONTRIBUTING AREAS, THIS INFORMATION IS
 ALSO MISSING FROM THE PLUMBING PLAN. 106.3.5.1.1(8).
 OVERFLOWS ARE NOT SIZED, FBC BUILDING 1503.4.3 OVERFLOW
 SCUPPERS SHALL BE SIZED IN ACCORDANCE WITH THE FBC
 PLUMBING CODE.
  
 24) 2ND REQUEST,ARCHITECTURAL PLANS ARE DEFICIENT IN
 INFORMATION FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 25) COMPLIED.E
  
  
 RENOVATION OF EXISTING NORTH WING :
  
  
 26A)SEMI-COMPLIED,SHEET A-100 PROJECT CRITERIA
 INDICATES THIS BUILDING IS TO BE CLASSIFIED AS A TYPE I
 BUILDING, IS THIS A TYPE IA BUILDING WITH 3HR FIRE
 PROTECTION OR TYPE IB WITH A 2 HR FIRE PROTECTION OF
 STRUCTURAL ELEMENTS, IN EITHERCASE THERE WOULD BE NO
 WOOD TRUSSES AND OR ROOF SHEATHING. PLEASE INDICATE
 MINIMUMBUILDING TYPE.
  
 THE OTHER ISSUE IS THIS BUILDING BE FIRE SPRINKLERED ?
 IS THE FIRE SPRINKLER REQUIRED?
 THESE QUESTIONS NEED TO BE ANSWERED TO KNOW IF THE
 CORRIDORS WILL REQUIRE RATED CORRIDORS,SEE TABLE 1016.1
 FOR DAY CARE OCCUPANCIES.
 THE PLANS INDICATE SOME OF THE DOORS BEING RATED BUT
 THERE ARE MANY NEW DOORS AND EXISTING DOOR FRAMES AND
 THE NEW DOORS ARE NOT RATED. WE STILL CAN NOT DO A
 COMPLETE REVIEW WITHOUT THE
 ABOVE INFORMATION PROVIDED.
  
 26B) SEMI- COMPLIED. SEE THE ABOVE STATEMENTS.
  
 26C) 2ND REQUEST, PLEASE ALSO INDICATE TO WHAT LEVEL
 ALTERATION WORK WILL ACCOMPLISHED UNDER THIS PERMIT.
 PLEASE SEE 2004 FBC EXISTING BUILDING CODE 301.1.THE
 WORK PREFORMED ON AN EXISTING BUILDING SHALL BE
 CLASSIFIED IN ACCORDANCE WITH THIS CHAPTER.RESPONCE
 INDICATES NOTES ON G-100 & A-101.PLANS DO NOT INDICATE
 LEVEL OF ALTERATION IN EITHER THE APPLICABLE CODE OR
 PROJECT CRITERIA.
  
 27) SEMI-COMPLIED THE DOOR SCHEDULE DOES NOW INDICATES
 ALOT OF NEW DOORS WITH EXISTING DOOR FRAMES BUT NO FIRE
 RATING, WITH NOT HAVING INFORMATION IF THERE IS FIRE
 SPRINKLERS OR IF THERE WILL BE FIRE SPRINKLERS ADDED,
 WE NEED TO KNOW THIS INFORMATION TO DETERMINE THROUGH
 TABLE 1016.1 FIRE RATINGS FOR CORRIDORS.
  
 28) COMPLIED- NO ROOF WORK UNDER THIS PERMIT FOR THIS
 BUILDING.
  
 29) NEW COMMENT DOOR # 5 IS A NEW OPENING, WILL NEED TO
 COMPLY WITH 11-4.13.6 MANEUVERING CLEARENCES AT DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG.
 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL. REQUIRES 18" ON THE
 LATCH SIDE.
  
 BUILDING PLAN REVIEW
 JIM WITMER CBO
 PLAN REVIEW II
 TEL:(561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-26 Cont ID  
Sent By jwitmer Date 2007-10-26 Time 14:13 Rev Time 14.00
Received By jwitmer Date 2007-10-25 Time 09:48 Sent To  
Notes
2007-10-26 14:15:06BUILDING PLAN REVIEW
 PERMIT: 07100001
 ADD: 1505 N AUSTRALIAN AVE.
 CONT: :?PLAN REVIEW/ MAJOR WORKING DRAWING?
 TEL: (561644-7416 JEFF HALVERSON
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 1E) THE MAJOR WORKING DRAWING REVIEW UNDER SCOPE OF
 PROJECT INDICATES A 10,000 SQ FT MULTIPURPOSE BUILDING,
 PLEASE ADD THE RENOVATION TO THE EXISTING BUILDING TO
 THE APPLICATION.
  
 2) DESIGN PROFESSIONAL REQUIREMENTS:
  
 2A) PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 2B) 481.219 F.S. CERTIFICATE OF AUTHORIZATION. THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
 LANDSCAPE ARCHITECT
 BA ARCHITECTURAL
  
 2C) 471.023 F.S. CERTIFICATE OF AUTHORIZATION. THE
 TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN
 ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY
 HAND.
 STRUCTURAL ENGINEER
 MEP ENGINEER
 CIVIL ENGINEER
  
 3) NEW BUILDING CONSTRUCTION. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED. A THOROUGH REVIEW CAN NOT BE MADE
 AT THIS TIME, AS A RESULT OF THE ADDITIONAL INFORMATION
 REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT
 PART OF THIS REVIEW.
  
 3A) 10.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3& 106.3.5.1.1(3).
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5 &
 6, TABLE 503 & 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) SQ. FT. FOOTPRINT
  
 3B) THE S-3.1 INDICATES THE WIND DESIGN FROM ASCE
 7-02FOR THE BUILDING, PLEASE REVIEW THE BUILDINGS
 CATEGORY AND IMPORTANCE FACTOR. PLEASE REVIEW SHEET
 A-101 & A-102 FOR OCCUPANCY. AS INDICATED THESE SHEETS
 INDICATE THE CAPABILITY OF 350 PEOPLE WITH THE ACTUAL
 OCCUPANT LOAD BEING QUIET HIGHER. PLEASE SEE ASCE 7-02
 TABLE 1-1 BUILDING CATEGORY III,
 BUILDINGS AND OTHER STRUCTURES WHERE MORE THAN 300
 PEOPLE CONGREGATE IN ONE AREA. PLEASE REVISE THE
 BUILDING CATEGORY AND IMPORTANCE FACTOR.
  
 3C) THE ABOVE CORRECTION OF BUILDING CATEGORY AND
 IMPORTANCE FACTOR WILL ALSO EFFECT THE
 COMPONENTS AND CLADDING PRESSURES FOR THE WINDOWS AND
 DOORS AS WELL AS THE ROOF ASSEMBLIES. ASCE 7-02
 COMPONENTS & CLADDING ?METHOD 1FIGURE 6-3, WALLS &
 ROOFS,
 AND HEIGHT ADJUSTMENT FACTORS FOR A MEAN ROOF HEIGHT OF
 18?-3? , ADJUSTMENT FACTOR 1.29 FOR 20 FT. .
  
 4) THE LIFE SAFETY SHEET A-800 IS TOTALLY
 BLANK!!!!!!!!!!!!!!!!! PLEASE PROVIDE A MEANS OF EGRESS
 PLAN LIFE SAFETY PLAN AND PROVIDE THE OCCUPANT LOADS
 THAT WILL BE GOING THROUGH EACH OF THE EGRESSES. SEE
 TABLE 1004.1.2, TABLE 1005.
  
 5A) ONE CONCERN IS THE ANSWER TO QUESTION 3C, THE PLANS
 ARE NOT CLEAR AS TO THE DISTANCE BETWEEN THE NEW
 BUILDING AND EXISTING BUILDINGS, WHERE IF NEEDED,
 ASSUMED PROPERTY LINES WOULD BE PLACED FOR THE AMOUNT
 OF ALLOWABLE OPENINGS, WITH OR WITHOUT OPENING
 PROTECTIVE?S FOR EACH BUILDING.
  
 THE OTHER UNKNOWN AT THIS TIME IS IF THE DESIGN TEAM
 WERE TO DESIGN THIS UNDER THE CODE SECTION 503.1.3, TWO
 BUILDINGS ON THE SAME LOT, THESE TYPE ISSUES NEED TO BE
 ADDRESSED BEFORE WE CAN REVIEW FOR ALLOWABLE AREAS,
 FIRE RESISTANCE, TABLE 601, TABLE 602 AND TABLE 704.8.
  
 5B) AT THIS TIME BECAUSE OF THE UNKNOWN BUILDING
 FACTORS THIS COMMENT MAY OR MAY NOT APPLY IN FUTURE
 REVIEWS: FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT
 INSPECTOR RESUME' AND LICENSE DOCUMENTS TO HAROLD
 PISKURA, DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM. A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION -
 ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE DESIGN IS BASED ON
 COMPRESSIVE STRENGTH (F'C) IN EXCESS OF 3000 PSI - PILE
 DRIVING
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION
  
 6) L-3.0 LANDSCAPE PAVING PLAN PLEASE PROVIDE AN
 ACCESSIBLE ROUTE WITHIN THE BOUNDARY OF THE SITE TO
 PUBLIC TRANSPORTATION, ACCESSIBLE PARKING, PASSENGER
 LOADING ZONES SIDEWALKS TO AN ACCESSIBLE ENTRANCE.
 11-4.1.2(1)-(5)
  
 7) INDICATE COMPLIANCE WITH: 11-4.29.5 DETECTABLE
 WARNINGS AT HAZARDOUS VEHICULAR AREAS.
  
 8) SHEET L-3 AND A-1.00 BOTH INDICATE A COVERED DROP
 OFF OR PASSENGER LOADING ZONE, PLEASE PROVIDE THE CLEAR
 ELEVATION UNDERNEATH THE CANOPY. 11-4.6.5.
  
 9) PASSENGER LOADING ZONES PLEASE PROVIDE ACCESS AISLE
 INDICATE CONDITIONS AT CURB OR DROPPED CURB AND
 COMPLIANCE WITH 11-4.29.5/ 11-4.6.6.
  
 10) SHEET A-1.00 INDICATES A CUT SECTION THROUGH THE
 DISABLED PARKING SPOTS DETAIL# 1 SHEET
 A-603, SHEET IS MISSING. PLANS ARE NOT COMPLETE,
 ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 11) SHEET L-5.0 & E-1 INDICATES LIGHT POLES TO BE USED
 IN THE PARKING LOT, FOR EACH TYPE OF LIGHT POLE AND
 CONFIGURATION OF LIGHTS SUPPLY CALCULATIONS FOR
 INSTALLATION TO 140 MPH WIND ZONE: 1805.7 DESIGNS
 EMPLOYING LATERAL BEARING. DESIGNS TO RESIST BOTH AXIAL
 AND LATERAL LOADS EMPLOYING POSTS OR POLES AS COLUMNS
 EMBEDDED IN EARTH OR EMBEDDED IN CONCRETE FOOTINGS IN
 THE EARTH SHALL CONFORM TO THE REQUIREMENTS OF SECTIONS
 1805.7.1 THROUGH 1805.7.3 .
  
 12) SHEET A-1 IN ROOM # 148 INDICATES THIS TO BE A
 GENERATOR ROOM. PLEASE PROVIDE CUT SHEETS FOR THE
 GENERATOR, TYPE OF FUEL, TANK SIZE AND REQUIREMENTS
 INDICATE LOCATION ON SITE PLAN, IS THIS A ABOVE THE
 GROUND TYPE TANK OR BURIED. WILL THIS BUILDING EVER BE
 USED FOR A HURRICANE SHELTER, THIS MAY EFFECT AMOUNTS
 OF FUEL TO BE REQUIRED.\
  
 13) SHEET A-1 DOES INDICATE WALL TAGS INDICATING WALLS
 BUT THE PLANS DO NOT PROVIDE A DETAIL SHEET IDENTIFYING
 WALL TYPES, THE INDEX LIST A-600 FOR WALL DETAILS ,
 THERE ARE NO WALL DETAILS PROVIDING WALL TYPES AND FIRE
 RATING, PLEASE SEE TABLE 1016.1. FOR ASSEMBLY OCCUPANCY
 AND FIRE RATING OF CORRIDOR.
  
 14) PLANS ARE INCOMPLETE AND A THROUGH REVIEW CAN NOT
 BE COMPLETED AT THIS TIME.
 106.3.5 WILL PROVIDE THE MINIMUM CRITERIA AND DOCUMENTS
 REQUIRED FOR REVIEW.
  
 15) THERE ARE NUMEROUS A-SHEETS THAT HAVE ARCHITECTURAL
 DETAILS BUT THERE IS NO WRITTEN INFORMATION PROVIDED,
 PLANS ARE INCOMPLETE.106.3.5.1.1(4) SEE FIRE RESISTANCE
 CONSTRUCTION REQUIREMENTS.
  
 16) SHEET A-101 INDICATES WHAT APPEARS TO BE A STAGE
 AND STAIRS ON THE WEST END OF THE MULTI-PURPOSE ROOM,
 SEE SECTION# 7 SHEET A-800 FOR DETAIL, SHEET A-800 IS A
 BLANK SHEET THAT IS SUPPOSE TO BE THE LIFE SAFETY
 SHEET. IF THIS IS A STAGE PLEASE PROVIDE VERTICAL
 ACCESSIBILITY, AND ALSO PROVIDE DETAILS FOR STAIRS AND
 HANDRAIL. 11-4.1.3(5).
  
 17) NEW BUILDING STRUCTURAL, S 3-1 PLANS ARE MISSING
 INFORMATION ON THE MASONRY WALL SCHEDULE 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 18) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED: STOREFRONT , CURTAIN WALL
 B) WINDOWS OPERABLE WINDOWS: SINGLE HUNG, CASEMENT C)
 MULLIONS
 D) GLASS BLOCK
 E) GLAZED SWING DOORS
 F) AUTOMATIC SLIDING DOORS
 G) HOLLOW METAL DOORS EXTERIOR
 H) OVERHEAD DOORS
 I) TRUSS ANCHORS
 J) ROOF HATCHES
 K) ROOF ASSEMBLIES
 L) PRE-ENGINEERED A/C STANDS
  
 19) 106.3 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 20) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 21) THIS ROOF IS MISSING PRODUCT COMPLIANCE REPORTS
 WITH THE FOLLOW ITEMS:
 __XX_ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 __XX_ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM TO
 BE USED.
 __XX_ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 __XX_ IF THE SUB-SYSTEM TO BE USED INDICATES
 LIMITATION# 9, NO ENHANCED FASTENING ALLOWED.
  
 22) THE SHEET S4.1 DETAIL# 1 INDICATES THE TRELLIS
 ASSEMBLY AND NOA?S:
 NOA 03-0508.05 POST CAPS EXPIRED
 NOA 05-0105.05 RAFTER CLIPS EXPIRED
  
 23) A-104 ROOF PLAN FAILS TO IDENTIFY ROOF DRAINAGE
 SYSTEM AND OR DETAILS, THE ROOF DRAIN SIZE IS NOT
 PROVIDED, WHAT TYPE OF SECONDARY DRAINAGE AND VERTICAL
 CONTRIBUTING AREAS, THIS INFORMATION IS ALSO MISSING
 FROM THE PLUMBING PLAN. 106.3.5.1.1(8).
  
 24) ARCHITECTURAL PLANS ARE DEFICIENT IN INFORMATION
 FOR THE ENERGY CODE AND CALCULATIONS,
 106.3.5(9) &106.3.5.1.4(1) & 13-400.0.ABC COMPLIANCE
 CRITERIA.
  
 25) ELEVATIONS OF THE BREAK ROOM ARE NOT SHOWN, PLEASE
 PROVIDE COMPLIANCE WITH :
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK
  
 RENOVATION OF EXISTING NORTH WING :
  
 26A) UNTIL THE DESIGN TEAM INDICATES UNDER THE NEW
 BUILDING PORTION OF THIS REVIEW COMMENT# 5, A REVIEW
 CAN NOT TAKE PLACE WITH ANY ACCURACY, IF THE NEW
 CONSTRUCTION IS TO BE CONSIDERED AN ADDITION TO THE
 EXISTING BUILDING, OR IF THE TWO BUILDINGS ARE GOING TO
 BE CONSIDERED ONE LARGE BUILDING OR IF A ASSUMED
 PROPERTY LINE WILL BE ASSUMED BETWEEN THE TWO
 BUILDINGS. TABLE 503, TABLE 601, TABLE 602 & TABLE
 704.8.
  
 26B) THE D-100 PLAN APPEARS THE ONLY WORK TO BE
 COMPLETED IN THE NORTH WING IS IN CLASSROOM# 140.
 PLEASE PROVIDE A DETAILED ACCOUNTING OF WHAT WORK WILL
 BE COMPLETED UNDER THE RENOVATION PORTION OF THE
 PERMIT.
  
 26C) PLEASE ALSO INDICATE TO WHAT LEVEL ALTERATION WORK
 WILL ACCOMPLISHED UNDER THIS PERMIT. PLEASE SEE 2004
 FBC EXISTING BUILDING CODE 301.1.THE WORK PREFORMED ON
 AN EXISTING BUILDING SHALL BE CLASSIFIED IN ACCORDANCE
 WITH THIS CHAPTER.
  
 27) INCOMPLETE PLANS SHEET A-700 FINISH SCHEDULE IS
 BLANK FOR CEILING AND WALLS, THE DOOR SCHEDULE IS BLANK
 TO DOOR TYPE, FRAMES AND DOOR LABELS. WINDOW SCHEDULE
 DOESN?T INDICATE
 WHAT WINDOWS ARE TO BE REPLACED ON THE FLOOR PLAN AND
 WHICH ARE EXISTING.
  
 28) PLEASE INDICATE IF ANY ROOFING WORK WILL TAKE PLACE
 ON THE EXISTING BUILDING.
  
 BUILDING PLAN REVIEW
 JIM WITMER CBO
 PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2009-11-24 Cont ID  
Sent By dpalmer Date 2009-11-24 Time 10:04 Rev Time 0.00
Received By dpalmer Date 2009-11-24 Time 09:01 Sent To  
Notes
2009-11-24 10:12:43** SEPARATE NOTE FROM PROVISO**
  
 1) NOTE: SCOPE OF WORK HAS INCREASED. APPLIED VALUE FOR
 SCOPE OF WORK NEEDS TO BE INCREASED FOR ADDITIONAL
 SCOPE OF WORK NOT PART OF ORIGINAL PLANS.
 FBC 108.3
2009-11-24 10:04:41** PROVISO **
  
  
 1) NOTE: PLEASE UPDATE PANEL SCHEDULES FOR ALL
 CIRCUITING TO BE SPECIFIC TO ROOMS AND AREAS WHICH THEY
 FEED. FOR EXAMPLE.
  
 S-7, RECEPTACLES ROOM 101, ETC.
 MAY BE ALPHA OR NUMERIC.
  
 408.4
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2009-08-27 Cont ID  
Sent By dpalmer Date 2009-08-27 Time 10:51 Rev Time 0.00
Received By dpalmer Date 2009-08-27 Time 10:51 Sent To  
Notes
2009-08-27 10:53:06NO ELECTRICAL COMMENTS ON THE IDR OF THE SUBMITTED
 ENERGY CALCULATIONS. HOWEVER CALCULATIONS WILL NOT GET
 ELECTRICAL STAMPS/SIGN OFF AS THERE ARE ITEMS ON THE
 IDR FOR OTHER TRADES WHICH DO NOT CORRELATE WITH PLANS.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-08-19 Cont ID  
Sent By dpalmer Date 2009-08-19 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2009-08-19 Time 11:36 Sent To M
Notes
2009-08-19 11:36:37REV #6 ON E-3 OK

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2009-06-26 Cont ID  
Sent By dpalmer Date 2009-06-26 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2009-06-26 Time 12:11 Sent To PC
Notes
2009-06-26 12:12:16LIFT STATION REVISION, E3 AND 4

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-01-05 Cont ID  
Sent By dpalmer Date 2009-01-05 Time 10:11 Rev Time 0.00
Received By dpalmer Date 2009-01-05 Time 10:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-12-18 Cont ID  
Sent By dpalmer Date 2008-12-18 Time 11:40 Rev Time 0.00
Received By dpalmer Date 2008-12-18 Time 11:40 Sent To  
Notes
2008-12-18 11:41:09** DENIED 6TH REVIEW **
  
 1) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO FS
 471.025 AND FAC 61G15-23.002. PLANS ARE STILL BEING
 SUBMITTED WITHOUT ORIGINAL SIGNATURES.
 SOME SHEETS IN EACH OF THE 6 SIX SETS ARE SIGNED IN
 LEAD PENCIL, SOME IN COLOR PENCILS, AND SOME IN EACH
 SET ARE ONCE AGAIN STAMPED WITH THE USE OF A RUBBER
 STAMP IN LIEU OF ORIGINAL SIGNATURE.
 IF ALL SHEETS IN ALL SETS HAD BEEN SIGNED AS REQUIRED
 BY THE ABOVE SECTIONS, THE ELECTRICAL REVIEW WOULD HAVE
 BEEN PASSED AND ALL ELECTRICAL SHEETS WOULD HAVE BEEN
 STAMPED.
  
 ALL SHEETS IN ALL SETS HAVE NOW BEEN RETAINED AND WILL
 BE FORWARDED TO THE STATE BOARD OF PROFESSIONAL
 ENGINEERS FOR REVIEW OF SAID PLANS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-11-24 Cont ID  
Sent By dpalmer Date 2008-11-24 Time 08:23 Rev Time 0.00
Received By dpalmer Date 2008-11-21 Time 17:02 Sent To  
Notes
2008-11-24 08:23:49 
  
  
 ** FAILED RESUBMITTED PLAN REVIEW **
  
  
  
 1) NOTE: PERMIT APPLICATION HAS STILL NOT BEEN MADE.
 PLANS SUBMITTED FOR *PLAN REVIEW**
  
 2) NOTE: ON PREVIOUS REVIEWS THERE WERE PLANS SUBMITTED
 WHICH CONTAINED A *RUBBER STAMP* FOR THE ENGINEER IN
 LIEU OF THE REQUIRED ORIGINAL SIGNATURE PER FS 471.025
 AND FAC 61G15-23.002. THIS COMMENT HAS BEEN MADE TO
 THIS SAME ENGINEER ON MANY PROJECTS AND ON THIS SAME
 PROJECT ON PREVIOUS REVIEWS FOR BOTH BUILDINGS.
 RESPONSE MENTIONS PLANS WILL BE SIGNED DATED AND SEALED
 HOWEVER THE NEW SHEETS NOW SUBMITTED DO NOT CONTAIN AN
 ORIGINAL SIGNATURE. THIS IS NOT PERMITTED ANYWHERE IN
 THE STATE OF FLORIDA.
 CONTACT WITH THE FLORIDA BOARD OF ENGINEERS HAS BEEN
 MADE AND PLANS WILL BE FORWARDED TO THE STATE WITH ALL
 PREVIOUS RETAINED PLANS FOR THE REVIEW. TWO COMPLETE
 SETS OF ELECTRICLA PLANS HAVE BEEN RETAINED AS
 REQUESTED BY THE STATE. WHEN RESUBMITTING PLANS PLEASE
 BE SURE TO PROVIDE NEW SETS OF ELECTRICAL PLANS.
  
  
 3) NOTE: PLEASE SEE THE SUBMITTED INPUT DATA REPORT FOR
 THE ENERGY CALCULATIONS NEEDS TO COORDINATE WITH PLANS.
 SOME EXAMPLES WERE GIVEN ON EACH OF THE PREVIOUS
 REVIEWS HOWEVER ITEMS ARE STILL IN NEED OF ADDRESSING.
 PLANS NEED TO BE REVISED OR REVISE CALCULATIONS. IN
 EITHER CASE THE CALCULATIONS NEED TO MEET
 13-415.400.3.A, 13-415.2,13-415.2.ABC.1.1,.1.2 AND
 .1.3.
 THERE ARE OTHER COMPONENTS AND SYSTEMS WHICH ALSO NEED
 COORDINATION. SEE COMMENTS FROM OTHER TRADES WITH
 RESPECT TO OTHER SYSTEMS/COMPONENTS IN THE IDR WHICH
 ARE NOT THE SAME ON PLANS.
  
 THE EXAMPLES ON PREVIOUS REVIEWS FOR NON-CODE
 COMPLIANCE WERE ?EXAMPLES? AND REVIEW STATED IT WAS IN
 NO WAY ALL ITEMS. THIS OFFICE IS REQUIRED TO STATE THE
 CODE SECTIONS. AS A BENEFIT THIS OFFICE GIVES SOME
 ITEMS TO HELP UNDERSTAND THE CODE COMPLIANCE ISSUE
 WHICH IS OUTSTANDING TO BE ADDRESSED.
 IN MEETINGS HELD BEFORE PLANS WERE RE-SUBMITTED THIS
 REVIEWER OFFERED SEVERAL TIMES TO RESPONSIBLE DESIGNERS
 PRESENT TO CALL ONCE CALCULATIONS ARE BEING COMPLETED
 TO GO OVER *ANY* QUESTIONS OR CONCERNS. THIS WOULD HELP
 TO ALLEVIATE ANY FURTHER DELAYS UNNECESSARILY. TO DATE
 OF THIS REVIEWER HAS NOT BEEN CONTACTED SINCE THE
 MEETING.
  
 EXAMPLE:
 PLEASE SEE ITEMS SUCH AS *PIPING* ON THE IDR WHICH IS
 ACTUALLY BLANK. 13-411.1.ABC.2 PIPING INSULATION.
  
 EXAMPLE:
 PLEASE SEE OTHER ITEMS SUCH AS LIGHTING. THE SHEETS FOR
 EXAMPLE L-4.2 STILL SHOW LIGHTING FIXTURES WITH A MUCH
 HIGHER WATTAGE THAN WHAT IS SUPPOSE TO BE THE SAME
 FIXTURES ON THE ELECTRICAL PLANS. THE FACT IS THE SAME
 FIXTURES ON THE ELECTRICAL PLANS WHICH IS (Y1) IS
 55WATTS ON THE IDR AND THE ELECTRICAL PLANS YET THE L
 SHEET INDICATES THIS SAME FIXTURE AS 120WATTS. IN THE
 PREVIOUS REVIEW AS WELL AS MEETINGS IT WAS STATED TO
 COORDINATE ALL PLANS AND CALCULATIONS.
  
 EXAMPLE: PLEASE SEE THE SAME L-4.2 WHICH SHOWS A J1
 BOLLARD WHICH NOT ON ELECTRICAL PLANS OR THE ENERGY
 CALCULATIONS.
  
 EXAMPLE: PLEASE BE SURE TO SEE ALL *Y* TYPE FIXTURES
 SOME ARE LESS ON IDR THAN ON PLANS. MINOR DIFFERENCES
 ON THESE.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2008-11-21 17:04:15PLANS WILL GO INTO FAILED REVIEW STATUS.
  
 NOTES TO BE POSTED ON 11/24. NOTES PERTAINING TO PLANS
 NOT BE SIGNED, DATED AND SEALED AS REQUIRED WILL BE
 PART OF REVIEW ALONG WITH NOTES PERTAINING TO ENERGY
 CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-10-10 Cont ID  
Sent By dpalmer Date 2008-10-10 Time 15:15 Rev Time 0.00
Received By dpalmer Date 2008-10-10 Time 15:15 Sent To  
Notes
2008-10-10 15:15:20 
 ** DENIED 4TH REVIEW**
  
  
 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND
 NOT FOR PERMIT.
  
 2) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 DO NOT COORDINATE WITH PLANS. THERE ARE SEVERAL
 INCONSISTENCIES WITH THE SQ FOOTAGE ETC. PLEASE SEE
 COMMENTS FOR OTHER TRADES FOR ITEMS SUCH AS FLOORING
 ETC.
 LS SAFETY PLANS FOR NEW BUILDING SHOW IN EXCESS OF
 11,000 SQ FT, A-1000 STATES 10,000 SQ FT AS TOTAL
 BUILDING FOOT-PRINT YET THE CALCULATIONS STATE A TOTAL
 OF 8913.
 PLEASE BE SURE ALL LIGHTING AS SHOWN ON PLANS FOR TYPE
 OF FIXTURES, WATTAGE OF FIXTURES AND THE NUMBER OF
 FIXTURES COORDINATE WITH THE INPUT DATA REPORT OF THE
 SUBMITTED ENERGY CALCULATIONS.
 FOR EXAMPLE: SEE EXTERIOR LIGHTING, SOME OF THE
 FIXTURES AS SHOWN ON THE EXTERIOR OF THE BUILDING
 INCLUDING SITE ARE NOT ON THE IDR AT ALL.
 FOR EXAMPLE: ONE WOULD BE THE 175 WATT SITE LIGHTS.
 THERE ARE NO 175W FIXTURES ON THE IDR AT ALL.
  
 FOR EXAMPLE: ANOTHER WOULD BE THE *Y* FIXTURES. THESE
 ARE NOTED ON THE FIXTURE LEGEND AND ON PLANS IN MANY
 LOCATIONS. THE FIXTURE LEGEND MENTIONS TO SEE LANDSCAPE
 PLANS. THE LANDSCAPE PLANS CALLS FOR THESE SAME ITEMS
 AS BOLLARDS. ARE THEY BOLLARDS WITH LIGHTING FIXTURES?
 IF SO HOW IS IT POSSIBLE THAT THEY ARE SHOWN AS A *Y*
 FIXTURE WHEN THE SAME DESIGNATION IS USED FOR OTHER
 FIXTURES WHICH ARE CLEARLY NOT BOLLARDS? THE SHEET E-6
 DOES SHOW BOLLARDS AS PART OF THE SCHEDULE. NO BOLLARDS
 ARE SHOWN ON FIXTURE LEGEND. COORDINATION, AND
 DESIGNATIONS IS NEEDED.
 ** COMPLETE LEGEND WITH FIXTURES. (((AS LONG AS PLANS
 COORDINATE AND SHOW A ***MINIMUM*** CODE COMPLIANCE
 THEY MAY ALWAYS BE REVISED AT A LATER DATE))).
  
 FOR EXAMPLE: PLEASE SEE THE IDR, THE AMOUNT OF *S*
 FIXTURES NEED COORDINATING.
  
 FOR EXAMPLE: AS NOTED ABOVE FOR THE *Y* FIXTURES WHICH
 ARE NOTED AS 50W/55W FIXTURES THE *U* FIXTURES ARE ALSO
 SHOWN AS 50W/55W FIXTURES. BETWEEN BOTH OF THESE
 FIXTURES WHICH ARE NOTED AS 50W/55W THERE SHOULD BE A
 NUMBER FIXTURE FAR GREATER THAN WHAT IS SHOWN ON THE
 IDR. IN FACT THE IDR ONLY INDICATES A TOTAL OF 27 -55W
 FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS SHOW A
 FAR GREATER NUMBER OF *Y* AND *U* FIXTURES WHICH ARE
 THE SAME WATTAGE. THIS IS ACCORDING TO THE LIGHTING
 PLANS SUBMITTED SIGNED, DATED AND SEALED ON 9/28/08,
 THE FIXTURE LEGEND SIGNED DATED AND SEALED 6/26/08 AND
 CALCULATIONS SIGNED, DATED AND SEALED 9/29/08.
  
 FOR EXAMPLE: PLEASE TAKE A LOOK AT THE LIGHTING FOR
 INTERIOR AND GO OVER ALL FIXTURES IN ALL
 ZONES/SPACES/AREAS. NOT ALL FIXTURES ARE IN CONFERENCE
 MEETING ROOMS ALTHOUGH IN THE SAME ZONE. *C*?
  
 13-400.3.A, 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE WHICH GAVE
 INFORMATION TO THE FACT THE SITE LIGHTING POLES WERE
 NOTING SBCCI FOR DESIGN HOWEVER SBCCI HAS NOT BEEN AN
 ADOPTED CODE IN THE STATE OF FLORIDA SINCE MARCH 1ST OF
 2002. SEE E-1 *PARKING LOT LIGHT POLE DETAIL*. THIS HAS
 BEEN CIRCLED ON PREVIOUS PLANS AS WELL ON THESE PLANS
 ONCE AGAIN.
 PLEASE SEE FBC 2004W/2007 REVISIONS AS ADOPTED BY FS
 553.73.
  
 4) NOTE: AS NOTED IN COMMENT NUMBER #2 ABOVE WITH
 RESPECT LIGHTING FIXTURES AND COORDINATION NEEDED.
 PLEASE SEE THE LIGHTING AS SHOWN ON THE LANDSCAPE PLANS
 DOES NOT COORDINATE WITH ELECTRICAL OR ELECTRICAL DOES
 NOT COORDINATE WITH LANDSCAPE PLANS. THE ELECTRICAL
 PLANS CONTAIN NOTES TO SEE LANDSCAPE PLANS HOWEVER
 COORDINATION OF PLANS IS ESSENTIAL.
 LOADS, CALCULATIONS, ENERGY CALCULATION, CIRCUITING ETC
 ALL NEED TO BE VERIFIED SHOWING THE MINIMUM FOR CODE
 COMPLIANCE.
 408.4,310.16,240.4, 220, ETC
 FBC 13-415 ETC
 FBC 106.1.1,106.1.2 FOR CLARITY, ADDITIONAL INFORMATION
 AND COORDINATION OF PLANS.
  
 5) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH
 THE LIGHTING CONTROLS AND PANEL SCHEDULES. ONE EXAMPLE
 WHICH WAS THE SAME EXAMPLE GIVEN ON THE PREVIOUS REVIEW
 IS CIRCUIT L4-36. THE PLANS SHOW THIS CIRCUIT FEEDING
 THE EXTERIOR LIGHTS YET THE PANEL SCHEDULE STILL SHOWS
 THIS CIRCUIT FEEDING A *PROJECTION SCREEN*.
 NO RESPONSE WAS MADE TO THIS PART OF THE PREVIOUS
 REVIEW COMMENT AS AN EXAMPLE.
  
 6) NOTE: PLEASE SEE THE LIGHTING CONTROLS AND TYPES OF
 DEVICE NEEDS SOME COORDINATION OF WHAT WILL BE
 INSTALLED AND REQUIRED. THE RESPONSE MENTIONS
 *PHOTO-SENSOR* FOR INTERIOR LIGHTING AND SHEET E-6 ALSO
 SHOWS *PHOTO-SENSOR*.
 DUAL TECHNOLOGY DEVICES FOR OCCUPANCY SENSORS AND
 PHOTO-SENSORS ARE NOT THE SAME. THE PREVIOUS NOTES GAVE
 SECTION 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING AND
 METHODS OF CONTROLS. THE PLANS CALL FOR 10HR BACK UP OF
 INTERIOR LIGHTING HOWEVER THIS SECTION OF THE CODE
 WHICH WHEN USING A TIME CLOCK, REQUIRES THAT TIME CLOCK
 TO BE ASTRONOMICAL AND WITH A 10HR BACK UP MINIMUM FOR
 PROGRAMMING. IF USING A PHOTO-SENSOR (ALSO KNOWN AS A
 PHOTO-CELL) THE ASTRONOMICAL TIME CLOCK IS NOT REQUIRED
 NOR IS THE 10HR BACK UP.
 HOW CAN THESE BE NOTED A PHOTO-SENSORS? THIS IS NOT
 POSSIBLE.
 SYMBOL LEGEND CALLS FOR MOTION SENSORS. THERE ARE
 DEVICE WHICH ARE ONLY MOTION AND DO NOT CONTAIN THE
 MULTI-LEVEL DESIGN FOR DUAL TECHNOLOGY, ULTRASONIC,
 INFRARED ETC.
 LIGHTING CONTROL SYSTEM NEEDS MEET FBC
 13-415.1.ABC.1.1,.1.2 AND .1.3.
 THE CONTROLS AND SYSTEM SHOWN ON PLANS IS CONFUSING AND
 AS SHOWN IT IS NOT POSSIBLE TO BE A WORKING SYSTEM.
  
 ** LIGHTING SYSTEM IN RENOVATED BUILDING ALSO NEEDS TO
 BE GONE OVER.
  
  
 ** THIS IS THE THIRD REVIEW IN WHICH COMMENTS HAVE BEEN
 MADE ON THE LIGHTING SYSTEM. IT IS RECOMMENDED BY THIS
 OFFICE TO HAVE A MEETING TO GO OVER THE PLANS.
  
 7) NOTE: PLANS STILL NOTE THAT 8 COPIES OF SHOP
 DRAWINGS ARE REQUIRED AND 7 COPIES WILL BE STAMPED BY
 THE REVIEWER. THIS IS A THRESHOLD PROJECT ONLY THREE
 SETS ARE NEEDED AND ONLY THREE SETS WILL BE PROCESSED
 AND STAMPED.
  
 8) NOTE: AS NOTED ON PREVIOUS REVIEW THE RENOVATED
 BUILDING SHALL CONTAIN A MAIN OR A PERMANENT DEAD FRONT
 WHICH WILL NOT PERMIT MORE THAN 6 BREAKERS TO BE
 INSTALLED. ONCE THE PHASE TWO WORK IS COMMENCED THIS
 MLO ONLY EQUIPMENT WILL HAVE A DISCONNECT AS SHOWN ON
 RISER FOR THE NEW BUILDING HOWEVER NEED TO HAVE SOME
 SORT OF DISCONNECT SHOWN AT THIS TIME FOR PERMIT
 ISSUANCE.
 225.31-225.39
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-07-28 Cont ID  
Sent By dpalmer Date 2008-07-28 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2008-07-28 Time 13:03 Sent To  
Notes
2008-07-28 13:03:56 
 ** DENIED3RD REVIEW **
  
 ** PLEASE SEE THERE ARE SEVERAL ITEMS STILL FROM
 PREVIOUS REVIEWS WHICH ARE IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 AND THE INPUT DATA REPORT IS NOT CODE COMPLIANT AND
 DOES NOT COORDINATE WITH THE SUBMITTED PLANS.
 PLEASE SEE THAT THE NUMBER OF FIXTURES AND THE WATTAGES
 OF FIXTURES IS REQUIRED TO MEET 13-415.2.ABC.1.1,.1.2
 AND .1.3.
 THESE ARE ALL REQUIRED TO BE LOCATED IN THE IDR FOR
 ENERGY CODE COMPLIANCE.
  
 2) NOTE: PLEASE SEE THE LIGHTING CONTROLS SHOWN ON
 PLANS ARE NOT CODE COMPLIANT.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4.
 THERE ARE AREAS WITH STILL NO LIGHTING CONTROLS AND
 OVER RIDES WHICH ARE REQUIRED. MAY NOT USE A SINGLE
 POLE SWITCH TO OVER RIDE TIMED SCHEDULING? THIS DOES
 NOT PROVIDE ANY WAY OF AUTOMATICALLY SHUTTING OFF THE
 LIGHTING ONCE OVER RIDDEN. HOW CAN A SINGLE POLE SWITCH
 IN AREAS SUCH AS CLASSROOM, COMPUTER LAB BE AN
 AUTOMATED OVER RIDE?
 THE RESPONSE LETTER MENTIONS THE KITCHEN LIGHTING IS
 EXEMPT PER 13-415.1.ABC.1.1. (NUMBER 3) THERE IS NO
 EXEMPTION #3 IN THIS SECTION OF THE CODE AND KITCHEN
 LIGHTING IS NOT EXEMPT FROM THE REQUIRED AUTOMATED
 CONTROLS OF SOME KIND. PLEASE ADJUST PLANS.
 PLEASE SEE OTHER AREAS AS THE MULTI-GANG BATHS WILL BE
 NOTED BELOW.
 PLEASE PROVIDE A WIRING DIAGRAM ON HOW THE NEW
 OCCUPANCY SENSORS WILL BE WIRED WITH THE STANDARD
 SINGLE POLE SWITCHES WHICH ARE STILL SHOWN ON PLANS.
 THE CODE REQUIRES OVER RIDE OF SOME TYPE AT THE POINT
 OF ENTRANCE INTO ANY ONE SPACE IF USING TIMED
 SCHEDULING. THIS ALSO REQUIRES THE OCCUPANT TO VISUALLY
 SEE *ALL* LIGHTING WHICH IS BEING OVER RIDDEN OR MEET
 THE EXCEPTION WHICH IS AN INDICATOR PANEL OF SOME TYPE.
  
 AN EXAMPLE IS THE POINT OF ENTRANCE IN NEW BUILDING
 HALLWAY. THERE IS ONLY OVER RIDES AT ONE END AND NOT
 BOTH. THERE ARE NO INDICATORS NOTED. PLEASE SEE COMMENT
 BELOW WITH RESPECT TO THE TWIST TIMERS SHOWN.
 PLEASE SEE THE EXTERIOR LIGHTING IS NOT COMPLETE. THERE
 ARE ITEMS SUCH AS EXTERIOR LIGHTING (L4-36) WHICH IS
 NOT LISTED ON SCHEDULE. THIS CIRCUIT IS ACTUALLY LISTED
 AS *PROJECTION SCREEN* ON PANEL SCHEDULE.
  
 ** AS SYSTEM IS NOT COMPLETE, THE ABOVE SECTIONS NEED
 TO BE MET.
  
 3) NOTE: PLEASE PROVIDE THE WIRING DIAGRAM FOR
 OCCUPANCY SENSORS AS NOTED ABOVE FOR THE GANG BATHS. IF
 THE SINGLE POLE SWITCH AS SHOWN ALLOWS AN OCCUPANT TO
 TURN THE LIGHTING OFF IN THE BATHROOMS WHILE ANOTHER
 OCCUPANT IS STILL OCCUPYING THE BATHROOM THIS WILL NOT
 MEET MINIMUM REQUIRED FOR LIFE SAFETY. AS NO DETAIL FOR
 THE TYPE OF DEVICE AND HOW A SINGLE POLE SWITCH WILL BE
 CONNECTED IN THIS SCENARIO THIS DOES NOT MINIMUM.
 LS 101 7.8, FBC 13-415.1.ABC.1.2, .1.1.
 PLEASE PROVIDE SPEC/CUT SHEET FOR THESE DEVICES. 110.3
  
 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR A GENERATOR AND ATS AS PREVIOUSLY REQUESTED. A
 MINIMUM CODE REQUIRED ATS AND GENERATOR WILL BE PART OF
 THE PERMITTED SET OF PLANS AND DOCUMENTS. THIS CAN
 ALWAYS BE REVISED AT A LATER DATE IF THE MANUFACTURE OR
 EQUIPMENT CHANGES.
 110.3,90.7, 702.6 ETC
 FBC 106.1.1,106.1.2
 *** IF NOT PART OF THE SCOPE OF WORK THEN DELETE ALL
 REFERENCE AND INDICATE AS FUTURE. SEPRATE PERMIT
 APPLICATION, PLANS, FEES ECT WILL BE REQUIRED AT A
 LATER DATE.
 ** IF ATS IS INSTALLED AT THIS TIME WITH SERVICE
 EQUIPMENT THEN SUBMIT A CODE COMPLIANT ATS AT THIS
 TIME.
  
 *** RESPONSE LETTER NOTES THIS IS AN OPTIONAL STAND-BY
 SYSTEM. IT HAS NO BEARING ON OPTIONAL OR NOT, THE CODE
 DOES NOT STATE IF *OPTIONAL* THEN THE EQUIPMENT DOES
 NOT NEED TO BE LISTED ETC.
  
 5) NOTE: AS NOTED ON PREVIOUS REVIEW PANEL MDP SHALL
 CONTAIN A MAIN OR A MAIN DISCONNECTING MEANS AHEAD OF
 THIS MLO.THE CODE ADDRESSES THE NUMBER OF MEANS OF
 DISCONNECT PERMITTED AND THE PERMITTED SPACES IN THE
 EQUIPMENT. THIS INSTALLATION WHICH IS NOTED AS
 TEMPORARY DUE TO PHASING HAS NO BEARING ON WHAT *MAY*
 OR *MAY NOT* BE PERMITTED IN THE FUTURE. PLANS ARE
 REQUIRED TO SHOWN MINIMUM CODE COMPLIANCE AT THIS TIME
 OR WILL NOT BE PERMITTED. LIFE SAFETY DOES NOT RELY ON
 WHAT MAY BE PERMITTED IN PHASES. THE FACT IS PHASE TWO
 MAY NEVER HAPPEN AND THE SERVICE AS SHOWN WOULD BE
 NON-CODE COMPLIANT.
 CODE SECTIONS 225 FOR DETACHED BUILDINGS ARE INTENDED
 TO FOLLOW REQUIREMENTS OF 230 EVEN IF NOT SERVICE
 ENTRANCE RATED EQUIPMENT. AS THERE ARE NO PROVISIONS TO
 PREVENT THIS HAZARD AS NOTED ABOVE A MAIN IS REQUIRED
 AT THIS TIME IN FIRST PHASE.
 THIS IS SERVICE ENTRANCE RATED EQUIPMENT AT THIS TIME.
 230 SECTIONS APPLY ALSO.230.70, 230.71, 230.72, 230.76,
 230.79 ETC.
 *** NOTE, PHASE ONE OR PHASE TWO HAS NOT APPLIED FOR
 ANY PERMIT.
  
 6) NOTE: PLEASE SEE NEW RULE 69A-60.004 FOR ADOPTION OF
 THE 2006 NFPA-101. AS THIS HAS NOT APPLIED FOR PERMIT.
 ** IT WAS NOTED THIS RULE MAY BE GETTING A CHANGE
 HOWEVER AT THIS TIME IT IS ADOPTED.
  
 7) NOTE: WIND LOADS REFERENCE BOTH THE FBC AND SBCCI.
  
 ** PLEASE COMPLETE PLANS.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-21 Cont ID  
Sent By dpalmer Date 2008-05-21 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2008-05-21 Time 16:29 Sent To  
Notes
2008-05-21 16:29:48** DENIED 2ND REVIEW**
  
 ** PLEASE SEE SEVERAL ITEMS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE NEW
 COMMENTS AS PLANS ARE NOW MORE COMPLETE THAN SUBMITTED
 ON PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE BOTH SETS OF PLANS FOR BOTH
 BUILDING DO NOT CONTAIN AN ORIGINAL SIGNATURE BY THE
 ENGINEER OF RECORD. IN FACT EACH AND EVERY SIGNATURE IS
 A *RUBBER-STAMP* ON ALL FOUR SETS OF PLANS. THIS IS
 DONE IN LIEU OF THE REQUIRED ORIGINAL SIGNATURE AS
 REQUIRED PER FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002.
 THIS OFFICE HAS MADE THIS SAME COMMENT TO THIS DESIGNER
 OF RECORD ON SEVERAL OTHER REVIEWS ON OTHER PROJECTS
 YET PLANS ARE STILL BEING SUBMITTED WITH THE SAME
 *RUBBER-STAMP*.
 THIS OFFICE IS LEFT WITH NO CHOICE BUT TO FORWARD ALL
 PLANS AND DOCUMENTS TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS FOR REVIEW OF SAID STATUTORY
 VIOLATIONS.
 THESE WILL BE SENT WITH PLANS FROM OTHER PROJECT
 PREVIOUSLY RETAINED FOR THE SAME COMMENT.
 PLEASE KNOW WHEN SIGNING, DATING AND SEALING PLANS: ALL
 MUST BE ORIGINAL SIGNATURE. A *RUBBER-STAMP* SHALL NOT
 BE USED. THIS HAS BEEN CONFIRMED WITH THE FLORIDA BOARD
 OF ENGINEERS AND LEGAL COUNSEL TO THE BOARD ON MANY
 OCCASIONS.
  
 2) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE SETS OF
 ALL DOCUMENTS INCLUDING ENERGY CALCULATIONS. ONLY ONE
 SET OF CALCULATIONS WERE SUBMITTED.
 FBC 106.1, 106.1.3, 106.5.
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH FLORIDA BUILDING
 CODE AND CHAPTER 13 FOR CODE REQUIRED LIGHTING CONTROLS
 HAS NOT BEEN MET. THIS WAS A COMMENT ON THE PREVIOUS
 REVIEW AS NO LIGHTING CONTROL SYSTEM WAS DESIGNED INTO
 THE PROJECT ON ORIGINAL PLANS SUBMITTED. RESPONSE
 MENTIONS TO SEE REVISED PLANS HOWEVER COMPLIANCE WITH
 CHAPTER 13 HAS STILL NOT BEEN MET.
 PLEASE SEE NOTE # 7 ON SHEET E-2: THIS NOTE SATES
 *LIGHTING CONTROLS SHALL BE PROVIDED TO MEET PARAGRAPH
 13-415.1.ABC.1.1 OF THE FLORIDA BUILDING CODE*. THE
 CODE SHALL NOT BE QUOTED IN LIEU OF REQUIRED DESIGN.
 PLEASE SEE OTHER SECTIONS OF CHAPTER 13 FOR LIGHTING
 CONTROLS IS ALSO REQUIRED SUCH AS 13-415.1.ABC.1.2,
 13-415.1.ABC.1.3 AND 13-415.1.ABC.1.4.
 PLEASE TAKE A LOOK AT SECTION 13-415.1.ABC.1.1 AND
 .1.2. THE LIGHTING CONTACTORS AS SHOWN DO NOT PROVIDE
 CODE COMPLIANCE. IN FACT ALL DEVICES IN ALL *SEPARATE
 SPACES* ARE STILL BEING SHOWN AS STANDARD SWITCHING
 DEVICES. PLEASE SEE THIS IS CLEAR ON THE SYMBOL LEGEND
 ON E-7 AS WELL AS NOTE #5 ON E-2. IT IS NOT POSSIBLE TO
 USE *STANDARD SWITCHES* WHEN MOST LIGHTING CIRCUITS ARE
 ALL GOING THROUGH LIGHTING CONTACTORS.
 PLEASE SEE THESE SAME SECTIONS OF CODES AS *ALL
 SEPARATE SPACES* ARE REQUIRED TO CONTAIN CONTROLS TO
 OVER RIDE ANY TIME OF DAY SCHEDULING.
 PLEASE SEE LIGHTING CONTROLS ARE REQUIRED TO BE LOCATED
 SO THE OCCUPANT CAN SEE THE LIGHTING IN WHICH IS BEING
 CONTROLLED OR MEETING THE EXCEPTIONS FOR *PILOT LIGHTS*
 ETC.
 PLEASE ALSO SEE 13-415.1.ABC.1.2 FOR OTHER TYPES OF
 ROOMS WHICH REQUIRE OCCUPANCY SENSOR DEVICES. THIS IS
 ABOVE ANY TIME OF DAY LIGHTING CONTROLS.
 EXAMPLES: AS LISTED IN THE CODE, CLASSROOMS,
 CONFERENCE/MEETING ROOMS, LUNCH, BREAK ROOMS.
 PLEASE THE LIGHTING CONTACTOR AND PLANS AS SHOWN DOES
 NOT SHOW ANY OVER RIDES, DOES NOT SHOW ANY SPACE
 CONTROLS ETC.
 PLEASE SEE 13-415.1.ABC.1.3 FOR *ADDITIONAL CONTROLS*
 REQUIRED.
 PLEASE SEE 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING
 CONTROLS. PLANS INDICATE LIGHTING TO BE THROUGH A TIME
 CLOCK HOWEVER THIS SECTION OF THE CODE REQUIRES ONE OF
 TWO METHODS OF CONTROL. PLEASE KNOW IF USING A TIME
 CLOCK THIS SHALL BE AN ASTRONOMICAL TIME CLOCK NOT A
 STANDARD TIME CLOCK. THIS TC MUST ALSO CONTAIN A
 MINIMUM BATTERY BACK UP FOR PROGRAMMING WHICH CONTAINS
 A MINIMUM 10 HOURS OF BACK UP.
  
 ** IT IS IMPORTANT TO KNOW AS SEVERAL DEVICES ON PLANS
 WILL BE REQUIRED TO BE REVISED TO MEET MINIMUM CODE
 COMPLIANCE THERE MAY CERTAINLY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT POSSIBLY BE MADE AT THIS
 TIME.
  
 *** PLEASE SEE COMMENT BELOW WITH RESPECT TO HAND-WOUND
 TIMERS SHOWN ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE SEE FLORIDA BUILDING CODE CHAPTER 13
 FOR LIGHTING PERFORMANCE AND CODE COMPLIANT ENERGY
 CALCULATIONS TO BE SUBMITTED.
 PLEASE SEE 13-400.0.A, 13-400.3.A, 13-415.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THE METHOD OF CALCULATION SUBMITTED FOR THE
 NEW BUILDING IS METHOD *A* HOWEVER NO CALCULATIONS WERE
 SUBMITTED FOR THE EXISTING SEPARATE BUILDING WHICH IS
 BEING RENOVATED.
 PLEASE SEE THE VERSION SUBMITTED IS NOT UNDER THE
 ADOPTION OF THE FBC 13-400.3.A. PLEASE SEE THE CODE
 SPECIFICALLY ADOPTS VERSION 2.5 AND THE VERSION
 SUBMITTED WAS 3.0. THIS HAS BEEN CONFIRMED WITH THE
 DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA BUILDING
 COMMISSION ON MORE THAN ONE OCCASION.
 PLEASE ALSO SEE THE CERTIFICATION SHEETS LIST
 MECHANICAL AND ELECTRICAL DESIGNERS WHICH ARE NOT
 LISTED AS ENGINEERS. IN FACT THE DESIGNER WHICH IS
 SIGNED, DATED AND SEALED ON THE CERTIFICATIONS IS NOT
 EVEN LISTED WITH NAME OR LICENSE NUMBER YET THIS
 DESIGNER IS LISTED ON PLANS AS THE MECHANICAL DESIGNER
 OF RECORD.
 PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS DO NOT
 MEET THE MINIMUM FOR CODE COMPLIANCE. IN FACT THERE ANY
 SEVERAL ITEMS ON PLANS THAT DO NOT COORDINATE WITH THE
 INPUT DATA REPORT. SOME EXAMPLES WILL BE GIVEN BELOW
 HOW THESE ARE NOT AN EXHAUSTIVE LIST OF ALL ITEMS: THE
 INPUT DATA REPORT WILL BE NOTED AS IDR.
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR EXTERIOR LIGHTING SHOWS NO
 LIGHTING AND IS COMPLETELY *BLANK*. HOW IS THIS
 POSSIBLE WHEN THE PLANS CLEARLY INDICATE AND SHOW
 DOZENS OF EXTERIOR LIGHTS?
 FOR EXAMPLE:
 PLEASE SEE THE IDR FOR INTERIOR LIGHTING WHICH
 INDICATES *MANUAL ON/OFF* CONTROLS FOR ALL INTERIOR
 LIGHTING. HOW IS THIS POSSIBLE WHEN ALL INTERIOR
 LIGHTING IS REQUIRED TO BE UNDER SOME SORT OF AUTOMATED
 CONTROL?
 FOR EXAMPLE:
 PLEASE SEE THE WATER HEATER KW RATINGS SHOWN ON THE IDR
 DO NOT COORDINATE WITH PLANS AS THE PLANS INDICATE A
 HIGHER KW RATING.
 ** THIS OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE BE
 SURE TO GO THROUGH ALL LIGHTING ON PLANS, METHOD OF
 CONTROLS, TYPES OF FIXTURES, WATTAGE OF FIXTURES AND
 NUMBERS OF FIXTURES. THESE WERE A FEW EXAMPLES ONLY.
  
 5) NOTE: PLEASE SEE THE CONDUIT SIZES AS LISTED ON E-4
 ON CONDUIT/WIRE NOTES. PLEASE SEE NOTES #1, 2 AND 3
 WHICH INDICATE AS MANY AS 4-500MCM AND EQUIPMENT
 GROUNDING CONDUCTOR?S 1/0 AND 2/0 IN TWO-INCH CONDUITS.
 THIS IS NOT POSSIBLE AS WELL AS NOT MEETING CODE FOR
 DE-RATING AND MINIMUM CONDUIT SIZING. PLEASE SEE
 CONDUIT FILL TABLES IN CHAPTER 9 OF THE NEC AND
 300.17.
  
 6) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE STILL
 SHOWING THE INSTALLATION OF A NATURAL GAS GENERATOR.
 THIS UNIT NEEDS TO BE CLASSIFIED AS *OPTIONAL STAND-BY*
 ONLY AS THIS IS NOT FOR AN EMERGENCY/LIFE SAFETY OR
 LEGALLY REQUIRED SYSTEMS.700,701,702.
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR THE
 PROPOSED GENERATOR AND ATS AS REQUESTED ON THE PREVIOUS
 REVIEW. RESPONSE MENTIONS THIS WILL BE DONE UNDER SHOP
 DRAWING SUBMITTALS HOWEVER IF THIS SCOPE IS INCLUDED IN
 THIS BASE BUILDING OR AS SHOWN ANY WORK WILL BE DONE
 UNDER BASE BUILDING THESE SHALL BE SUBMITTED AT THIS
 TIME.
 110.3, 90.7
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 ** IT IS IMPORTANT TO KNOW IF THE GENERATOR UNIT FEEDS
 ANY LIFE SAFETY OR LEGALLY REQUIRED LOADS THERE MAY
 ALSO BE OTHER REQUIREMENT SIN NFPA-110 WHICH ARE
 REQUIRED TO BE MET.
 PLEASE SEE FBC CHAPTER 27 WHICH REFERENCES ALL BACK UP
 POWER SYSTEMS SHALL BE INSTALLED PER NFPA-110. AS THERE
 IS INFORMATION NOT YET SUBMITTED SOME COMMENTS CAN NOT
 BE MADE.
 PLEASE SEE LOCATION SHALL MEET CHAPTER 7 FOR ROOM
 CONSTRUCTION, VENTILATION, ELECTRICAL EQUIPMENT
 INSTALLATION ETC.
  
 7) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2. PLEASE
 PLACE NOTES ON PLANS ACCORDINGLY.
  
 8) NOTE: PLEASE CLARIFY THE MAIN BREAKER DISCONNECT
 BEING SHOWN. THE PLANS CALL FOR A *SHUNT-TRIP* WHICH
 MAY NOT BE USED IN LIEU OF THE REQUIRED MANUAL MEANS OF
 DISCONNECT RATED FOR THE LOAD SERVED PER 230.76,
 230.79.
 THE NOTE #14 ON PLANS ON SHEET E-4 GIVES ANY PERSON
 FALSE SENSE THAT THE MAIN WILL BE TURNED OFF BY USE OF
 SHUNT TRIP.
 THE MEANS OF DISCONNECTS FOR MAIN WILL BE LABELED FOR
 NORMAL AND EMERGENCY, NOT THE SHUNT TRIP.
 PLEASE SEE 230.2E, 702.8.
 PLEASE ALSO PLACE NOTES ON PLANS THAT OTHER BUILDINGS
 WHICH WILL NOW BED FED FROM TWO SOURCES OF POWER SHALL
 CONTAIN NOTES FOR SIGNS AT EACH OF THESE EXISTING
 LOCATIONS.
  
 9) NOTE: PLEASE PROVIDE GROUNDING ELECTRODE SYSTEMS AT
 EACH STRUCTURE AND SERVICE PER 250.50. THE PLANS SHALL
 SHOW MINIMUM REQUIRED ATTACHMENTS. QUOTING THE CODE IN
 LIEU OF MINIMUM REQUIRED BY CODE IS NOT ACCEPTABLE.
 PLEASE BE SURE TO SEE 250.32, 250.50 AT ANY DETACHED
 BUILDINGS.
  
 10) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN ON THE LINE SIDE OF PANEL MDP TO
 THE THIS MDP.250.50, 250.110, 250.122, 250.32 ETC
 THE EQUIPMENT GROUND IS BROUGHT TO THE MAIN BUT NOT
 FROM MAIN TO MDP.
  
 11) NOTE: PLEASE SEE THE CODE SECTIONS GIVEN ON THE
 LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70
 (NEC) ADOPTED BY THE STATE OF FLORIDA.
 PLANS SHOW 220.35
 PLEASE SUBMIT THE FPL DOCUMENTS SUPPORTING THE
 DE-RATING OF SOME SERVICE EQUIPMENT AS MUCH AS 600AMPS.
 220.87
 FBC 106.1.2
  
 12) NOTE: PLEASE PLACE NOTES ON PLANS FOR REQUIRED ARC
 FLASH PROTECTION PER 110.16
  
 13) NOTE: PLEASE KNOW AT THIS POINT IN TIME THE
 APPLICATION CODE IS THE 2004 FBC WITH THE 2007
 REVISIONS.
 THE STATE OF FLORIDA IS SCHEDULED TO ADOPT NEW CODE
 STANDARDS ON OCT 1ST, 2008.
  
 14) NOTE: PLEASE SEE THAT ALL INFORMATION ON TITLE
 BLOCKS IS REQUIRED TO BE COMPLETE AND ACCURATE. PLEASE
 SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 61G1-16.004, FLORIDA STATUTES 471.023 AND 481.219 FOR
 REQUIRED INFORMATION AND LICENSING INFORMATION TO BE ON
 TITLE BLOCKS.
 THIS COMMENT IS MADE UNDER ELECTRICAL REVIEW BASED ON
 THE FACT THE TITLE BLOCKS FOR ALL FIRMS ARE LISTED ON
 ALL SHEETS AND LICENSE INFORMATION ON AT LEAST ONE FIRM
 IS NOT LISTED AND CURRENT WITH THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 ** LANDSCAPE ENGINEER**.
 PLEASE SEE LANDSCAPE PLANS INDICATE A *LANDSCAPE
 ARCHITECTURAL FIRM* NOT A LANDSCAPE ENGINEERING FIRM.
 PLEASE SEE THE TITLE BLOCKS ON OTHER SHEETS SUCH AS
 LANDSCAPE SHEETS; CIVIL SHEETS ETC DO NOT CONTAIN
 LICENSING INFORMATION AS REQUIRED UNDER ADMINISTRATIVE
 CODES OR STATUTES. THIS INFORMATION MAY OR MAY NOT BE
 MADE UNDER OTHER TRADE REVIEWS. IN ANY CASE THESE ARE
 IN VIOLATION OF SECTIONS GIVEN AND SHALL BE MET WHETHER
 OR NOT COMMENT IS MADE BY ANY OTHER TRADE REVIEWER(S).
 THIS COMMENT DOES APPLY TO SMITH ENGINEERING AS THEIR
 INFORMATION LISTED IS CORRECT INFORMATION ON THEIR
 TITLE BLOCKS.
 THIS COMMENT DOES APPLY TO ALL MEP PLANS AS THESE OTHER
 FIRMS ARE LISTED ON THE MEP SHEETS.
  
 15) NOTE: PLEASE COORDINATE ALL PLANS FOR BOTH
 BUILDINGS FOR SERVICE EQUIPMENT ETC.
 PLEASE SEE ONE EXAMPLE OF THIS IS THE RISER ON THE
 RENOVATED GYM BUILDING INDICATES CLEARLY THE EXISTING
 CT CAN IS TO REMAIN AND DOES NOT SHOWN ANY NEW MAIN
 DISCONNECT BEING FED FROM THE NEW DP PANEL AT THE NEW
 BUILDING. THE RISER ON SHEET E-4 ON THE NEW BUILDING
 SHOWS AND NOTES A NEW 600AMP MAIN HOWEVER THE RISER ON
 SHEET E-3 FOR THE RENOVATED GYM DOES NOT SHOW ANY NEW
 MAIN.
 PLEASE SEE THE EXISTING GYM BUILDING RISER ON SHEET E-3
 CLEARLY INDICATES A NEW 600AMP MDP YET THE RISER ON
 SHEET E-4 OF NEW BUILDING SHOWS *EXISTING* 600AMP MDP.
 240.4, 310.16, 225.31-225.39, 250.32 ETC.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION
 AND COORDINATION.
  
  
 16) NOTE: PLEASE SEE AS NOTED ABOVE THIS SUPPOSED NEW
 600AMP MDP AS SHOWN ON THE RENOVATED PLANS ON SHEET E-3
 SHOWS EACH BREAKER AS MAIN 1 OF 4, 2 OF 4, 3 OF 4, 4 OF
 4 AND THEN A 5 OF 4. HOW CAN THIS BE 5 OF 4? EACH OF
 THESE WOULD BE 1 OF 5 ETC.
 PLEASE KNOW IN ANY CASE IF THIS PANEL BOARD WILL BE A
 NEW MDP, THERE MAY NOT BE SPACE FOR MORE THAN 6 MAINS.
 THIS EQUIPMENT IS SHOWN WITH 30 SPACES AND THIS
 EQUIPMENT IS SHOWN AS A MLO (MAIL LUG ONLY) BOARD.
 THIS IS NOT PERMITTED. 225.33A
 PLEASE COORDINATE WITH RISER ON SHEET E-4 OF NEW
 BUILDING PLANS AS A MAIN IS SHOWN IN FRONT OF THIS
 EQUIPMENT. IF THIS IS THE CASE EACH BRANCH BREAKER
 WOULD NOT BE LABEL *MAINS 1 OF 4/5*.
 THESE WOULD NO LONGER BE MAINS.
  
 17) NOTE: PLEASE SEE NOTES ABOVE FOR NEW BUILDING WITH
 RESPECT TO REQUIRED LIGHTING CONTROLS, DEVICES, OVER
 RIDES, SEPARATE SPACES ETC ALSO APPLIED TO THE
 RENOVATED BUILDING.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4.
  
 18) NOTE: PLEASE KNOW ENERGY CALCULATIONS PER
 13-101.1.3, 13-400.3.B, 13-400.3.C MAY BE REQUIRED
 BASED ON RENOVATION VALUE. AT THIS TIME THIS CAN NOT BE
 CONFIRMED AS THE APPLIED VALUE HAS NOT BEEN
 DETERMINED.
  
 19) NOTE: PLEASE SEE FBC CHAPTER 11, AS SPRING WOUND
 TIMERS IN ACCESSIBLE AREAS ARE NOT PERMITTED. THESE DO
 NOT MEET THE FOLLOWING SECTION.
 11-4.27.4 CONTROLS AND OPERATING MECHANISMS SHALL BE
 OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER THAN
 5 LBF (22.2 N).
  
 20) NOTE: PLEASE SEE THE POWER PLANS AND PLANS IN
 GENERAL NEED TO SHOW THE LOCATION OF ALL PANELS AND
 SERVICE EQUIPMENT.
 PLEASE SEE RISER WHICH INDICATES A NEW BACK FEED FROM
 NEW *DP* TO EXISTING *SW* HOWEVER COULD NOT LOCATE THE
 LOCATION OF THIS EXISTING *SW*.
 NOTE ON RISER MENTIONS TO GROUND PER 250 OF THE NEC
 HOWEVER AS NOTED ABOVE, MAY NOT QUOTE CODE IN LIEU OF
 REQUIRED DETAIL.
 PLEASE SHOW LOCATION OF *SW*, COULD NOT LOCATE THIS ON
 THE GYM BUILDING PLANS AS SHEET E-4 ON NEW BUILDING DP
 NOTES THIS IS THE LOCATION. HOWEVER THIS CAN NOT BE
 CONFIRMED.
 110.26, 240.24 ETC
  
 21) NOTE: PLEASE KNOW PLANS ARE BEING RETAINED AT THIS
 TIME.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-21 Cont ID  
Sent By dpalmer Date 2007-10-21 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2007-10-21 Time 14:41 Sent To  
Notes
2007-10-21 16:09:052007-10-21 16:09:05
  
 *** DENIED ***
  
 1) NOTE: PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED
 FOR *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT.
 PLEASE ALSO SEE THAT PLANS AS SUBMITTED ARE NOT
 COMPLETE AND A COMPLETE REVIEW CAN NOT BE DONE. SOME
 SHEETS ARE 60 PERCENT AND SOME SHEETS LIKE THE LIFE
 SAFETY PLANS ARE BLANK WITH NO INFORMATION.
 PLEASE SEE THERE IS NUMEROUS SUPPORTING DOCUMENTATION
 NEEDED FOR REVIEW WHICH WAS NOT SUBMITTED.
 ** PLEASE KNOW THAT REVIEW NOTES CAN ONLY BE MADE ON
 PLANS AND DOCUMENTS SUBMITTED. THERE MAY VERY WELL BE
 NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 POSSIBLY BE MADE AT THIS TIME.
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
  
 ** PLEASE SEE SOME CODES ARE SHOWN ON COVER SHEETS
 WHICH ARE NO LONGER IN AFFECT IN THE STATE OF FLORIDA
 PLEASE SEE FOR EXAMPLE THE 2002 NFPA-70 AND 2000
 NFPA-101 WHICH IS REFLECTED ON PLANS.
  
 3) NOTE: PLEASE BE SURE WHEN PLANS ARE SUBMITTED THAT
 ALL SHEETS CONTAIN COMPLETED TITLE BLOCKS ON ALL SHEETS
 AND FOR ALL TRADES ON THE RESPECTIVE SHEETS. PLEASE SEE
 FAC 61G1-16.004, 61G15-23.002 ETC AS THIS INCLUDES
 ARCHITECTURAL, LANDSCAPE, MEP ETC.
  
 4) NOTE: PLEASE BE SURE ALL PLANS ARE SIGNED, DATED AND
 SEALED AS REQUIRED PER THE SAME SECTIONS ON THE FAC AND
 FLORIDA STATUTES 471.025, 481.221 ETC.
  
 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER FBC
 CHAPTER 13.
 PLEASE BE SURE TO SEE THE FACT THAT THIS NEW BUILDING
 ELECTRICAL SERVICE WILL FEED EXISTING BUILDING WHICH
 WILL HAVE ENERGY USE.
 PLEASE SEE 13-415.1.AB.1, 13-415.2, 13-415.1.ABC.1.2,
 13-415.2.ABC.1.3 ETC.
 FBC 106.1.2, 106.3.5.1.2 ETC
  
 6) NOTE: PLEASE SUBMIT MORE INFORMATION ON COMPLETE
 LIGHTING CONTROLS AND SYSTEM PER 13-415.1.1, .1.2, .1.3
 AND .1.4.
 NOT ENOUGH INFORMATION SUBMITTED FOR COMPLETE REVIEW.
 PLANS APPEARS TO SHOW STANDARD SWITCHING DEVICES. FBC
 106.1.23 FOR ADDITIONAL INFORMATION.
  
 7) NOTE: PLEASE SHOW ALL FIRE ALARM DEVICE LOCATIONS
 AND MINIMUM LEVELS FOR ADA COMPLIANCE.
 PLEASE SEE FBC 11-4.28.1,.2, AND .3(4)
 ** THIS IS REQUIRED EVEN AS THE FIRE ALARM PLANS ARE
 UNDER SEPARATE PERMITS AND PLANS.
  
 8) NOTE: PLEASE PROVIDE INFORMATION ON ANY EMERGENCY
 AND/OR LIFE SAFETY SYSTEMS OR DEVICES IN THE EXISTING
 BUILDINGS WHICH MAY BE FED FROM THIS NEW GENERATOR.
 THIS MAY AFFECT THE RISER AND SYSTEM AS SHOWN. 700.1,
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 9) NOTE: PLEASE SEE KEY NOTES ON E-1 ARE NOT COMPLETE
 ON PLANS.
 PLEASE SHOW AND LABEL ALL SERVICE EQUIPMENT ON PLANS.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
 NEC 240.24, 110.26 ETC
  
 10) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT
 SHEETS FOR THE PROPOSED GENERATOR AND ATS.
 110.3, 90.7.
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
 11) NOTE: PLEASE INDICATE THE MINIMUM LIGHTING LEVELS
 FOR EGRESS PATHS TO PUBLIC RIGHT OF WAY/EXIT
 DISCHARGE.
 PLEASE SEE FOR EXAMPLE THE ENTRANCE HALLWAY WHICH DOES
 NOT SHOW ANY EMERGENCY LIGHTING.
 LS-101 7.8, 7.9.
 FAC 61G15-33.004.
 PLEASE SEE AS THE LIFE SAFETY PLANS ARE NOT COMPLETE,
 PLEASE BE SURE TO SEE NFPA-101 7.10.1.6 AND 12.4.7.7.2
 IN ASSEMBLY AREAS FOR POSSIBLE FLOOR PROXIMITY EXIT
 LIGHTING.
 PLEASE ALSO SEE FBC CHAPTER 1006.3.8.2, 1006.3.8.3.
  
 12) NOTE: PLEASE SEE 2005 NEC FOR LOAD CALCULATIONS.
 PLEASE SEE FOR EXAMPLE ELECTRICAL WATER HEATER LOADS
 ARE NOW CONSIDERED CONTINUOUS IN THE NEW CODE. THIS
 REQUIRES THE LOADS TO BE SHOWN AND FIGURED AT 125%.
 PLEASE ALSO SEE THE LOAD SHOWN *PER FPL* FOR THE
 EXISTING PANEL SW EXCEEDS THAT OF THE RATING OF THE NEW
 FEEDERS AND OVER CURRENT PROTECTION FEEDING THIS
 EXISTING EQUIPMENT. 240.4, 310.16 ETC.
 PLEASE THE SECTION OF THE CODE REFLECTED ON
 CALCULATIONS IS FROM THE PREVIOUS CODE.
 ** PLEASE PROVIDE MORE INFORMATION ON THE EXISTING
 LOADS ON THE EXISTING BUILDINGS. *SW* IS GOING FROM A
 1200AMP SERVICE DOWN TO A 600AMP FEEDER WHICH CREATES
 SOME QUESTIONS.
 NEC 220.
 FBC 106.3.5.1.2
  
 13) NOTE: PLEASE PLACE NOTE(S) ON RISER/PLANS FOR
 DISCONNECTS AT THE EXISTING BUILDINGS WHICH WILL NOW
 BED FROM THE NEW SERVICE.
 PLEASE SE THAT ALL NEUTRAL AND GROUNDING CONNECTIONS AT
 THE FIRST MEANS OF DISCONNECT MUST BE SEPARATED. THIS
 IS FOR MAIN DISCONNECTS 8/10/ AND 12 AS LABELED WITH
 NOTES ON RISER.
 ** OCTAGONAL NOTE #12 DOES CONTAIN A MENTION OF
 REMOVING BONDING JUMPER.
 250.6, 250.24 ETC
  
 14) NOTE: PLEASE SUBMIT VOLTAGE DROP CALCULATIONS FOR
 WORST CASE ON FEEDERS PER 13-413.1.ABC.1.1 AND BRANCH
 CIRCUITS PER 13-413.1.ABC.1.2.,
 **ONLY NEED TO SHOW WORST CASE FOR EACH.
  
 15) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE
 BREAKER ON THE GENERATOR. WILL THIS BREAKER BE READILY
 ACCESSIBLE FOR DISCONNECTING THE EMERGENCY POWER? AS
 THIS CAN NOT BE CONFIRMED, THE DP MAY BE REQUIRED TO
 CONTAIN A DISCONNECTING MEANS SUCH AS A MAIN CIRCUIT
 BREAKER OR DISCONNECT ON THE LOAD SIDE OF THE GENERATOR
 MAY BE REQUIRED.
 IF BREAKER IS ON UNIT AND IS READILY ACCESSIBLE, THEN
 PLEASE PROVIDE NOTE FOR SIGNAGE REQUIRED FOR DISCONNECT
 MEANS DURING AND EMERGENCY SITUATION.
 445.18
  
 16) NOTE: PLEASE KNOW THE RESTROOMS AS SHOWN ON PLANS
 WILL BE REQUIRED TO CONTAIN A BATTERY BACK UP LIGHTING
 FIXTURE OF SOME KIND FOR EGRESS LIGHTING.
 PLEASE BE SURE TO ALSO KNOW THAT DEPENDING ON LIGHTING
 CONTROL DEVICES WHICH HAVE NOT YET BEEN REVIEWED, A
 NIGHT LIGHT MAY BE NEEDED.
 PLEASE SEE NEC 700.12F, 700.16, LS 101 7.8, 7.9. PLEASE
 SEE NOTES ABOVE WITH RESPECT TO LIGHTING LEVELS
 REQUIRED FOR EGRESS.
  
 ** PLEASE KNOW AS MENTIONED ABOVE AS PLANS AND
 INFORMATION IS NOT COMPLETED A COMPLETE REVIEW COULD
 NOT BE DONE.
  
 ** PLEASE SURE TO SEE COMMENTS FROM OTHER TRADES WHICH
 MAY ALSO AFFECT THE ELECTRICAL PLANS/DESIGN.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 5 Status F Date 2010-09-22 Cont ID  
Sent By mgonzale Date 2010-09-22 Time 11:40 Rev Time 2.00
Received By mgonzale Date 2010-09-22 Time 11:40 Sent To  
Notes
2010-09-22 11:41:38PER OUR SITE MEETING WALK-THRU ON SEPTEMBER 21, 2010, A
 CRITICAL ISSUE LIST WAS DEVELOPED TO ASSIST IN
 DETERMINING OUTSTANDING WORK. PLEASE REVIEW THE
 FOLLOWING CRITICAL ISSUES:
 ??? DETECTABLE WARNING TRUNCATED DOMES ARE REQUIRED AT
 TWO (2) LOCATIONS.
 O THE PEDESTRIAN ENTRANCE TO THE BUILDING INTERSECTING
 THE VEHICULAR DROP-OFF. (FLORIDA
 BUILDING CODE 2007, FLORIDA ACCESSIBILITY CODE
 11-4.29.5)
 O THE PUBLIC ACCESS SIDEWALK ADJACENT THE PARKING AREA
 MUST PROVIDE DETECTABLE
 WARNING AT ALL PEDESTRIAN / VEHICULAR INTERSECTS.
 (DEPARTMENT OF JUSTICE, ADA
 ACCESSIBILITY GUIDELINES -ADAAG, ACCESSIBLE
 RIGHTS-OF-WAY, CHAPTER 3, SUBSECTION
 3.2)
 ??? ONE (1) SEWER CLEAN-OUT, AS SHOWN ON AS-BUILT TO BE
 UNCOVERED.
 ??? CRACKED SIDEWALK.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-10-14 Cont ID  
Sent By   Date 2008-10-14 Time   Rev Time 0.00
Received By   Date 2008-10-14 Time   Sent To  
Notes
2008-10-14 11:15:27PASSED.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-07-16 Cont ID  
Sent By rchokshi Date 2008-07-16 Time 11:26 Rev Time 0.00
Received By rchokshi Date 2008-07-16 Time 11:21 Sent To  
Notes
2008-07-16 11:26:51***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 PLEASE NOTE THATNOI, SFWMD PERMIT ARE IN E-MAIL SENT
 BY JEFF HALVERSON, DATED 4/10/08 @3:33PM FOR FUTURE
 REFERENCE.
  
 1.STORM WATER QUALITY CALCULATIONS MUST BE APPROVED
 BY MR. JONATHAN BRAMLEY,DIRECTOR,45TH STREET
 ENGINEERING SERVICES BEFORE WE ISSUE A PERMIT.
  
 OUR RESPONSE: NEED AN APPROVAL 45TH ST.MOCK ROOS
 PROBABLY REVIEWS IT, I HAVE NOT RECEIVED AN APPROVAL
 LETTER FROM MOCK ROOS YET.
  
 2.WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G. OR EMERY F.), UTILITY DEPT BEFORE WE
 ISSUE A PERMIT.
  
 OUR RESPONSE:MANNY OR EMERY PUT A STAMP ON THE
 DRAWINGS. I HAVE NOT RECEIVED STAMPED DRAWING FROM
 MANNY OR EMERY,YET.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-04-11 Cont ID  
Sent By rchokshi Date 2008-04-11 Time 11:07 Rev Time 0.00
Received By rchokshi Date 2008-04-11 Time 11:03 Sent To  
Notes
2008-04-11 11:07:24***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 PLEASE NOTE THATNOI, SFWMD PERMIT ARE IN E-MAIL SENT
 BY JEFF HALVERSON, DATED 4/10/08 @3:33PM FOR FUTURE
 REFERENCE.
  
 1.STORM WATER QUALITY CALCULATIONS MUST BE APPROVED
 BY MR. JONATHAN BRAMLEY,DIRECTOR,45TH STREET
 ENGINEERING SERVICES BEFORE WE ISSUE A PERMIT.
  
 2.WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G. OR EMERY F.), UTILITY DEPT BEFORE WE
 ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By rchokshi Date 2007-10-22 Time 16:12 Rev Time 0.00
Received By rchokshi Date 2007-10-22 Time 16:03 Sent To  
Notes
2007-10-22 16:12:15***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FROM
 1000, 45 STREET FOR ALL THESE CITY STANDARDS NOTES.
 PHONE# 494-1040
 3. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4. PLEASE SHOW ON WATER QUALITY CALCULATTIONSTHAT YOU
 HAVE CONSIDERED FLOOD ZONE AREA, & 5,10, 25, 100 YEAR
 FLOOD CRITERIA & CROWN OF THE ROAD TO DETERMINE THE
 FIRST FLOOR ELEVATION & PARKINGLOT ELEVATION.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES.
 PLEASE SHOW DETAIL OF THE CONTROL STRUCTURESWITH
 ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON
 DRAWINGS, CALCULATION FOR EXFILTRATION TRENCHES, PLEASE
 SHOW DRY DETENTION/WET DETENTION AREAS IN STORM WATER
 CALS.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
 9.POLLUTION PREVENTION DETAILS:HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2009-12-02 Cont ID  
Sent By mawillia Date 2009-12-02 Time 15:34 Rev Time 0.00
Received By mawillia Date 2009-12-02 Time 15:01 Sent To  
Notes
2009-12-02 15:12:10*****REVISION APPROVED*****
  
 REVISED PLAN SHEETS LS-100, A-700, AND E-1 & E-2 (1501)
 WERE STAMPED, INITIALED, AND DATED.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2009-04-16 Cont ID  
Sent By mawillia Date 2009-04-16 Time 10:54 Rev Time 0.00
Received By mawillia Date 2009-04-16 Time 10:31 Sent To  
Notes
2009-04-16 10:53:06*****APPROVED*****
  
  
 THE FOLLOWING REVISED SHEETS: A-104, A-601, P-3, P-5,
 S-5.1, S-5.2, & S-5.3 WERE REVIEWED; HOWEVER
 FIRE-STAMPING NOT NECESSARY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-01-23 Cont ID  
Sent By mwennerg Date 2009-01-23 Time 15:21 Rev Time 0.00
Received By mwennerg Date 2009-01-23 Time 15:21 Sent To  
Notes
2009-01-23 15:25:09APPROVAL FOR UNDERGROUND FIRE LINE WATER DISTRIBUTION
 EQUIPMENT
  
  
 1) TITLE BLOCK WAS RED LINED TO INDICATE NUMERICAL
 ADDRESS OF THIS PROJECT.
 2) FIRE DEPARTMENT CONNECTION SHALL BE ROTATED TO FACE
 IN THE DIRECTION OF THE ACCESS ROAD.
 3) KNOX LOCKING CAPS REQUIRED FOR THE FIRE DEPARMENT
 CONNECTION. CONTACT THE BUREAU OF FIRE PREVENTION AT
 (561) 804-4724 FOR ASSISTANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-12-30 Cont ID  
Sent By mawillia Date 2008-12-29 Time 16:31 Rev Time 0.00
Received By mawillia Date 2008-12-29 Time 15:11 Sent To  
Notes
2008-12-29 15:35:02*****APPROVED*****
  
  
 ALL PREVIOUS COMMENTS HAVE BEEN ADDRESSED; PLAN SHEETS
 C6, C10, LS-1.0, A-201, A-700, E-2 & E-3 (1505), E-1 &
 E-2 (1501), AND FP-1 & FP-2 WERE STAMPED, INITIALED,
 AND DATED.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-12-02 Cont ID  
Sent By mawillia Date 2008-12-02 Time 11:54 Rev Time 0.00
Received By mawillia Date 2008-12-02 Time 11:19 Sent To  
Notes
2008-12-02 11:24:18*****DENIED*****
  
 THE FOLLOWING COMMENT TAKEN FROM THE PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED:
  
  
 00. THE ACTUAL PROJECT LOCATION SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET. AMEND/CORRECT
 A-103, A-200, A-300, A-400 THRU A-402, A-601, A-603,
 A-900, A-901, S-1.2, S-3.4 THRU S-4.2, E8 THRU E-10,
 P-3 & P-5, AND FP-1 & FP-2.
 (NOTE: SOME SHEETS FROM THE PREVIOUS REVIEW HAVE BEEN
 CORRECTED, THE LISTED HAVE NOT.)
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
 " 644-7326

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-10-16 Cont ID  
Sent By mawillia Date 2008-10-16 Time 12:53 Rev Time 0.00
Received By mawillia Date 2008-10-16 Time 12:15 Sent To  
Notes
2008-10-16 12:52:03*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED:
  
  
 00. THE ACTUAL PROJECT LOCATION SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET. AMEND/CORRECT
 A-103, A-200, A-300, A-400 THRU A-402, A-601, A-603,
 A-900, A-901, S-1.2 & S--2, S-3.3 THRU S-4.2, E-1, E4,
 E5, E8 THRU E-10, P-3 & P-5, AND FP-1 & FP-2.
  
 18. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE THE
 BUILDING(S) FIRE ALARM SYSTEM(S) TO ACTIVATE. COMMENT
 NOT ADDRESSED ON SHEET E-9 AS INDICATED IN YOUR
 RESPONSE
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-08-07 Cont ID  
Sent By mawillia Date 2008-08-07 Time 15:51 Rev Time 0.00
Received By mawillia Date 2008-08-07 Time 14:34 Sent To  
Notes
2008-08-07 15:18:18*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED:
  
  
 00. THE ACTUAL PROJECT LOCATION SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET. AMEND/CORRECT SHEET
 L-4.1 & L-4.2, L-5.1 THRU L-5.3, L-6.1, A-103, A-200,
 A-300, A-400 THRU A-402, A-601, A-603, A-900, A-901,
 S-1.2 & S--2, S-3.3 THRU S-4.2, M-1 THRU M-3, E-1 THRU
 E-10, P-1 THRU P-5, AND FP-1 & FP-2.
  
 03. UNDERGROUND UTILITIES ARE TO BE LOCATED PRIOR TO
 ANY EXCAVATING. COMMENT NOT ADDRESSED ON SHEET D-100 AS
 INDICATED IN YOUR RESPONSE
  
 18. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE THE
 BUILDING(S) FIRE ALARM SYSTEM(S) TO ACTIVATE. COMMENT
 NOT ADDRESSED ON SHEET E-9 AS INDICATED IN YOUR
 RESPONSE
  
 29. STAIRS TO COMPLY WITH THE FLORIDA BUILDING AND
 FLORIDA FIRE PREVENTION CODE. NOT ADDRESSED ON SHEET
 A-301 AS INDICATED IN YOUR RESPONSE
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-28 Cont ID  
Sent By mawillia Date 2008-05-28 Time 22:24 Rev Time 0.00
Received By mawillia Date 2008-05-28 Time 19:00 Sent To  
Notes
2008-05-29 00:50:26*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS REVIEW
 STILL NEED TO BE ADDRESSED:
  
 01.ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.ADD NFPA 241 TO APPLICABLE CODES
 ON SHEET G-100
  
 03.UNDERGROUND UTILITIES ARE TO BE LOCATED PRIOR TO
 ANY EXCAVATING.ADD COMMENT TO SHEET D-100
  
 08.PLEASE ILLUSTRATE ALL ACCESS POINTS TO THE
 EXISTING FACILITY THAT CAN BE USED BY FIRE RESCUE.
 ILLUSTRATE ON THE APPROPIATE PLAN SHEET
  
 09.BUILDING ADDRESS REQUIRED ON NEW STRUCTURE.A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS AND AT LEAST 1"
 WIDE SHALL BE PROVIDED.NUMBERS SHALL CONTRAST WITH
 THE BACKGROUND.SHOW THE ACTUAL ADDRESS NUMBERS ON THE
 APPROPIATE EXTERIOR ELEVATIONTHE PROJECT
 SITE ADDRESS (1505, NOT 1501) SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET
  
 10.A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING. SHOW
 THE LOCATION OF THE KNOX BOX ON THE APPROPIATE EXTERIOR
 ELEVATION.
  
 11.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE NEW
 FIRE DEPARTMENT CONNECTION.ADD COMMENT TO AN
 APPROPIATE PLAN SHEET
  
 17.NO FIRE SPRINKLER SYSTEM DRAWINGS PROVIDED WITH
 PLANS.SHOW A LAYOUT OF THE FIRE SPRINKLER HEADS
  
 18.DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE
 THE BUILDING(S) FIRE ALARM SYSTEM(S) TO ACTIVATE.ADD
 COMMENT TO THE APPROPIATE PLAN SHEET
  
 21.WHAT IS THE PROPOSED HEIGHT OF THE PORTACACHERE.
 SHOW 13' 8 1/2" ON THE APPROPIATE PLAN SHEET
  
 27.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS
 FOR ANY HANDRAILS OR GUARDRAILS.
  
 29.STAIRS TO COMPLY WITH THE FLORIDA BUILDING AND
 FLORIDA FIRE PREVENTION CODE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mcarsill Date 2007-10-22 Time 11:23 Rev Time 0.00
Received By mcarsill Date 2007-10-22 Time 10:28 Sent To  
Notes
2007-10-22 11:23:341. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 2. ALL DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 3. UNDERGROUND UTILITIES ARE TO BE LOCATED PRIOR TO ANY
 EXCAVATING.
  
 4. ON PAGE FOUR LABELED WATER DISTRIBUTION AND
 WASTEWATER PLANS ONLY ONE FIRE HYDRANT, FIRE HYDRANT #
 1 IS SHOWN. PLEASE DISPLAY ALL EXISTING AND NEW FIRE
 HYDRANTS FOR THE SITE.
  
 5. ALL FIRE LINE BAKFLOW DEVICES SHALL BE EQUIPPED WITH
 TAMPER SWITCHES, CHAINS AND LOCKS.
  
 6. ALL NEW FIRE HYDRANTS SHALL MEET UTILITY AND FIRE
 RESCUE STANDARDS.
  
 7. SUITABLE FIRE AND PARAMEDICAL ACCESS SHALL BE
 PROVIDED DURING CONSTRUCTION.
  
 8. PLEASE ILLUSTRATE ALL ACCESS POINTS TO THE EXISTING
 FACILITY THAT CAN BE USED BY FIRE RESCUE.
  
 9. BUILDING ADDRESS REQUIRED ON NEW STRUCTURE. A
 MINIMUM OF AT LEAST 6" HIGH NUMBERS AND AT LEAST 1"
 WIDE SHALL BE PROVIDED. NUMBERS SHALL CONTRAST WITH THE
 BACKGROUND.
  
 10. A KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.
  
 11. KNOX-BOX LOCKING CAPS SHALL BE PROVIDED FOR THE NEW
 FIRE DEPARTMENT CONNECTION.
  
 12. SEPERATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM INSTALLATION.
  
 13. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM EQUIPMENT INSTALLATION.
  
 14. FIRE SPRINKLER AND FIRE ALARM SYSTEM TO BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 15. PLEASE EXPLAIN SINGLE EXIT DOOR LEADING FROM THE
 MULTI-PURPOSE ROOM INTO THE PANTRY AREA.
  
 16. ARE ANY EMERGENCY LIGTHING FIXTURES PLANNED FOR THE
 RESTROOMS.
  
 17. NO FIRE SPRINKLER SYSTEM DRAWINGS PROVIDED WITH
 PLANS. PLANS AND CALCULATIONS ARE TO BE PROVIDED.
  
 18. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE THE
 BUILDING(S) FIRE ALARM SYSTEM(S) TO ACTIVATE.
  
 19. ARE ANY CARBON MONOXIDE DETECTORS PLANNED TO BE
 INSTALLED.
  
 20. NATURAL GAS INSTALLATION TO COMPLY WITH NFPA CODES
 AND ALL OTHER APPLICABLE CODES AND STANDARDS.
  
 21. WHAT IS THE PROPOSED HEIGHT OF THE PORTACACHERE.
  
 22. LIFE SAFETY SHEET PAGE A-800 IS BLANK.
  
 23. DOOR SCHEDULE ON PAGE A-700 DECLARES NO RATED FIRE
 DOORS PLANNED FOR THE SITE.
  
 24. PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE REQUIRED
 ON ALL DOORS SUBJECT TO AN OCCUPANCY LOAD OF 100 OR
 MORE PERSONS.
  
 25. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 26. PLEASE DECLARE CONSTRUCTION OF TRELLIS.
  
 27. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ANY HANDRAILS OR GUARDRAILS.
  
 29. STAIRS ARE TO COMPLY WITH THE FLORIDA BUILDING AND
 FLORIDA FIRE PREVENTION CODE.
  
 30. ALL EXTERIOR STAIRS USED FOR EXIT DISCHARGE SHALL
 BE SLIP RESISTANT.
  
 31. PLEASE DECLARE LOCATIONS OF ALL FIRE EXTINGUISHERS
 AND THE TYPES BEING PROPOSED.
  
 32. PLEASE PROVIDE DETAILS ON FLAME SPREAD FOR THE
 DIVISING WALLS AND ANY HARDWARE ATTACHED TO THIS
 DEVICE.
  
 33. PLEASE EXPLAIN PURPOSE OF CLASSROOM. WHAT AGES ARE
 PLANNED.
  
 34. OCCUPANT LOAD TO BE DETERMINED BY THE BUREAU OF
 FIRE PREVENTION.
  
 35. TABLES AND CHAIRS APPEAR TO BE TIGHT IN SOME
 LOCALES IN THE MULTI-PURPOSE ROOM.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2008-11-19 Cont ID  
Sent By kstevens Date 2008-11-19 Time 13:04 Rev Time 0.00
Received By kstevens Date 2008-11-19 Time 13:04 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2008-10-08 Cont ID  
Sent By kstevens Date 2008-10-08 Time 15:01 Rev Time 0.00
Received By kstevens Date 2008-10-01 Time 17:36 Sent To  
Notes
2008-10-08 15:02:37DENIED
 REFERENCE: FBC-2004 FUEL GAS CODE
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 ********FROM PREVIOUS REVIEWS:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
 ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE
 THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE
 GAS PERMIT.
 ******RESPONSE NOTED, SHEETS NOT SUBMITTED.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. OK
 2B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-07-22 Cont ID  
Sent By kstevens Date 2008-07-22 Time 10:52 Rev Time 0.00
Received By kstevens Date 2008-07-22 Time 10:52 Sent To  
Notes
2008-07-22 10:54:53DENIED
 REFERENCE: FBC-2004 FUEL GAS CODE
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
 ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE
 THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE
 GAS PERMIT.
 ******RESPONSE NOTED, SHEETS NOT SUBMITTED.
  
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. OK
 2B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-05-10 Cont ID  
Sent By kstevens Date 2008-05-10 Time 13:13 Rev Time 0.00
Received By kstevens Date 2008-05-10 Time 13:13 Sent To  
Notes
2008-05-10 13:14:02DENIED
 REFERENCE: FBC-2004 FUEL GAS CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE LENGTHS OF THE CUT SECTIONS
 ARE NOT SHOWN ON THE RISER DIAGRAM.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN
 COMMENT "A" IS ADDRESSED.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
 ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE
 THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE
 GAS PERMIT.
  
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE "ETR"
 & WITHIN 6' OF THE GENERATOR PER SECTION 409.5. PLEASE
 INDICATED ON THE GAS RISER DIAGRAM.
  
 2B. PER TABLE 402.4(2), 2-1/2" PIPE IS REQUIRED FOR THE
 GAS LINE TO THE GENERATOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-27 Cont ID  
Sent By kstevens Date 2007-10-27 Time 13:11 Rev Time 0.00
Received By kstevens Date 2007-10-27 Time 13:10 Sent To  
Notes
2008-05-10 13:13:06DENIED
 REFERENCE: FBC-2004 FUEL GAS CODE
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
  
 27. PLANS DO NOT APPEAR TO BE 100% COMPLETE AND MORE
 COMMENTS MAY BE FORTHCOMING ACCORDING TO COMMENT
 RESPONSES AND NEW INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2009-11-09 Cont ID  
Sent By jgomez Date 2009-11-09 Time 09:37 Rev Time 0.00
Received By jgomez Date 2009-11-09 Time 09:34 Sent To  
Notes
2009-11-09 09:42:53SENT TO BOX #C22.

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date   Cont ID  
Sent By   Date 2009-10-22 Time   Rev Time 0.00
Received By   Date 2009-10-22 Time   Sent To B
Notes
2009-10-22 16:48:49ROUTED TO J WITMER'S DESK PER R BROWN

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2009-10-05 Cont ID  
Sent By dpalmer Date 2009-10-05 Time 10:35 Rev Time 0.00
Received By dpalmer Date 2009-10-05 Time 10:35 Sent To B
Notes
2009-10-05 10:35:25TO JW'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2009-09-16 Cont ID  
Sent By kstevens Date 2009-09-16 Time 08:32 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 08:32 Sent To  
Notes
2009-09-16 08:35:15SENT TO C-34.

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2009-08-19 Cont ID  
Sent By lmartine Date 2009-08-19 Time 14:48 Rev Time 0.00
Received By lmartine Date 2009-08-19 Time 14:48 Sent To  
Notes
2009-08-19 14:53:44ALSO, WALL PENETRATION,AND ENERGY CALC'S, REVISION
2009-08-19 14:51:47ALSO, ROOF SOFFIT DETAIL REVISION
2009-08-19 14:50:25GAVE TO JIM, SEMCO STRUCT REVISION

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2009-08-17 Cont ID  
Sent By dpalmer Date 2009-08-17 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2009-08-17 Time 16:03 Sent To E
Notes
2009-08-17 16:03:47ELEC AND MECH REV ROUTED TO DVP'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2009-07-28 Cont ID  
Sent By rbrown Date 2009-07-28 Time 13:07 Rev Time 0.00
Received By rbrown Date 2009-07-28 Time 13:07 Sent To  
Notes
2009-07-28 13:08:32FIRE SPRINKLER SHOP DRAWINGS AND HYDRAULIC DESIGN INFO
 ROUTED TO MIKE WILLIAMS.

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2009-07-01 Cont ID  
Sent By rmcdouga Date 2009-07-01 Time 11:12 Rev Time 0.00
Received By rmcdouga Date 2009-07-01 Time 11:12 Sent To  
Notes
2009-07-01 11:14:29EXPEDITED REVISIONS FOR BUILDING, PLUMBING AND
 LANDSCAPE / TO COMM BD # C38

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-06-16 Cont ID  
Sent By lmartine Date 2009-06-16 Time 15:53 Rev Time 0.00
Received By lmartine Date 2009-06-15 Time 15:53 Sent To  
Notes
2009-06-16 15:54:42ELECTRICAL RISER FOR LIFT STATION, GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-06-16 Cont ID  
Sent By lmartine Date 2009-06-16 Time 15:46 Rev Time 0.00
Received By lmartine Date 2009-06-15 Time 15:45 Sent To  
Notes
2009-06-16 15:47:32RESPONCES TO RFI'S # 70-74, GAVE TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-06-16 Cont ID  
Sent By lmartine Date 2009-06-15 Time 15:37 Rev Time 0.00
Received By lmartine Date 2009-06-15 Time 15:37 Sent To  
Notes
2009-06-16 15:39:13ENTRANCE CANOPY REVISION
2009-06-16 15:38:03GAVE TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-05-05 Cont ID  
Sent By dpalmer Date 2009-05-05 Time 16:13 Rev Time 0.00
Received By dpalmer Date 2009-05-05 Time 16:13 Sent To B
Notes
2009-05-05 16:13:43TO JW

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-04-20 Cont ID  
Sent By swurafti Date 2009-04-20 Time 16:37 Rev Time 0.00
Received By swurafti Date 2009-04-20 Time 16:37 Sent To B
Notes
2009-04-20 16:39:04TO "JWITMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-04-08 Cont ID  
Sent By adarroug Date 2009-04-08 Time 11:17 Rev Time 0.00
Received By adarroug Date 2009-04-08 Time 11:17 Sent To B
Notes
2009-04-08 11:18:16TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-04-03 Cont ID  
Sent By adarroug Date 2009-04-03 Time 08:12 Rev Time 0.00
Received By adarroug Date 2009-04-03 Time 08:12 Sent To M
Notes
2009-04-03 08:17:59TO RREGUEIRO DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-03-30 Cont ID  
Sent By adarroug Date 2009-03-30 Time 12:12 Rev Time 0.00
Received By adarroug Date 2009-03-30 Time 12:12 Sent To  
Notes
2009-03-30 12:13:13TO "C30"

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-12-10 Cont ID  
Sent By adarroug Date 2008-12-10 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-12-10 Time 15:28 Sent To  
Notes
2008-12-10 15:54:48TO "COMM" BD#47--6 ROLLS AND PAPERWORK--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 10:00 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 10:00 Sent To  
Notes
2008-11-18 10:05:19TO "COMM" BD#8-PLANS ON RACK-6
 ROLLS/PAPERWORK--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-09-30 Cont ID  
Sent By adarroug Date 2008-09-30 Time 15:48 Rev Time 0.00
Received By adarroug Date 2008-09-30 Time 15:48 Sent To  
Notes
2008-09-30 15:55:01TO "COMM" BD#30--PLANS ON RACK/6 ROLLS AND
 PAPERWORK--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-01 Cont ID  
Sent By adarroug Date 2008-07-01 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-07-01 Time 10:51 Sent To  
Notes
2008-07-01 10:52:06TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 09:06 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 09:06 Sent To  
Notes
2008-04-08 09:09:40TO "COMM" BD#38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 08:56 Rev Time 0.00
Received By adarroug Date 2007-10-01 Time 16:26 Sent To  
Notes
2007-10-21 14:41:46TO COMM BOARD SPACE #1
2007-10-01 16:26:37WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 6 Status P Date 2009-07-06 Cont ID  
Sent By rkussner Date 2009-07-06 Time 16:24 Rev Time 0.00
Received By rkussner Date 2009-07-06 Time 16:24 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 5 Status P Date 2008-12-18 Cont ID  
Sent By rkussner Date 2008-12-18 Time 15:54 Rev Time 0.00
Received By rkussner Date 2008-12-18 Time 15:54 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 4 Status F Date 2008-11-24 Cont ID  
Sent By adavila Date 2008-11-24 Time 08:49 Rev Time 0.00
Received By adavila Date 2008-11-24 Time 08:49 Sent To  
Notes
2008-11-24 08:56:35***FAILED FOR PLAN REVIEW. PLANS WITH LAST REVISION
 DATE NOV. 4, 2008, AND SIGNED AND SEALED ON NOV. 11,
 2008 ARE OKAY***
  
 PER ROBERT KUSSNER, LANDSCAPE PLANNER.

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2008-10-16 Cont ID  
Sent By rkussner Date 2008-10-16 Time 16:04 Rev Time 0.00
Received By rkussner Date 2008-10-16 Time 16:04 Sent To  
Notes
2008-10-16 16:32:18***LANDSCAPE REVIEW FAILED***
  
 1. THERE ARE CONFLICTS BETWEEN PROPOSED UTILITIES AND
 LANDSCAPING. DRAINAGE LINES AND OTHER UTILITIES SHALL
 BE KEPT OUT OF THE LANDSCAPE ISLANDS. NOT ALL OF THE
 NEWLY PROPOSED STREET LIGHTS ARE SHOWN ON THE LANDSCAPE
 PLAN AND SEVERAL OF THEM WILL BE IN CONFLICT WITH
 PROPOSED TREES.
  
 2. STAFF RECOMMENDS THAT THE PROPOSED YELLOW TABEBUIA
 TREES BE CHANGED TO PINK TABEBUIA OR ANOTHER SPECIES.
 YELLOW TABEBUIA TREES HAVE WEAK ROOT SYSTEMS AND ARE
 SUBJECT TO FALLING OVER IN HIGH WINDS.
  
 3. PURSUANT TO SECTION 94-443(C)(3)(A), LANDSCAPE
 ISLANDS SHALL HAVE A MINIMUM RADIUS OF 2 1/2 FEET AT
 ITS END SO AS TO ALLOW CAR MANEUVERING.
  
  
 FOR ANY QUESTIONS REGARDING THESE COMMENTS, PLEASE
 CONTACT ROBERT KUSSNER @ (561) 822-1462.
  
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2008-07-24 Cont ID  
Sent By rkussner Date 2008-07-24 Time 09:40 Rev Time 0.00
Received By rkussner Date 2008-07-24 Time 09:34 Sent To  
Notes
2008-07-24 09:36:41PLEASE SEE ZONING COMMENTS DATED 7/11/08.
 PLEASE CONTACT ROBERT KUSSNER @ (561) 822-1462 IF YOU
 HAVE ANY QUESTIONS REGARDING THE LANDSCAPING.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-04-14 Cont ID  
Sent By rkussner Date 2008-04-14 Time 14:33 Rev Time 0.00
Received By rkussner Date 2008-04-14 Time 14:33 Sent To  
Notes
2008-04-14 14:51:21PLANNING AND ZONING
 LANDSCAPE COMMENTS
  
 FAILED****CONTACT ROBERT KUSSNER @ 822-1462,
  
 1,THE SYMBOLS 'PSN' AND 'CAB' WERE SHOWN ON THE PLAN
 BUT WERE NOT ON THE PLANT LIST.
  
 2.THERE ARE ATE LEAST TWO (2) MAHOGANY TREES FOUND
 ON SITE THAT WERE SEVERELY STORM DAMAGED.PLEASE
 CAREFULLY EXAMINE ALL TREES SCHEDULED TO REMAIN IN
 PLACE OR BE RELOCATED AND REMOVE THOSE TREES THAT ARE
 NOT IN GOOD CONDITION.
  
 3.PURSUANT TO SECTION 94-443(C)(5)(A), LANDSCAPE
 AREAS SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NON-MOUNTABLE, CONCRETE CURBING OF THE TYPE
 CHARACTERIZED AS "TYPE D".THE CURBING MUST BE ADDED
 THROUGHOUT THE PARKING LOT ASSOCIATED WITH THIS
 MODIFICATION AND NOT JUST WHERE ASPHALT WORK IS BEING
 DONE.
  
 4.ELIMINATE ALL CONFLICTS BETWEEN PROPOSED STREET
 LIGHTS AND TREES.ALSO, SHOW ALL UTILITIES AND
 EASEMENTS ON THE LANDSCAPE PLAN TO AVOID ANY OTHER
 CONFLICTS WITH LANDSCAPING.

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2010-08-16 Cont ID  
Sent By hmoser Date 2010-08-16 Time 11:02 Rev Time 0.00
Received By hmoser Date 2010-08-16 Time 11:01 Sent To  
Notes
2010-08-16 11:03:53TEST AND BALANCE REPORT IS OK 8/19/10

Review Stop M MECHANICAL (A/C)
Rev No 12 Status F Date 2009-12-01 Cont ID  
Sent By rregueir Date 2009-12-01 Time 16:46 Rev Time 0.00
Received By rregueir Date 2009-12-01 Time 15:38 Sent To  
Notes
2009-12-01 16:46:11REVIEW #: REVISION
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE VENTILATION CALCULATIONS WITH SPACE-BY-SPACE
 REQUIREMENTS FOR OCCUPANCY CLASSIFICATION, OCCUPANT
 LOAD AND VENTILATION RATES TO BE PROVIDED IN ACCORDANCE
 WITH FBC-M SECTION 403.
  
 2. PLANS AND NOTE #5 ON PAGE M-1 INDICATE NEW AHUS TO
 BE INSTALLED AND CONNECTED TO EXISTING CONDENSING
 UNITS. PROVIDE SUPPORTING DOCUMENTATION SHOWING THESE
 TO BE MATCHED SYSTEMS IN ACCORDANCE WITH FBC-B
 13-101.6.
  
 3. PROVIDE ATTACHMENT DETAIL ALONG WITH MANUFACTURER'S
 DATA FOR WIND RESISTANT INSTALLATION OF OUTDOOR
 CONDENSING UNITS IN ACCORDANCE WITH FBC-M 301.13.
  
 4. SYSTEM SIZING SUMMARIES WERE SUBMITTED FOR NEW
 SYSTEMS IN LIEU OF FULL COOLING LOAD CLACULATIONS.
 SYSTEM SIZING SUMMARIES SHALL BE SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER IN ACCORDANCE WITH FBC-B
 13-407.AB.1.
  
 5. AHU 4 SHALL BE PROVIDED WITH DUCT SMOKE DETECTOR IN
 ACCORDANCE WITH FBC-M 606.2.1.
  
 6. THE SCOPE OF WORK RELATED TO THIS REVISION
 REPRESENTS A SIGNIFICANT EXPANSION FROM THE SCOPE
 COVERED BY THE PERMIT AT TIME OF ISSUANCE. THE
 VALUATION OF WORK SHALL BE ADJUSTED TO REFLECT AND
 INCLUDE THE VALUE OF THE EXPANDED SCOPE.
  
 NOTE: SEPARATE PLANS AND PERMIT APPLICATION SHALL BE
 SUBMITTED FOR KITCHEN EXHAUST AND VENTILATION SYSTEM.
 THE KITCHEN EXHAUST/VENTILATION SYSTEMS ARE NOT PART OF
 THIS REVIEW AND HAVE NOT BEEN EVALUATED FOR CODE
 COMPLIANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2009-11-24 Cont ID  
Sent By rregueir Date 2009-11-24 Time 08:04 Rev Time 0.00
Received By rregueir Date 2009-11-24 Time 08:03 Sent To  
Notes
2009-11-24 08:04:28REVISED M-1 DELTA 5, REVISED SUBMITTAL #17A DATED
 10/12/09

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2009-08-31 Cont ID  
Sent By rregueir Date 2009-08-31 Time 09:11 Rev Time 0.00
Received By rregueir Date 2009-08-31 Time 09:11 Sent To B
Notes
2009-08-31 09:11:31NEW E-CALCS FOR REDUCED ROOF R-VALUE

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2009-08-24 Cont ID  
Sent By rregueir Date 2009-08-24 Time 09:47 Rev Time 0.00
Received By rregueir Date 2009-08-24 Time 09:47 Sent To  
Notes
2009-08-24 09:48:13REVISED M-1 DELTA 4, REVISED M-2 DELTA 6

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2009-04-09 Cont ID  
Sent By hmoser Date 2009-04-09 Time 09:33 Rev Time 0.00
Received By hmoser Date 2009-04-09 Time 09:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2009-01-06 Cont ID  
Sent By rregueir Date 2009-01-06 Time 14:31 Rev Time 0.00
Received By rregueir Date 2009-01-06 Time 14:30 Sent To  
Notes
2009-01-06 14:30:54***********PROVISO************
  
 PROVIDE MANUFACTURER'S SUBMITTAL OR OTHER SUPPORTING
 DATA SHOWING THE OUTDOOR APPLIANCES WHICH ARE EXPOSED
 TO WIND ARE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBCM 301.13. THIS INFORMATION SHALL BE
 PROVIDED FOR REVIEW PRIOR TO INSTALLATION AND
 INSPECTION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-12-20 Cont ID  
Sent By rregueir Date 2008-12-20 Time 09:33 Rev Time 0.00
Received By rregueir Date 2008-12-20 Time 09:04 Sent To  
Notes
2008-12-20 09:17:38REVIEW #: 6TH
 ACTION: PASSED W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 BASED ON THE BUILDING PLAN REVIEW, THE ENERGY
 CALCULATIONS ARE BEING CORRECTED AND RESUBMITTED.
 MECHANICAL REVIEW WILL BE IN TEMPORARY FAIL STATUS
 PENDING RECEIPT OF THE CORRECTED ENERGY CALCULATIONS.
 ONCE ENERGY CALCULATIONS ARE RECEIVED, REVIEWED AND
 PASSED, THE MECHANICAL REVIEW STATUS WILL BE CHANGED TO
 PASS STATUS WITH THE FOLLOWING PROVISO:
  
 ***********PROVISO************
  
 PROVIDE MANUFACTURER'S SUBMITTAL OR OTHER SUPPORTING
 DATA SHOWING THE OUTDOOR APPLIANCES WHICH ARE EXPOSED
 TO WIND ARE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBCM 301.13. THIS INFORMATION SHALL BE
 PROVIDED FOR REVIEW PRIOR TO INSTALLATION AND
 INSPECTION OF OUTDOOR APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
 NOTE: DESIGNER'S WRITTEN RESPONSES DATED 12/4/08
 INDICATE THAT ONE OF THE MECHANICAL REVIEW COMMENTS
 [COMMENT 2(D) DATED 11/24/08] WAS "BASED ON THE PLAN
 REVIEWER VALUE ENGINEERING THE PLANS." THIS RESPONSE IS
 NEITHER HELPFUL NOR ACCURATE. IN A PREVIOUS REVIEW IT
 WAS ASKED FOR PURPOSES OF CLARIFICATION WHETHER ALL
 FIRE DAMPERS WERE INTENDED TO BE FIRE/SMOKE DAMPERS, OR
 IF THERE WOULD BE STANDARD FIRE DAMPERS WHERE THE
 COMBINATION DAMPERS WERE NOT REQUIRED BY CODE. THE
 RESPONSE FROM STEVE HOCKMAN WAS THAT THE PLANS WOULD BE
 CHANGED TO REFLECT FIRE/SMOKE DAMPERS ONLY IN LOCATIONS
 REQUIRED BY CODE. WHEN THE PLANS WERE RESUBMITTED AND
 THIS CHANGE WAS NOT MADE, DESPITE A WRITTEN RESPONSE
 INDICATING THAT THE CHANGE WAS MADE, COMMENT 2(D)
 REQUESTED CLARIFICATION AGAIN. THIS WAS NOT AN ATTEMPT
 AT "VALUE ENGINEERING" AND AT NO TIME DID ANY REVIEW
 COMMENTS INSTRUCT ANYONE TO CHANGE FIRE/SMOKE DAMPERS
 TO FIRE DAMPERS TO SAVE MONEY.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-11-24 Cont ID  
Sent By rregueir Date 2008-11-24 Time 18:43 Rev Time 0.00
Received By rregueir Date 2008-11-24 Time 17:47 Sent To  
Notes
2008-11-24 18:43:10REVIEW #: 5TH
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2 AND 12: COMMENT #2 AND #12 ARE BEING COMBINED IN THIS
 REVIEW AS THEY DEAL WITH THE SAME SUBJECT. THERE
 CONTINUES TO BE COORDINATION PROBLEMS BETWEEN
 ARCHITECTURAL, LIFE SAFETY AND MECHANICAL PLANS RELATED
 TO WALL TYPES, RATINGS AND DUCT PENETRATIONS OF WALLS:
  
 A) **THIS COMMENT NOT ADDRESSED** THE LOCATION OF RATED
 WALL ASSEMBLIES ON LS-1.0 AND A-102 DO NOT CORRESPOND.
 EXAMPLE: THE WALLS ON THE EAST AND WEST SIDE OF
 CLASSROOM 160 ARE SHOWN TO BE 1-HOUR RATED (WALL TAG
 1A) ON PAGE A-102 BUT NO RATING IS SHOWN OB PAGE LS
 1.0. THERE ARE MULTIPLE DUCT PENETRATIONS OF THESE
 WALLS SHOWN ON PAGE M-2 WITH NO PROTECTION. IT WILL NOT
 BE CLEAR ON PLANS IF ALL DUCT PENETRATIONS WHICH
 REQUIRE PROTECTION ARE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5 UNTIL ALL PLANS ARE COORDINATED.
  
 B) **PARTIALLY ADDRESSED** THE 30X14 SUPPLY DUCT FROM
 AHU-3 IS PENETRATING A 1-HOUR CORRIDOR WALL AS IT
 ENTERS CLASSROOM 160 WITH NO PROTECTION OF THIS
 PENETRATION SHOWN ON FLOOR PLAN. SHOW HOW THIS OPENING
 IS TO BE PROTECTED IN ACCORDANCE WITH FBCM 607.5.
 **PLEASE ADDRESS: THERE IS STILL NO INDICATION ONPLANS
 WHETHER THIS IS A FIRE DAMPER OR A FIRE/SMOKE DAMPER. A
 FIRE/SMOKE DAMPER IS REQUIRED AT THIS LOCATION IN
 ACCORDANCE WITH FBCM 607.5 AND 607.5.4.
  
 C) OK
  
 D) **THIS COMMENT NOT ADDRESSED** MECHANICAL
 SPECIFICATIONS NOTE #10 ON PAGE M-1 INDICATES ALL FIRE
 DAMPERS ARE TO BE CORRIDOR COMBINATION FIRE/SMOKE
 DAMPERS. FLOOR PLAN ONLY HAS ONE SYMBOL USED FOR FIRE
 DAMPERS AT ALL LOCATIONS. IS THE DESIGN INTENT THAT ALL
 FIRE DAMPERS REGARDLESS OF LOCATION BE COMBINATION
 FIRE/SMOKE DAMPERS? NOT ALL FIRE DAMPERS ON PLANS ARE
 LOCATED AT A CORRIDOR WALL PENETRATION AND THERE IS NO
 MEANS ON PLANS TO DIFFERENTIATE BETWEEN CORRIDOR TYPE
 COMBINATION DAMPERS AND STANDARD FIRE DAMPERS. PLEASE
 CLARIFY, SHOWING COMPLIANCE WITH FBCM 607.5.3 AND
 607.5.4.
  
 3 THROUGH 7: OK
  
 8. OK
  
 9. **THIS COMMENT NOT ADDRESSED** NEW COOLING LOAD
 CALCULATIONS HAVE STILL NOT BEEN PROVIDED WITH ENERGY
 CALCULATIONS AS REQUIRED BY FBCB 13-407.1.ABC.1.
 **PLEASE ADDRESS: ONE SYSTEM SIZING SUMMARY SET WAS
 SUBMITTED WITH ORIGINAL SEAL AND SIGNATURE. THE OTHER
 TWO SETS HAVE PHOTOCOPIED SIGNATURES AND NO SEALS.
 PLEASE ATTACH A SIGNED AND SEALED SYSTEM SIZING SUMMARY
 SET TO EACH SET OF ENERGY CALCULATIONS SUBMITTED IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1 AND FBCB 106.1.
  
 10. OK
  
 11. **PARTIALLY ADDRESSED** THIS COMMENT HAS NOT BEEN
 ADDRESSED. THERE IS NO INSTALLATION ATTACHMENT DETAIL
 FOR WIND RESISTANCE FOR THE OUTDOOR INSTALLED ERV AND
 NO INFORMATION ON THE CONSTRUCTION OF THE ERV SHOWING
 IT IS DESIGNED TO RESIST WIND PRESSURES IN ACCORDANCE
 WITH FBCM 301.13.
 **PLEASE ADDRESS: ATTACHMENT INFORMATION ON PLANS OK.
 HOWEVER, NO INFORMATION WAS PROVIDED REGARDING WIND
 RESISTANCE OF THE ERV ITSELF. APPLIANCES EXPOSED TO
 WIND SHALL BE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBCM 301.13.
  
 12. SEE COMMENT #2 ABOVE.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED AS
 WELL AS WHERE THE PROVIDED INFORMATION CAN BE FOUND.
 THIS WILL ASSIST IN PROVIDING A TIMELY REVIEW WITH AS
 FEW DELAYS AS POSSIBLE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-10-11 Cont ID  
Sent By rregueir Date 2008-10-11 Time 13:58 Rev Time 0.00
Received By rregueir Date 2008-10-11 Time 13:46 Sent To  
Notes
2008-10-11 13:58:13REVIEW #: 4TH
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY.
 NO WRITTEN RESPONSE TO PREVIOUS MECHANICAL REVIEW
 COMMENTS WERE PROVIDED. WHILE THIS IS NOT A CODE
 REQUIREMENT, IT DOES ASSIST THE REVIEWER IN
 UNDERSTANDING HOW THE COMMENTS HAVE BEEN ADDRESSED,
 SAVES UNNECCESARY REVIEW TIME AND AVOIDS DELAYS.
  
 1. OK
  
 2 AND 12: COMMENT #2 AND #12 ARE BEING COMBINED IN THIS
 REVIEW AS THEY DEAL WITH THE SAME SUBJECT. THERE
 CONTINUES TO BE COORDINATION PROBLEMS BETWEEN
 ARCHITECTURAL, LIFE SAFETY AND MECHANICAL PLANS RELATED
 TO WALL TYPES, RATINGS AND DUCT PENETRATIONS OF WALLS:
  
 A) THE LOCATION OF RATED WALL ASSEMBLIES ON LS-1.0 AND
 A-102 DO NOT CORRESPOND. EXAMPLE: THE WALLS ON THE EAST
 AND WEST SIDE OF CLASSROOM 160 ARE SHOWN TO BE 1-HOUR
 RATED (WALL TAG 1A) ON PAGE A-102 BUT NO RATING IS
 SHOWN OB PAGE LS 1.0. THERE ARE MULTIPLE DUCT
 PENETRATIONS OF THESE WALLS SHOWN ON PAGE M-2 WITH NO
 PROTECTION. IT WILL NOT BE CLEAR ON PLANS IF ALL DUCT
 PENETRATIONS WHICH REQUIRE PROTECTION ARE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5 UNTIL ALL PLANS ARE
 COORDINATED.
  
 B) THE 30X14 SUPPLY DUCT FROM AHU-3 IS PENETRATING A
 1-HOUR CORRIDOR WALL AS IT ENTERS CLASSROOM 160 WITH NO
 PROTECTION OF THIS PENETRATION SHOWN ON FLOOR PLAN.
 SHOW HOW THIS OPENING IS TO BE PROTECTED IN ACCORDANCE
 WITH FBCM 607.5.
  
 C) THE 14X10 SUPPLY DUCT BRANCH COMING FROM AHU-3 IS
 SHOWN ON FLOOR PLAN WITH A FIRE DAMPER WHERE THERE IS
 NO WALL ASSEMBLY. FIRE DAMPERS SHALL BE INSTALLED AT
 RATED WALL ASSEMBLIES IN ACCORDANCE WITH FBCM 607.2.
  
 D) MECHANICAL SPECIFICATIONS NOTE #10 ON PAGE M-1
 INDICATES ALL FIRE DAMPERS ARE TO BE CORRIDOR
 COMBINATION FIRE/SMOKE DAMPERS. FLOOR PLAN ONLY HAS ONE
 SYMBOL USED FOR FIRE DAMPERS AT ALL LOCATIONS. IS THE
 DESIGN INTENT THAT ALL FIRE DAMPERS REGARDLESS OF
 LOCATION BE COMBINATION FIRE/SMOKE DAMPERS? NOT ALL
 FIRE DAMPERS ON PLANS ARE LOCATED AT A CORRIDOR WALL
 PENETRATION AND THERE IS NO MEANS ON PLANS TO
 DIFFERENTIATE BETWEEN CORRIDOR TYPE COMBINATION DAMPERS
 AND STANDARD FIRE DAMPERS. PLEASE CLARIFY, SHOWING
 COMPLIANCE WITH FBCM 607.5.3 AND 607.5.4.
  
 3 THROUGH 7: OK
  
 8. NOTE 13 ON PAGE M-2 HAS BEEN MODIFIED TO SHOW TWO
 LINE SETS PER CONDENSING UNIT FOR AHU-1 AND AHU-2. DOES
 THIS MEAN THERE ARE TWO CONDENSING UNITS PER AHU? THERE
 IS ONLY ONE CONDENSING UNIT PER AHU SHOWN ON PLANS.
 PLEASE CLARIFY PER FBCM 304.1 AND FBCB 106.1.1.
  
 9. NEW COOLING LOAD CALCULATIONS HAVE STILL NOT BEEN
 PROVIDED WITH ENERGY CALCULATIONS AS REQUIRED BY FBCB
 13-407.1.ABC.1. ALSO, PLEASE SEE BUILDING PLAN REVIEW
 COMMENTS RELATED TO DISCREPANCIES BETWEEN BUILDING
 PLANS AND SQUARE FOOTAGE SHOWN ON ENERGY CALCULATIONS.
 PLANS AND CALCULATIONS SHALL CORRESPOND IN ACCORDANCE
 WITH FBCB 13-103.2.
  
 10. OK
  
 11. THIS COMMENT HAS NOT BEEN ADDRESSED. THERE IS NO
 INSTALLATION ATTACHMENT DETAIL FOR WIND RESISTANCE FOR
 THE OUTDOOR INSTALLED ERV AND NO INFORMATION ON THE
 CONSTRUCTION OF THE ERV SHOWING IT IS DESIGNED TO
 RESIST WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 12. SEE COMMENT #2 ABOVE.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED AS
 WELL AS WHERE THE PROVIDED INFORMATION CAN BE FOUND.
 THIS WILL ASSIST IN PROVIDING A TIMELY REVIEW WITH AS
 FEW DELAYS AS POSSIBLE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-07-17 Cont ID  
Sent By rregueir Date 2008-07-17 Time 16:56 Rev Time 0.00
Received By rregueir Date 2008-07-16 Time 16:35 Sent To  
Notes
2008-07-17 16:56:51REVIEW #: 3RD. **PLAN REVIEW**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. SOME OF THE COMBINATION FIRE/SMOKE DAMPERS WHICH
 HAVE BEEN ADDED TO THE CORRIDOR WALLS AT HALLWAY 152
 ARE NOT SHOWN AT THE LOCATION OF THE RATED WALL
 ASSEMBLIES AS SHOWN ON PAGE LS-1.0. SOME ARE SHOWN AT A
 SOFFIT RATHER THAN BEING SET-BACK IN THE ALCOVE WHERE
 THE RATED WALL ASSEMBLY IS LOCATED. ALSO, HALL 165 IS
 SHOWN ON LS-1.0 AS BEING ON THE CORRIDOR SIDE OF THE
 RATED WALL ASSEMBLY. THE RESULT IS THERE ARE NO DAMPERS
 SHOWN ON PAGE M-2 WHERE THE DUCTS ACTUALLY PENETRATE
 THE RATED WALLS. PLEASE COORDINATE MECHANICAL PLANS
 WITH ARCHITECTURAL AND LIFE SAFETY PLANS TO SHOW DUCT
 PENETRATIONS LOCATED AT THE ACTUAL WALL ASSEMBLIES IN
 ACCORDANCE WITH FBCM 607.5.
  
 3 THROUGH 5: OK
  
 6. IS THIS DESIGN WITH TEK (SHEET METAL) SCREWS INTO
 WOOD AND ONLY ATTACHING TO CORRUGATED DECKING INTENDED
 AND DESIGNED FOR WIND RESISTANCE? PLEASE CLARIFY AND
 COORDINATE WITH STRUCTURAL DRAWINGS. ALSO, NO
 INFORMATION WAS PROVIDED REGARDING THE WIND RESISTANCE
 OF THE GREENHECK ROOF CAP. SHOW COMPLIANCE WITH FBCM
 301.13 AS STATED IN PREVIOUS REVIEW COMMENT #6.
  
 7. OK PENDING BUILDING REVIEW.
  
 8. OK
  
 9A. OK
  
 9B. OK
  
 9C. THE IDR HAS BEEN CORRECTED FOR MECHANICAL ITEMS.
 HOWEVER, COOLING LOAD CALCULATION HAVE NOT BEEN
 ATTACHED TO THE ENERGY CALCULATIONS AS REQUIRED BY FBCB
 13-407.1.ABC.1.
 NOTE: SOME VALUES OF THE OLD COOLING LOAD CALCULATIONS
 MAY HAVE CHANGED SINCE THE ADDITION OF THE ERV AND
 NEWLY CALCULATED VENTILATION RATES. PLEASE UPDATE
 COOLING LOAD CALCULATIONS TO REFLECT THESE NEW VALUES
 PRIOR TO RESUBMITTING.
  
 9D. OK
  
 10. OK
  
 NEW COMMENTS RELATED TO NEW INFORMATION ON PLANS:
  
 11. A NEW ERV UNIT HAS BEEN ADDED TO THE MECHANICAL
 PLANS. NO INFORMATION WAS PROVIDED REGARDING WIND
 MOUNTING AND WIND RESISTANCE FOR THIS OUTDOOR
 APPLIANCE. PROVIDE INSTALLATION DETAIL AND
 MANUFACTURER'S DATA SHOWING COMPLIANCE WITH THE WIND
 RESISTANCE REQUIREMENTS OF FBCM 301.13.
  
 12. PAGE A-101 AND LS-1.0 CONTINUE TO HAVE COORDINATION
 PROBLEMS. EXAMPLE: STORAGE ROOM 151AND MULTI-PURPOSE
 ROOM 146 ARE SHOWN ON LS-1.0 TO BE SEPARATED BY 1-HOUR
 CONSTRUCTION. PAGE A-101 WALL TAG AND A-600 WALL TYPES
 SHOW THIS WALL AS CARRYING NO FIRE RATING. THE NEW DUCT
 FOR THE ERV SYSTEM IS SHOWN PENETRATING THIS WALL WITH
 NO PROTECTION. ALSO, THE WALLS AT MECHANICAL ROOM 150
 AND PANTRY 147 ARE ALSO SHOWN WITH FIRE RATED WALLS.
 THERE ARE MULTIPLE DUCT PENETRATIONS IN THESE AREAS
 WITHOUT PROTECTION. PLEASE COORDINATE ALL AEAS OF
 MECHANICAL, ARCHITECTURAL AND LIFE SAFETY PLANS AND
 SHOW EACH DUCT PENETRATION TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5.
 NOTE: SMOKE DAMPERS ARE ONLY REQUIRED AT THE CORRIDOR
 PENETRATIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-20 Cont ID  
Sent By rregueir Date 2008-05-20 Time 11:16 Rev Time 0.00
Received By rregueir Date 2008-05-19 Time 09:52 Sent To  
Notes
2008-05-20 11:16:42REVIEW #: 2ND **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THERE ARE TWO SEPARATE PLANS FOR THE NEW AND
 EXISTING BUILDINGS. ARE THESE TO BE DONE UNDER SEPARATE
 PERMITS? THERE ARE TWO DIFFERENT PAGES NUMBERED M-1 AND
 M-2 AND THEY COVER DIFFERENT SCOPES OF WORK. PLEASE
 CLARIFY. ALSO, THE LEVEL OF ALTERATION COULD NOT BE
 FOUND ON PLANS. THE DESIGN PROFESSIONAL SHALL DECLARE
 THE LEVEL OF ALTERATION IN ACCORDANCE WITH FBCEB
 301.5.
  
 2. WRITTEN RESPONSE TO THIS COMMENT INDICATES THAT
 THERE ARE NO DUCTWORK PENETRATIONS OF RATED WALL
 ASSEMBLIES ON THIS PROJECT. THIS STATEMENT IS IN
 CONFLICT WITH THE INFORMATION ON PAGES LS-1.0 AND M-2.
 PAGE LS-1.0 SHOWS THE WALL BETWEEN THE MULTI-PURPOSE
 ROOM AND THE ENTRANCE HALLWAY TO BE 1-HOUR FIRE
 RESISTANCE RATED. PAGE M-2 SHOWS AT LEAST TWO TYPE J
 AIR TRANSFER OPENINGS IN THIS RATED WALL.
  
 ADDITIONALLY, THE ENTRANCE HALLWAY IS SERVING AS AN
 EXIT ACCESS CORRIDOR FOR THE ASSEMBLY OCCUPANCY IN THE
 MULTI-PURPOSE ROOM. THIS CORRIDOR IS REQUIRED TO BE
 1-HOUR FIRE RESISTANCE RATED IN ACCORDANCE WITH FBCB
 TABLE 1016.1. THIS WOULD REQUIRE BOTH SIDES OF THE
 CORRIDOR TO BE FIRE RESISTANCE RATED. THERE ARE
 MULTIPLE DUCT PENETRATIONS IN THE WALL ON THE OTHER
 SIDE OF THE CORRIDOR IN ADDITION TO THE AIR TRANSFER
 OPENINGS MENTIONED ABOVE. ALL OF THESE OPENINGS AND
 PENETRATIONS OF THE RATED CORRIDOR WALLS ARE REQUIRED
 TO BE PROTECTED IN ACCORDANCE WITH FBCM 607.5.
 NOTE: DUCT PENETRATIONS AND AIR TRANSFER OPENINGS IN
 FIRE-RESISTANCE RATED CORRIDORS ARE REQUIRED TO BE
 PROTECTED WITH FIRE AND SMOKE DAMPERS IN ACCORDANCE
 WITH FBCM 607.5.4 AND FBCB 715.3.3. SHOW HOW THESE
 OPENINGS AND PENETRATIONS ARE TO BE PROTECTED IN
 ACCORDANCE WITH THESE SECTIONS. ALSO, SHOW HOW THESE
 SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH
 FBCM 607.5.4.1.
  
 3. PAGE M-1 OUTSIDE AIR CALCULATIONS STATE "BASED ON
 ASHRAE 62.1-2007." THIS IS A STANDARD WHICH IS NOT
 REFERENCED OR ADOPTED IN THE 2004 FBCM. THE CURRENT
 ADOPTED STANDARD IS ASHRAE 62.1-2004. VENTILATION
 SYSTEMS SHALL BE DESIGNED IN ACCORDANCE WITH THIS
 STANDARD OR FBCM 403.3 AND NOT BY A STANDARD WHICH HAS
 NOT BEEN ADOPTED BY CODE. PLEASE CORRECT AND RESUBMIT.
  
 NOTE: ACCORDING TO ASHRAE 62.1-2004 TABLE 6.1, A
 MULTI-USE ASSEMBLY SPACE REQUIRES 7.5 CFM PER PERSON
 AND HAS AN OCCUPANT LOAD OF 100 PEOPLE PER 1000 SQ.FT.
 PAGE LS-1.0 SHOWS THIS SPACE AT 4501 SQ.FT. WHICH WOULD
 GIVE AN OCCUPANT LOAD OF 450 PEOPLE. THE OCCUPANT LOAD
 SHALL BE BASED ON SQUARE FEET OF FLOOR AREA AND NOT
 SEATING AS THE SEATING IN THIS AREA IS NOT FIXED.
 PLEASE VERIFY ALL VALUES IN THE OUTSIDE AIR
 CALCULATIONS ARE IN CONFORMANCE WITH TABLE 6.1 AND
 ADJUST CALCULATIONS AS NEEDED IN ACCORDANCE WITH FBCM
 403.4.
  
 4. OK
  
 5. OK
  
 6. ROOF VENTILATOR DETAIL, THERE IS NO INFORMATION
 REGARDING THE SIZE AND TYPE OF FASTENERS USED TO ATTACH
 THE VENTILATOR TO THE CURB. THERE IS ALSO NO
 INFORMATION REGARDING THE TYPE AND SIZE OF FASTENERS
 USED TO ATTACH THE CURB TO THE STRUCTURE. IF WOOD
 NAILERS ARE USED FOR THE CURB, THEN INFORMATION IS
 NEEDED ON THE NAILERS, SUCH AS SIZE AND TYPE OF NAILER,
 HOW THE NAILER IS ATTACHED TO THE STRUCTURE. ALSO,
 PROVIDE INFORMATION FROM THE MANUFACTURER SHOWING THE
 VENTILATOR IS DESIGNED TO WITHSTAND ANTICIPATED WIND
 PRESSURES. MECHANICAL EQUIPMENT, APPLIANCES AND
 SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT
 AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING PER FBCM 301.13.
 SUFFICIENT DETAIL AND INFORMATION SHALL BE PROVIDED FOR
 BUILDING PLAN REVIEW TO DETERMINE COMPLIANCE WITH FBCB
 SECTIONS 1604 AND 1609.
  
 7. IT IS UP TO THE DESIGNER TO DETERMINE THE SIZE,
 NUMBER AND SPACING OF FASTENERS NEEDED TO SECURE
 OUTDOOR APPLIANCES TO WITHSTAND ANTICIPATED WIND
 PRESSURES. NO DETAIL HAS BEEN PROVIDED. PLEASE SEE
 COMMENT ABOVE. MANUFACTURER?S INSTALLATION INSTRUCTIONS
 MAY BE SUFFICIENT IF MANUFACTURER?S DATA SHOWS THE
 ATTACHMENT METHODS SPECIFIED HAVE BEEN TESTED TO MEET
 ANTICIPATED WIND PRESSURES IN ACCORDANCE WITH FBCM
 301.13, FBCB 1604 AND FBCB 1609. PLEASE PROVIDE
 SUPPORTING DOCUMENTATION IN SUFFICIENT DETAIL FOR
 BUILDING PLAN REVIEW IN ACCORDANCE WITH THESE
 SECTIONS.
  
 8. NOTE #13 ON M-2 STATES "ONLY ON SET OF LINES PER PVC
 CONDUIT." THIS MAY JUST BE A TYPO AND INTENDED TO SAY
 "ONLY ONE SET"? BUT THE MEANING IS UNCLEAR. PLEASE
 CLARIFY. FBCM 1107.2.1, FBCB 106.1.1.
  
 9. ENERGY CALCULATIONS:
 A) THE CERTIFICATION PAGE STATES THE CALCULATIONS WERE
 PREPARED BY "C. HAMMOND." IS C. HAMMOND AN ENGINEER OR
 ARCHITECT? ENERGY CALCULATIONS SHALL BE PREPARED BY AN
 ARCHITECT OR ENGINEER IN ACCORDANCE WITH FBCB 13-103.2.
 ALSO, C. HAMMOND HAS NOT CERTIFIED THESE CALCULATIONS
 AS REQUIRED BY FBCB 13-103.1.1.
  
 B) S. HOCKMAN AND C. HAMMOND ARE LISTED AS THE
 ELECTRICAL AND MECHANICAL DESIGNERS FOR THIS PROJECT.
 NEITHER OF THESE PEOPLE ARE THE DESIGNERS OF RECORD, AS
 THEY DID NOT SIGN AND SEAL THE PLANS. THEY ALSO DID NOT
 PROVIDE LICENSE NUMBERS ON THE CERTIFICATION FORM.
 DESIGN PROFESSIONALS RESPONSIBLE UNDER FLORIDA LAW FOR
 THE DESIGN OF LIGHTING, ELECTRICAL, MECHANICAL, AND
 PLUMBING SYSTEMS AND THE BUILDING SHELL, SHALL CERTIFY
 COMPLIANCE OF THOSE BUILDING SYSTEMS WITH THE CODE BY
 SIGNING AND PROVIDING THEIR PROFESSIONAL REGISTRATION
 NUMBER ON THE ENERGY CODE FORM PROVIDED AS PART OF THE
 PLANS AND SPECIFICATIONS TO THE BUILDING DEPARTMENT.
 EXCEPTION: TYPED NAMES AND REGISTRATION NUMBERS MAY BE
 PROVIDED IN LIEU OF A SIGNATURE WHERE ALL RELEVANT
 INFORMATION HAS BEEN INCLUDED ON SIGNED AND SEALED
 PLANS IN ACCORDANCE WITH FBCB 13-103.1.1.
  
 C) INPUT DATA REPORT (IDR): SOME ENTRIES IN THE IDR DO
 NOT MATCH THE INFORMATION ON THE PLANS OR THE RATINGS
 OF THE EQUIPMENT SPECIFIED. EXAMPLE: AC-1 AND AC-2 IN
 THE IDR SHOW EFFICIENCY AT 10.1 WHILE THE EQUIPMENT
 SCHEDULE AND MANUFACTURER?S DATA SHOW THESE SYSTEMS
 RATED AT 9.7 EER. THIS IS NOT AN EXHAUSTIVE LIST OF ALL
 DISCREPANCIES. PLEASE VERIFY ALL DATA WHICH IS INPUT
 INTO THE PROGRAM CORRESPONDS WITH THE INFORMATION ON
 THE PLANS IN ACCORDANCE WITH FBCB 13-103.2
  
 D) COMPLIANCE FORM SUBMITTED IS FLA/COM 2004 V3.00. THE
 CORRECT FOR IS FLA/COM V2.5 FORM 400A-04R IN ACCORDANCE
 WITH FBCB 13-400.3.A. THIS VERSION 2.5 FORM MAY
 INCORPORATE THE LATEST VERSION OF ENERGYGAUGE.
  
 NOTE: THESE CALCULATIONS ARE ONLY BEING REVIEWED FOR
 COMPLIANCE WITH THE GENERAL AND MECHANICAL PORTIONS OF
 THE ENERGY CODE. PLEASE SEE OTHER TRADE REVIEWS FOR
 ADDITIONAL COMMENTS, IF APPLICABLE.
  
 10. NOT ADDRESSED. NO INFORMATION COULD BE FOUND IN THE
 SUBMITTAL PACKAGE REGARDING THE GENERATOR.
  
 11. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-30 Cont ID  
Sent By rregueir Date 2007-10-30 Time 11:53 Rev Time 0.00
Received By rregueir Date 2007-10-29 Time 18:29 Sent To PC
Notes
2007-10-30 11:53:01REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: AT THIS TIME PLANS ARE SUBMITTED FOR *PLAN REVIWE
 ONLY.* NO PERMIT HAS BEEN APPLIED FOR AT THIS TIME.
 ADDITIONAL REVIEWS MAY BE POSSIBLE TO VERIFY COMPLIANCE
 WITH CODES IN EFFECT AT TIME OF APPLICATION.
  
 1. PLAN ONLY SHOWS MECHANICAL SCOPE OF WORK FOR NEW
 BUILDING AREA. NO INFORMATION WAS PROVIDED REGARDING
 SCOPE OF MECHANICAL WORK IN EXISTING AREAS. WHAT IS THE
 LEVEL OF ALTERATION IN EXISTING BUILDING? THE DESIGN
 PROFESSIONAL MUST ELECT ONE OR A COMBINATION OF LEVELS
 OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE IN ACCORDANCE WITH FBC, EB 301.5. THIS
 INFORMATION MAY IMPACT THE LEVEL OF CODE COMPLIANCE
 REQUIRED IN EXISTING AREAS.
  
 2. A SCHEDULE OF WALL TYPES COULD NOT BE LOCATED IN
 PLANS. WITHOUT THIS INFORMATION IT IS NOT POSSIBLE TO
 DETERMINE SOME REQUIREMENTS SUCH AS WHERE OPENING
 PROTECTIVES (FIRE AND/OR SMOKE DAMPERS) ME BE REQUIRED.
 FBC,M 607.5. PROVIDE ALL MISSING INFORMATION NEEDED TO
 PERFORM A COMPLETE REVIEW. FBC 106.1.1.
  
 3. PG M-1: OUTSIDE AIR AND EXHAUST, THE CALCULATIONS
 STATE "BASED ON FBC2004 - MECHANICAL AND ASHRAE 62."
 PLEASE DECLARE WHICH METHOD IS BEING USED, EITHER FBC,M
 403.3 OR ASHRAE 62.1-2004. ONE METHOD OR THE OTHER MAY
 BE USED BUT NOT BOTH. SEE FBC,M 403.4. VENTILATION AND
 EXHAUST REQUIREMENTS CAN NOT BE REVIEWED AT THIS TIME.
  
 4. PG M-2: AHU'S 1 AND 2 SHOW A COMMON RETURN PLENUM.
 SAME WITH AHU'S 3 AND 4. AS SUCH, SMOKE DETECTORS ARE
 REQUIRED ON BOTH THE SUPPLY AND RETURN IN ACCORDANCE
 WITH FBC,M 606.2.2. ALSO, SMOKE DETECTORS SHALL BE
 CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC,M 606.4.1. SHOW COMPLIANCE WITH
 THESE SECTIONS.
  
 5. M-3 FLEXIBLE DUCT DETAIL:
 A) PLEASE REFERENCE THE CORRECT CODE: FBC,M 2004, AND
 NOT 2001.
 B) FLEXIBLE DUCT SUPPORTS SHALL BE NOT LESS THAN 1 1/2
 IN. WIDE PER FBC,M 603.5.6.6(6), NOT 1 IN. AS STATED IN
 DETAIL NOTES.
  
 6. M-3: OA/EXHAUST VENT DETAIL, SHOW ROOF CURB AND
 VENTILATORS TO BE DESIGNED TO MEET 140MPH WINDS IN
 ACCORDANCE WITH FBC,M 301.13 AND FBC SEC 1609. SHOW
 SUFFICIENT DETAIL FOR CURB TO ROOF AND VENT TO CURB
 ATTACHMENTS ALONG WITH WIND LOAD CALCULATIONS FOR
 STRUCTURAL REVIEW. FBC 106.1.2.
  
 7. M-2: KEY NOTE 1, PROVIDE DETAIL FOR CONDENSING UNIT
 ATTACHMENTS TO SLABS SHOWING HOW UNITS ARE TO BE
 ATTACHED TO MEET WIND LOAD REQUIREMENTS IN ACCORDANCE
 WITH FBC,M 301.13 AND FBC 1609. PROVIDE MANUFACTURER'S
 SUBMITTAL SHOWING EQUIPMENT DESIGNED FOR MIN. 140MPH
 AND WIND LOAD CALCULATIONS FOR ATTACHMENTS FOR
 STRUCTURAL REVIEW. FBC 106.1.2.
  
 8. M-2: PLEASE SHOW SIZE AND ROUTING OF REFRIGERANT
 LINES FROM REMOTE CONDENSERS TO AHU'S AND SHOW
 COMPLIANCE WITH FBC,M 1107.2.1 WHERE PIPES PASS UNDER A
 SLAB OR THROUGH WALLS, CEILINGS, FLOORS OR BEAMS.
  
 9. PROVIDE ENERGY CODE COMPLIANCE FORM/ CALCULATIONS TO
 SHOW COMPLIANCE WITH FBC CH.13 IN ACCORDANCE WITH FBC
 13-400.0 AND 13-101.1. A REVIEW FOR FLORIDA ENERGY CODE
 COMPLIANCE CAN NOT BE PERFORMED AT THIS TIME.
  
 10. PORVIDE SUBMITTAL FOR GENERATOR AS SHOWN ON A-101
 AND P-2. GENERATORS SHALL BE IN COMPLIANCE WITH NFPA
 37-02 IN ACCORDANCE WITH FBC,M 915.1.
  
 11. A MINIMUM OF TWO SETS OF PLANS SHALL BE SUBMITTED
 PER FBC 106.1 AND SHALL BE SIGNED AND SEALED BY THE
 DESIGNER OF RECORD IN ACCORDANCE WITH FS 471 AND 481.
 ALSO PLEASE SEE FAC RULE 61G15-23.002 FOR ADDITIONAL
 REQUIREMENTS FOR DESSIGNERS PROVIDING SERVICES UNDER AN
 ENGINEERING BUSINESS.
  
 NOTE: DUE TO THE SIGNIFICANT VOLUME OF MISSING
 INFORMATION, ADDITIONAL REVIEW COMMENTS ARE LIKELY FROM
 SUBSEQUENT REVIEWS ONCE ALL MISSING INFORMATION IS
 PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 13 Status P Date 2009-09-21 Cont ID  
Sent By kstevens Date 2009-09-21 Time 13:04 Rev Time 0.00
Received By kstevens Date 2009-09-21 Time 13:04 Sent To  
Notes
2009-09-21 13:05:55REVISION OK -- SHT A-104 NEW OVERFLOW SCUPPERS SIZES.

Review Stop P PLUMBING
Rev No 12 Status P Date 2009-07-07 Cont ID  
Sent By kstevens Date 2009-07-07 Time 15:09 Rev Time 0.00
Received By kstevens Date 2009-07-07 Time 15:09 Sent To  
Notes
2009-07-07 15:11:45REVISION OK -- SHTS P-2, L-6.0 & L-6.1.

Review Stop P PLUMBING
Rev No 11 Status P Date 2009-04-17 Cont ID  
Sent By kstevens Date 2009-04-17 Time 17:02 Rev Time 0.00
Received By kstevens Date 2009-04-17 Time 17:02 Sent To  
Notes
2009-04-17 17:02:45REVISIONS OK -- SHTS P-3 & P-5

Review Stop P PLUMBING
Rev No 10 Status P Date 2009-01-05 Cont ID  
Sent By kstevens Date 2009-01-05 Time 16:44 Rev Time 0.00
Received By kstevens Date 2008-12-15 Time 13:52 Sent To  
Notes
2008-12-16 11:36:11ATTEMPTED TO REVIEW EXPEDITED PLANS BUT WAS STILL
 MISSING HEALTH DEPT. STAMP/REVIEW. TRIED TO CONTACT
 JEFF H. BUT TO NO AVAIL. RON R. CONTACTED JEFF ON
 12-16-08 AND INDICATED THAT I SHOULD HOLD MY REVIEW
 UNTILL THE SHEETS WERE INCLUDED. PLACED PLANS BACK ON
 RACK. UNABLE TO EXPEDITE.

Review Stop P PLUMBING
Rev No 9 Status F Date 2008-11-19 Cont ID  
Sent By kstevens Date 2008-11-19 Time 11:30 Rev Time 0.00
Received By kstevens Date 2008-11-19 Time 11:30 Sent To  
Notes
2008-11-19 13:02:32REVIEW FOR NEW BUILDING:
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 ********FROM PREVIOUS REVIEWS:
  
 **********FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. PLANS SHALL BE ROUTED TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW PRIOR TO RESUBMITTING TO THE CITY FOR PLAN
 REVIEW. PLANS SHALL BE STAMPED AS REVIEWED BY THE
 HEALTH DEPT. (901 EVERNIA (561) 355-3018). SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT IF FOOD IS BEING SERVED THEN A
 REVIEW BY THE COUNTY HEALTH DEPT. IS REQUIRED.
 ******RESPONSE NOTED, PLANS NOT REVIEWED/STAMPED AT
 THIS TIME.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
 **********RESPONSE NOTED, BUT THE HEALTH DEPT.
 INFORMATION SUBMITTED IS FOR THE CONSTRUCTION OF THE
 WATER DISTRIBUTION SYSTEM TO PROVIDE POTABLE WATER &
 FIRE SERVICE ONLY. THE REQUIREMENT REQUESTED IS FOR THE
 PANTRY AREA INSIDE THE BUILDING. PLANS SHALL BE STAMPED
 BY THE HEALTH UNIT.
  
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
  
 26. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. OK
 2B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 8 Status F Date 2008-10-08 Cont ID  
Sent By kstevens Date 2008-10-08 Time 14:42 Rev Time 0.00
Received By kstevens Date 2008-10-08 Time 14:42 Sent To  
Notes
2008-10-08 14:44:51REVIEW FOR NEW BUILDING:
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 ********FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. PLANS SHALL BE ROUTED TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW PRIOR TO RESUBMITTING TO THE CITY FOR PLAN
 REVIEW. PLANS SHALL BE STAMPED AS REVIEWED BY THE
 HEALTH DEPT. (901 EVERNIA (561) 355-3018). SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT IF FOOD IS BEING SERVED THEN A
 REVIEW BY THE COUNTY HEALTH DEPT. IS REQUIRED.
 ******RESPONSE NOTED, PLANS NOT REVIEWED/STAMPED AT
 THIS TIME.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
  
 26. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
 ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE
 THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE
 GAS PERMIT.
 ******RESPONSE NOTED, BUT SHEETS NOT SUBMITTED.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. OK
 2B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-10-01 Cont ID  
Sent By kstevens Date 2008-10-01 Time 16:48 Rev Time 0.00
Received By kstevens Date 2008-10-01 Time 16:48 Sent To  
Notes
2008-10-01 16:48:50NORTH WING RENOVATIONS ONLY THIS REVIEW STOP

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-10-08 Cont ID  
Sent By kstevens Date 2008-10-08 Time 11:48 Rev Time 0.00
Received By kstevens Date 2008-10-01 Time 17:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-07-22 Cont ID  
Sent By kstevens Date 2008-07-22 Time 10:59 Rev Time 0.00
Received By kstevens Date 2008-07-22 Time 10:59 Sent To  
Notes
2008-07-22 10:59:47NORTH WING RENOVATIONS ARE OK AT THIS TIME BUT WILL
 REMAIN IN FAILED STATUS UNTILL THE ADDITION IS APPROVED
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-07-22 Cont ID  
Sent By kstevens Date 2008-07-22 Time 10:03 Rev Time 0.00
Received By kstevens Date 2008-07-21 Time 15:59 Sent To  
Notes
2008-07-22 10:40:35REVIEW FOR NEW BUILDING:
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
  
 2. ALL SHEETS DESIGNED BY PROFESSIONAL ARCHITECT,
 ENGINEER, SURVEYOR, LANDSCAPE ARCH. DESIGNER ETC. SHALL
 CONTAIN THE INFORMATION IN THE TITLE BLOCK THAT IS
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE AND FLORIDA
 STATUTES.
 ****RESPONSE NOTED, BUT THE BUSINESS LICENSE,
 (CERTIFICATE OF AUTHORIZATION), IS NOT INDICATED IN THE
 TITLE BLOCK FOR THE ARCHITECT. FAC 61G1-16.004(2) & FS
 481.219. (THIS FOR LANDSCAPE AND IRRIGATION SHEETS
 ALSO).
 ******RESPONSE NOTED, BUT THE ADDRESS OF RECORD FOR THE
 ARCHITECT, (1 EAST BROWARD BLVD. FT. LAUDERDALE FLA.),
 DOES NOT REFLECT THE ADDRESS OF RECORD AS SHOWN ON THE
 STATE OF FLORIDA DBPR WEBSITE, (2601 S BAYSHORE DR.
 MIAMI FLA., SEE ATTACHED SHEET). PLEASE UPDATE THE
 TITLE BLOCK OR THE DBPR WEBSITE PRIOR TO RESUBMITTING
 FOR REVIEW. -- ALSO BERMELLO AJAMIL & PARTNERS INC IS
 IDENTIFIED AT THE LANDSCAPE ARCHITECT IN THE TITLE
 BLOCKS ON ALL LANDSCAPE AND IRRIGATION PLANS. PLEASE
 INDICATE THE CORRECT ARCHITECT FOR THE LANDSCAPE AND
 IRRIGATION TITLE BLOCKS.
  
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. PLANS SHALL BE ROUTED TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW PRIOR TO RESUBMITTING TO THE CITY FOR PLAN
 REVIEW. PLANS SHALL BE STAMPED AS REVIEWED BY THE
 HEALTH DEPT. (901 EVERNIA (561) 355-3018). SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT IF FOOD IS BEING SERVED THEN A
 REVIEW BY THE COUNTY HEALTH DEPT. IS REQUIRED.
 ******RESPONSE NOTED, PLANS NOT REVIEWED/STAMPED AT
 THIS TIME.
  
 12. SHT A-102 INDICATES A PANTRY. WILL FOOD BE
 PREPARED? A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE
 CONTACT INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE, RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected] OR CALVIN WILLIAMS, (561) 822-2284,
 E-MAIL [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. A WRITTEN DETERMINATION, FROM ENVIRONMENTAL
 COMPLIANCE, INDICATING IF A GREASE INTERCEPTOR IS
 REQUIRED OR NOT SHALL BE SUBMITTED WITH PLANS. ARTICLE
 III SECTION 90-124(7)(F).
 ****RESPONSE NOTED, BUT NO EVIDENCE OF CONTACT WITH
 ENVIRONMENTAL COMPLIANCE. PLEASE COMPLY WITH INITIAL
 REQUEST.
 ******RESPONSE NOTED, AWAITING REPLY FROM RODNEY COMPO
  
 13. OK
 14. OK
 15. OK
  
 16. SHT A-501 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 ******RESPONSE NOTED, COMMENT NOT ADDRESSED.
 B. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE FLUSH CONTROLS SHALL BE
 INDICATED ON THE WIDE SIDE OF THE TOILET TANK. ___FOR
 ACCESS. STALL:
 A. OK
 ___FOR URINALS:
 A. OK
 B. OK
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 ******RESPONSE NOTED, BUT CLEAR FLOOR SPACE FOR THE
 UNISEX TOILET ROOM LAV SHALL BE FORWARD APPROACH. SHOWN
 AS PARALLEL APPROACH.
 B. OK
  
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
  
 26. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. OK
 B. OK
 C. OK
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
 ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE
 THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE
 GAS PERMIT.
 ******RESPONSE NOTED, BUT SHEETS NOT SUBMITTED.
  
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. OK
 2B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-05-10 Cont ID  
Sent By kstevens Date 2008-05-10 Time 14:39 Rev Time 0.00
Received By kstevens Date 2008-05-10 Time 14:38 Sent To  
Notes
2008-05-10 14:48:28NORTH WING RENOVATIONS
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCK. THE
 BUSINESS LICENSE, (CERTIFICATE OF AUTHORIZATION), IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET. FAC
 61G1-16.004(2) & FS 481.219.
  
 2. SHT D-100 SHOWS 5 SINKS BEING REMOVED. IN THE
 REMOVAL OF ANY PART OF THE DRAINAGE SYSTEM, DEAD ENDS
 ARE PROHIBITED. SECTION 704.5. ALL BRANCH LINES TO THE
 SINKS SHALL BE REMOVED TO THE BUILDING SANITARY DRAIN.
 PLEASE INDICATE ON PLANS.
  
 3. DRINKING FOUNTAINS ARE REQUIRED PER TABLE 403.1.
 SUBMIT CALCULATIONS FOR THE NET AREA TO DETERMINE THE
 NUMBER OF DRINKING FOUNTAINS REQUIRED AND SHOW THE
 LOCATION OF THE DRINKING FOUNTAINS. INDICATE IF THE
 DRINKING FOUNTAINS ARE EXISTING OR NEW. IF NEW DRINKING
 FOUNTAINS ARE TO BE INSTALLED, THE REQUIREMENTS OF
 SECTION 11-4.15 WITH ALL SUBSECTIONS ALONG WITH SECTION
 11-4.1.2(10)(A)PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING SHALL BE INDICATED ON
 THE PLANS WITH A DETAIL.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-10 Cont ID  
Sent By kstevens Date 2008-05-10 Time 11:10 Rev Time 0.00
Received By kstevens Date 2008-05-10 Time 11:10 Sent To  
Notes
2008-05-10 13:09:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. ALL SHEETS DESIGNED BY PROFESSIONAL ARCHITECT,
 ENGINEER, SURVEYOR, LANDSCAPE ARCH. DESIGNER ETC. SHALL
 CONTAIN THE INFORMATION IN THE TITLE BLOCK THAT IS
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE AND FLORIDA
 STATUTES.
 ****RESPONSE NOTED, BUT THE BUSINESS LICENSE,
 (CERTIFICATE OF AUTHORIZATION), IS NOT INDICATED IN THE
 TITLE BLOCK FOR THE ARCHITECT. FAC 61G1-16.004(2) & FS
 481.219. (THIS FOR LANDSCAPE AND IRRIGATION SHEETS
 ALSO).
  
 3. OK
  
 4. SHT G-100 THE INDEX OF DRAWINGS INDICATES AN
 EXISTING BUILDING. THE DESCRIPTION OF THE PROJECT ON
 THE PERMIT APPLICATION SHALL REFLECT THE PROJECT IN
 DETAIL. PLEASE HAVE THE DESCRIPTION INDICATE AN
 EXISTING BUILDING, IF IT AN ALTERATION, RENOVATION ETC.
 AND IF IT IS A CHANGE OF OCCUPANCY OR NOT AS REQUIRED
 ON THE APPLICATION. ALSO THE TITLE BLOCK PROJECT NAME,
 "GAINES PARK COMMUNITY CENTER EXPANSION" & THE "NEW
 FACILITY" ON SHT A-100 IS NOT INDICATED IN THE PROJECT
 DESCRIPTION ON THE PERMIT APPLICATION. PLEASE CLARIFY.
 SECTION 105.3.
 ****RESPONSE NOTED, BUT THE PERMIT APPLICATION
 DESCRIPTION OF WORK STILL DOES NOT REFLECT THE SCOPE OF
 WORK OF THE PLANS.
  
 5. OK
 6. OK
  
 7. NINE SHEETS WERE SUBMITTED WITH DIFFERENT
 INFORMATION BUT THE SAME SHEET NUMBERS. THIS IS NOT
 APPROVED. (SEE SHEETS G-100, A-101, A-102, A-401 THRU
 A-405 & A-700) SECTION 106.1.3. PLEASE SUBMIT 2
 COMPLETE SETS OF PLANS FOR ALL WORK TO REFLECT THE
 DESCRIPTION OF WORK DETAILED ON THE PERMIT APPLICATION.
 SHEET NUMBERS SHALL NOT DUPLICATE WITH DIFFERENT
 INFORMATION.
 ****RESPONSE NOTED, BUT THIS IS NOT REFLECTED ON THE
 PERMIT APPLICATION DESCRIPTION OF WORK AS REQUIRED.
  
 8. INDICATE THE LEVEL OF ALTERNATION FOR THE EXISTING
 BUILDING PER CHAPTER 3 OF THE EXISTING BUILDING CODE.
 ****RESPONSE NOTED, BUT LEVEL OF ALTERATION IS NOT
 INDICATED ON THE PLANS. INDICATE LEVEL 1, LEVEL 2, OR
 LEVEL 3.
  
 9. SHT G-100 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEET SUBMITTED. SHT A-800 NOT SUBMITTED. PLEASE
 CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SHTS 11, 12, 13, L-5.2, L-5.3
 P-4 & P-5 WERE SUBMITTED BUT ARE NOT SHOWN ON THE INDEX
 OF DRAWINGS. PLEASE CORRELATE. SECTION 106.1.3.
  
 10. OK
  
 11. PLANS SHALL BE ROUTED TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW PRIOR TO RESUBMITTING TO THE CITY FOR PLAN
 REVIEW. PLANS SHALL BE STAMPED AS REVIEWED BY THE
 HEALTH DEPT. (901 EVERNIA (561) 355-3018). SECTION
 102.2.1.
 ****RESPONSE NOTED, BUT IF FOOD IS BEING SERVED THEN A
 REVIEW BY THE COUNTY HEALTH DEPT. IS REQUIRED.
  
 12. SHT A-102 INDICATES A PANTRY. WILL FOOD BE
 PREPARED?A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE
 CONTACT INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE, RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected] OR CALVIN WILLIAMS, (561) 822-2284,
 E-MAIL [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. A WRITTEN DETERMINATION, FROM ENVIRONMENTAL
 COMPLIANCE, INDICATING IF A GREASE INTERCEPTOR IS
 REQUIRED OR NOT SHALL BE SUBMITTED WITH PLANS. ARTICLE
 III SECTION 90-124(7)(F).
 ****RESPONSE NOTED, BUT NO EVIDENCE OF CONTACT WITH
 ENVIRONMENTAL COMPLIANCE. PLEASE COMPLY WITH INITIAL
 REQUEST.
  
 13. OK
 14. OK
 15. OK
  
 16. SHT A-501 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 B. 11-4.16.5 FLUSH CONTROLS
 ****NOT ADDRESSED.
 ___FOR ACCESS. STALL:
 A. 11-4.17.3 EXCEPTION(2) THE W/C SHALL BE LOCATED IN
 THE CORNER DIAGONAL TO THE DOOR.
 ****NOT ADDRESSED.
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 B. 11-4.18.4 FLUSH CONTROLS
 ****NOT ADDRESSED.
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ****NOT ADDRESSED.
 B. OK
  
 17. SUBMIT A DETAIL/ELEVATION FOR THE DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****RESPONSE NOTED, NOT ADDRESSED.
  
 18. SHT A-700 FINISH SCHEDULE FOR ROOMS 164 & 166. THE
 WALLS WITHIN 2 FEET OF WATER CLOSETS AND URINALS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. SECTION
 S-1210.2. PLEASE INDICATE HOW PAINT COMPLIES WITH THESE
 REQUIREMENTS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 19. OK
 20. OK
 21. OK
  
 22. SHT P-3 SANITARY ISOMETRIC RISER DIAGRAM IS NOT
 COMPLETE. SHOW ALL PIPING TO ALL FIXTURES ON THE RISER.
 SECTION 106.3.5.1.3(4)(6)(13).
 ****RESPONSE NOTED, BUT FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED FOR THE ICE MAKER IN THE PANTRY. SECTIONS
 802.3 & 802.3.2.
  
 23. OK
  
 24. SUBMIT STORM PIPING INFORMATION. SHOW THE LOCATION
 OF ALL PRIMARY AND SECONDARY ROOF DRAINS. SUBMIT A
 STORM ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES,
 OFFSETS & TERMINATION POINT. SECTION
 106.3.5.1.3(7)(13).
 ****RESPONSE NOTED, BUT THE PIPING SHALL BE INSTALLED
 WITH A UNIFORM SLOPE. ONE RISER HAS THE HORIZONTAL
 PIPING FROM THE FIRST ROOF DRAIN AT 1/4"/FT THEN
 CHANGES TO 1/8"/FT AFTER THE SECOND ROOF DRAIN AND THEN
 CHANGES BACK TO 1/4"/FT AFTER THE THIRD ROOF DRAINL.
 THE PIPING SHALL BE 1/4"/FT THROUGHOUT THE RUN. SECTION
 7-4.1. (THIS SHALL BE CHANGED ON THE ROOF PLAN ALSO).
  
 25. OK
  
 26. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE LENGTHS OF THE CUT SECTIONS
 ARE NOT SHOWN ON THE RISER DIAGRAM.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 RESPONSE NOTED, BUT THIS WILL BE VERIFIED WHEN COMMENT
 "A" IS ADDRESSED.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ****NO RESPONSE, NOT ADDRESSED.
  
 D. OK
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
 ****RESPONSE NOTED. SHEETS WILL BE REQUIRED TO APPROVE
 THE GAS PORTION OF THE PLAN REVIEW AND THE ISSUE THE
 GAS PERMIT.
  
 27. OK
  
 **********NEW GAS COMMENTS**********
  
 1B. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE "ETR"
 & WITHIN 6' OF THE GENERATOR PER SECTION 409.5. PLEASE
 INDICATE ON THE GAS RISER DIAGRAM.
  
 2B. PER TABLE 402.4(2), 2-1/2" PIPE IS REQUIRED FOR THE
 GAS LINE TO THE GENERATOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-27 Cont ID  
Sent By kstevens Date 2007-10-27 Time 10:01 Rev Time 0.00
Received By kstevens Date 2007-10-26 Time 19:00 Sent To  
Notes
2007-10-27 14:04:19DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 EXISTING BUILDING CODE
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 1. ALL SHEETS. PLANS SHALL BE SIGNED, SEALED, & DATED
 AS REQUIRED BY SECTION 106.1, FAC 61G1-16.003, FAC
 61G1-16.004(5), FAC 61G15-23.002(1)(2) & FS 471.025, FS
 481.2055.
  
 2. ALL SHEETS DESIGNED BY PROFESSIONAL ARCHITECT,
 ENGINEER, SURVEYOR, LANDSCAPE ARCH. DESIGNER ETC. SHALL
 CONTAIN THE INFORMATION IN THE TITLE BLOCK THAT IS
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE AND FLORIDA
 STATUTES.
  
 3. SHT G-100 GENERAL NOTES 32 INDICATES THE BUILDING
 WAS DESIGNED UNDER THE 2001 CODE. ALSO APPLICABLE CODES
 #1 INDICATES BUILDING, MECHANICAL, PLUMBING & FUEL GAS
 CODE IN EFFECT AS 2001 WITH 2003 REVISIONS. AT PRESENT
 THE STATE HAS ADOPTED THE FBC-2004 WITH 2006 & 2006
 REVISIONS. PLEASE UPDATE THE DESIGN & CODE REFERENCE.
  
 4. SHT G-100 THE INDEX OF DRAWINGS INDICATES AN
 EXISTING BUILDING. THE DESCRIPTION OF THE PROJECT SHALL
 REFLECT THE PROJECT IN DETAIL. PLEASE HAVE THE
 DESCRIPTION INDICATE AN EXISTING BUILDING, IF IT AN
 ALTERATION, RENOVATION ETC. AND IF IT IS A CHANGE OF
 OCCUPANCY OR NOT AS REQUIRED ON THE APPLICATION. ALSO
 THE TITLE BLOCK PROJECT NAME, "GAINES PARK COMMUNITY
 CENTER EXPANSION" & THE "NEW FACILITY" ON SHT A-100 IS
 NOT INDICATED IN THE PROJECT DESCRIPTION. PLEASE
 CLARIFY. SECTION 105.3.
  
 5. SHT D-100 GENERAL DEMOLITION LEGEND NOTE #3 STATES,
 "CONTRACTOR IS RESPONSIBLE FOR CAPPING & SECURING ALL
 EXISTING UNDER GROUND UTILITIESPRIOR TO COMMENCEMENT
 OF CONSTRUCTION". THESE INCLUDE WATER, SEWER & GAS.
 PLEASE SHOW THE LOCATION WHERE ALL THESE SYSTEMS WILL
 BE CAPPED ON THE DEMO SHEET. SECTION 106.1.2. DEAD ENDS
 WILL BE PROHIBITED PER SECTION 704.5.
  
 6. NO NEW WORK IS SHOWN ON THE PLANS FOR THE EXISTING
 BUILLDING. EXISTING FLOOR PLANS, EXISTING REFLECTED
 CEILING PLAN, EXISTING ELEVATIONS ETC. WERE SUBMITTED
 AND NO PLUMBING SHEETS. PLEASE SUBMIT PLANS SHOWING THE
 EXTENT OF THE WORK BEING DONE IN THE EXISTING BUILDING.
 SECTION 106.1.2 (MORE INFORMATION REQUIRED).
  
 7. NINE SHEETS WERE SUBMITTED WITH DIFFERENT
 INFORMATION BUT THE SAME SHEET NUMBERS. THIS IS NOT
 APPROVED. (SEE SHEETS G-100, A-101, A-102, A-401 THRU
 A-405 & A-700) SECTION 106.1.3. PLEASE SUBMIT 2
 COMPLETE SETS OF PLANS FOR ALL WORK TO REFLECT THE
 DESCRIPTION OF WORK DETAILED ON THE PERMIT APPLICATION.
 SHEET NUMBERS SHALL NOT DUPLICATE WITH DIFFERENT
 INFORMATION.
  
 8. INDICATE THE LEVEL OF ALTERNATION FOR THE EXISTING
 BUILDING PER CHAPTER 3 OF THE EXISTING BUILDING CODE.
  
 9. SHT G-100 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEET SUBMITTED. SHT A-800 NOT SUBMITTED. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 10. SUBMIT NEW BUILDING DATA. SHOW THE SQUARE FOOTAGE
 OF THE BUILDING AND DECLARE THE OCCUPANCY. IF ASSEMBLY,
 POTTY PARITY MAY BE IN EFFECT. SECTIONS 106.1.2 &
 P-104.3.1.1.
  
 11. PLANS SHALL BE ROUTED TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL HEALTH FOR
 REVIEW PRIOR TO RESUBMITTING TO THE CITY FOR PLAN
 REVIEW. PLANS SHALL BE STAMPED AS REVIEWED BY THE
 HEALTH DEPT. (901 EVERNIA (561) 355-3018). SECTION
 102.2.1.
  
 12. SHT A-102 INDICATES A PANTRY. WILL FOOD BE
 PREPARED?A GREASE INTERCEPTOR MAY BE REQUIRED. PLEASE
 CONTACT INDUSTRIAL PRETREATMENT, ENVIRONMENTAL
 COMPLIANCE, RODNEY COMPO, (561) 822-2272, E-MAIL
 [email protected] OR CALVIN WILLIAMS, (561) 822-2284,
 E-MAIL [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. A WRITTEN DETERMINATION, FROM ENVIRONMENTAL
 COMPLIANCE, INDICATING IF A GREASE INTERCEPTOR IS
 REQUIRED OR NOT SHALL BE SUBMITTED WITH PLANS. ARTICLE
 III SECTION 90-124(7)(F).
  
 13. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES S-1004.1.2& P-403.1.
  
 14. SHT A-104 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS FOR ALL ROOFS. SHOW THE SQUARE
 FOOTAGE AREA FOR EACH ROOF DRAIN WITH 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THE ROOF
 DRAIN AREA AS WELL AS ANY ARE OF ROOF THAT DRAINS ONTO
 THE ROOF FROM ABOVE. SHOW THE LOCATION OF ALL ROOF
 DRAINS AND SECONDARY ROOF DRAINS/SCUPPERS REQUIRED BY
 SECTION 1107. SECTION 1106.
  
 15. SHT A-501 SOME ACCESSIBLITY INFORMATION IS NOT
 LEGIBLE NOR COMPLETE. PLEASE MAKE SURE INFORMATION IS
 LEGIBLE. SECTION 106.1.1.
  
 16. SHT A-501 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR ACCESS. STALL:
 A. 11-4.17.3 EXCEPTION(2) THE W/C SHALL BE LOCATED IN
 THE CORNER DIAGONAL TO THE DOOR.
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES.
  
 17. SUBMIT A DETAIL/ELEVATION FOR THE DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 18. SHT A-700 FINISH SCHEDULE FOR ROOMS 164 & 166. THE
 WALLS WITHIN 2 FEET OF WATER CLOSETS AND URINALS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. SECTION
 S-1210.2. PLEASE INDICATE HOW PAINT COMPLIES WITH THESE
 REQUIREMENTS.
  
 19. SHT A-800 IS BLANK, NO INFORMATION. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 20. SHT P-1 THE WATER HEATER INDICATES AN 80 GAL. W/H,
 BUT SHT P-2 ENLARGED PANTRY DETAIL INDICATES A 60 GAL.
 W/H. PLEASE CORRELATE INFORMATION. SECTION 106.1.1.
  
 21. SHT P-3 SANITARY ISOMETRIC RISER DIAGRAM. A
 CLEANOUT IS REQUIRED NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER & AT ALL CHANGES OF
 DIRECTION GREATER THAN 45 DEGREES. PLEASE SHOW ON THE
 RISER. SECTIONS 708.3.5 & 708.3.3.
  
 22. SHT P-3 SANITARY ISOMETRIC RISER DIAGRAM IS NOT
 COMPLETE. SHOW ALL PIPING TO ALL FIXTURES ON THE RISER.
 SECTION 106.3.5.1.3(4)(6)(13).
  
 23. SHT P-3 DOMESTIC WATER ISOMETRIC RISER DIAGRAM IS
 NOT COMPLETE. SHOW ALL PIPE SIZES, VALVES AND WATER
 HAMMER ARRESTORS THAR ARE REQUIRED ON QUICK CLOSING
 VALVES. (DISH WASHER, ICE MAKER ETC.). SECTION 604.9.
 --SHOW ALL PIPING TO ALL FIXTURES. SECTION
 106.3.5.1.3(3)(10)(13).
  
 24. SUBMIT STORM PIPING INFORMATION. SHOW THE LOCATION
 OF ALL PRIMARY AND SECONDARY ROOF DRAINS. SUBMIT A
 STORM ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES,
 OFFSETS & TERMINATION POINT. SECTION
 106.3.5.1.3(7)(13).
  
 25. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, OFFSETS, TRAPS AND TERMINATION POINT
 FOR ALL CONDENSATE PIPING TO REFLECT THE FLOOR PLAN.
 SECTION 106.3.5.1.3(13).
  
 26. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 REQUIREMENTS FOR THE GAS PERMIT SHALL BE SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS INCLUDING CLEARANCES ARE REQUIRED.
  
 27. PLANS DO NOT APPEAR TO BE 100% COMPLETE AND MORE
 COMMENTS MAY BE FORTHCOMING ACCORDING TO COMMENT
 RESPONSES AND NEW INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 8 Status P Date 2009-07-07 Cont ID  
Sent By eschneid Date 2009-07-07 Time 12:04 Rev Time 1.00
Received By eschneid Date 2009-07-07 Time 12:04 Sent To  
Notes
2009-07-07 12:06:07NOTE - NEED A REVISED SHEET A-100 TO MATCH THE
 REVISIONS ON SHEETS A-101 & A-102.

Review Stop Z ZONING
Rev No 7 Status P Date 2008-12-18 Cont ID  
Sent By eschneid Date 2008-12-18 Time 15:36 Rev Time 0.00
Received By eschneid Date 2008-12-18 Time 15:36 Sent To  
Notes
2008-12-18 15:36:53SIGNS AND FENCES REQUIRE A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 6 Status F Date 2008-11-24 Cont ID  
Sent By adavila Date 2008-11-24 Time 14:05 Rev Time 0.00
Received By adavila Date 2008-11-24 Time 08:58 Sent To  
Notes
2008-11-24 14:06:58PLANNING AND ZONING DEPARTMENT
  
 ***FAILED PLAN REVIEW. PLANS SIGNED AND SEALED NOV. 11,
 2008 ARE OKAY***
  

Review Stop Z ZONING
Rev No 5 Status P Date 2008-10-09 Cont ID  
Sent By adavila Date 2008-10-09 Time 17:48 Rev Time 0.00
Received By adavila Date 2008-10-09 Time 17:48 Sent To L
Notes
2008-10-09 17:50:38PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 SEE PROVISOS ON ALL PLANS. ALL PROVISOS SHALL BE
 CORRECTED AT NEXT SUBMITTAL. FAILURE TO CORRECT ALL
 PROVISOS MAY RESULT IN FUTURE PLAN REVIEW FAILURE.
  
 ALL SIGNS, WALLS AND FENCES SHALL BE APPROVED ON A
 SEPARATE PERMIT.
  
  
 ***PLEASE NOTE LANDSCAPE REVIEW REQUIRED.***
  
  

Review Stop Z ZONING
Rev No 4 Status F Date 2008-10-09 Cont ID  
Sent By adavila Date 2008-10-09 Time 10:34 Rev Time 0.00
Received By adavila Date 2008-10-08 Time 08:17 Sent To L
Notes
2008-10-09 10:34:48PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO ALL THE REVIEW COMMENTS MADE BY
 THE PLANNING AND ZONING DEPARTMENT, TO INCLUDE ANY
 COMMENTS MADE PRIOR TO THIS PERMIT REVIEW STOP.
  
 2. REPEAT COMMENT - ALL PLANS SHALL SHOW SAME
 CONDITIONS, AND SHALL REFLECT THE CONDITIONS APPROVED
 PER THE SITE PLAN APPROVAL LETTER DATED JULY 8, 2008,
 PRIOR TO OBTAINING BUILDING PERMIT APPROVAL.
 A. PLEASE ENSURE THAT ALL PLANS AND DETAILS MATCH EACH
 OTHER, AND MATCH THE APPROVED SITE PLAN DATED JULY 8,
 2008. THERE ARE STILL SOME INSTANCES WHERE THE PLANS
 AND DETAILS DO NOT MATCH. EXAMPLES ARE THE PARKING
 STALL DETAILS, WHEEL STOP DETAILS, NEW PARKING ROW
 ALONG THE CIRCULAR DRIVEWAY (IN REGARDS TO DEPTH AND
 WIDTH), ETC.
  
 3. SHEETS NO. 2, 4 AND 6 SHOWS A NEW 2 FOOT WIDE
 CONCRETE PAD IN THE LANDSCAPE ISLAND BETWEEN THE
 EXISTING PARKING ROWS THAT IS NOT SHOWN IN ANY OF THE
 OTHER PLANS, NOR WAS IT SHOWN IN THE APPROVED SITE PLAN
 DATED JULY 8, 2008. PLEASE ADDRESS.
  
 4. ALL SIGNS, WALLS AND FENCES SHALL BE APPROVED ON A
 SEPARATE PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
2008-10-09 08:17:321 COPY OF PLANS IN ZONING FOR REVIEW.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2008-07-11 Cont ID  
Sent By adavila Date 2008-07-11 Time 15:47 Rev Time 0.00
Received By adavila Date 2008-07-11 Time 15:47 Sent To  
Notes
2008-07-11 15:47:34PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. ACCORDING TO THE SITE PLAN APPROVAL LETTER DATED
 JULY 8, 2008, THE FOLLOWING SHALL BE COMPLETED:
  
 A. A TYPE "D" CURB, OR A CURB OF SIMILAR DURABILITY,
 SHALL BE PROVIDED AROUND ALL TERMINAL LANDSCAPE
 ISLANDS.
 B. THE LANDSCAPE ISLAND TERMINATING THE NORTH END OF
 THE PARKING ROW ALONG THE CIRCULAR DRIVEWAY SHALL BE
 EXTENDED UP TO THE PARKING SPACE AS SHOWN ON THE
 GRADING, PAVING AND DRAINAGE PLAN (SHEET 4).
  
 C. THE POINTS OF THE PROPOSED FENCE AND GATES SHALL BE
 BLUNTED.
 D. MISCELLANEOUS DETAILS PLAN (SHEET A-605), PARKING
 STALL DETAILS SHALL BE REVISED TO SHOW 12 INCHES
 BETWEEN THE DOUBLE STRIPING PER THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), AND HANDICAP PARKING
 STALL DETAILS SHALL BE REVISED TO SHOW THE HANDICAP
 SYMBOL TWO (2) FEET FROM THE OPEN END OF THE PARKING
 SPACE.
 E. ALL ELECTRICAL, PHOTOMETRIC, MECHANICAL, STRUCTURAL,
 CIVIL AND MISCELLANEOUS PLANS SHALL SHOW THE SAME
 CONDITIONS, AND REVISED TO MATCH THE APPROVED SITE
 PLANS, AFTER THE CHANGE IN NO. 1(B) ABOVE IS MADE.
  
 2. THERE ARE A NUMBER OF PLANS THAT DO NOT MATCH.FOR
 EXAMPLE, SHEETS NOS. 3, 4, 5, 6 AND 13 DO NOT SHOW THE
 INTERIOR LANDSCAPE ISLAND IN THE NEW (2ND) PARKING ROW.
 ADDITIONALLY, SHEET NO. 13 SHOWS THE NEW HANDICAP
 PARKING SPACES IN THE WRONG LOCATION; SHEET NO. 8 SHOWS
 THE HANDICAP PARKING SPACE WITH 6 INCH DOUBLE STRIPES,
 AND 2 INCHES IN BETWEEN INSTEAD OF THE 4 INCH STRIPES
 WITH 12 INCHES IN BETWEEN AS REQUIRED PER THE ZLDRS
 (SEE COMMENT 1(D) ABOVE); SHEETS L-1.0, L-2.0, L-3.0,
 L-4.0, A-100, ETC., DOES NOT SHOW THE TERMINAL ISLAND
 EXTENDING TO THE PARKING SPACE AT THE NORTH END OF THE
 PARKING ROW ALONG THE CIRCULAR DRIVEWAY.ALL PLANS
 SHALL SHOW SAME CONDITIONS, AND SHALL REFLECT THE
 CONDITIONS APPROVED PER THE SITE PLAN APPROVAL LETTER
 DATED JULY 8, 2008, PRIOR TO OBTAINING BUILDING PERMIT
 APPROVAL.
  
 3. PLEASE NOTE THAT ALL SIGNS, WALLS AND FENCES SHALL
 BE APPROVED ON A SEPARATE PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-04-11 Cont ID  
Sent By adavila Date 2008-04-11 Time 08:09 Rev Time 0.00
Received By adavila Date 2008-04-09 Time 16:06 Sent To L
Notes
2008-04-11 08:09:38 
  
 PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. SITE PLAN APPROVAL SHALL BE OBTAINED PRIOR TO
 BUILDING PERMIT APPROVAL.
  
 2. PROVIDE A SITE DATA TABLE INDICATING THE FOLLOWING:
 A. TOTAL GROSS BUILDING SQUARE FOOTAGE (EXISTING VS.
 PROPOSED).ACCORDING TO THE BUILDING PERMIT (AND
 INFORMAL SITE PLAN REVIEW) APPLICATION(S), THE PROPOSED
 DEVELOPMENT IS A 10,000 SQUARE FOOT MULTIPURPOSE
 BUILDING; HOWEVER, THE SITE PLAN SHOWS A 7,991 SQUARE
 FOOT BUILDING.PLEASE ADDRESS.
 B. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE AND IMPERMEABLE SURFACE.
 C. FLOOR AREA RATIO (FAR).
  
 3. PROVIDE STANDARD CITY DETAILS OF PARKING (SMALL CAR,
 HANDICAP SPACE, STANDARD SPACE) MEETING THE ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 4. PROVIDE LOCATION, HEIGHT AND INTENSITY OF ALL
 OUTDOOR ILLUMINATION.PLEASE NOTE THAT GLARE SHALL NOT
 EXCEED 0.5 FOOT CANDLE AT OR BEYOND THE NORTH PROPERTY
 LINE.
  
 5. PURSUANT TO SECTION 94-443(C)(3)(B), ONE INTERIOR
 LANDSCAPE ISLAND SHALL BE PROVIDED FOR EVERY TEN
 PARKING SPACES OR FRACTION THEREOF.INTERIOR LANDSCAPE
 ISLANDS SHALL BE AT LEAST FIVE FEET WIDE OF LANDSCAPING
 AND SHALL CONTAIN AT LEAST ONE SHADE OR FLOWERING TREE.
 AN INTERIOR LANDSCAPE ISLAND SHALL BE PLACED ON THE
 PARKING ROWS ON THE EAST HALF OF THE PARKING LOT.
  
 6. PER SECTION 94-443(C)(5)(B), WHEEL STOPS SHALL HAVE
 A MINIMUM HEIGHT OF SIX INCHES ABOVE THE FINISHED GRADE
 OF THE PARKING AREA.WHEEL STOPS SHALL BE TWO FEET
 FROM THE CURB TO THE BACK OF THE WHEEL STOP.
  
 7. PROVIDE WIDTH AND DEPTH DIMENSIONS OF ALL DRIVE
 AISLES.PLEASE NOTE THAT PER SECTION 94-485(J)(2), 90
 DEGREE PARKING SPACES AND TWO-WAY DRIVE AISLES SHALL
 HAVE A DRIVE AISLE OF A MINIMUM OF 24 FEET.
  
 8. PURSUANT TO SECTION 94-485(Q)(1), ONE BICYCLE
 PARKING SPACE SHALL BE PROVIDED FOR EVERY 10 AUTOMOBILE
 PARKING SPACES.PROVIDE DETAILS AND LOCATION OF THE
 BICYCLE PARKING SPACES MEETING THE DESIGN STANDARDS
 OUTLINED IN SECTION 94-485(Q)(2).
  
 9. THERE IS A DISCREPANCY BETWEEN THE LANDSCAPE PLAN
 AND SITE PLAN.ACCORDING TO THE LANDSCAPE PLAN, THE
 AREA BETWEEN THE PARKING ROW AND THE SEMI-CIRCULAR
 DRIVEWAY WILL BE A LANDSCAPED AREA.HOWEVER, SITE PLAN
 SHOWS THE WESTERN PORTION TO BE A SIDEWALK AND THE
 REMAINING AS LANDSCAPED.PLEASE REVISE.ALL PLANS
 SHALL SHOW SAME CONDITIONS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA D?VILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
2008-04-09 16:07:011 COPY IN ZONING FOR REVIEW.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By adavila Date 2007-10-22 Time 16:26 Rev Time 0.00
Received By adavila Date 2007-10-19 Time 13:43 Sent To  
Notes
2007-10-22 16:27:03PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE SUBMITTED PLANS SHOW RENOVATION OF THE EXISTING
 FACILITY PLUS A NEW ADDITION.PURSUANT TO SECTION
 94-35(D)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, ATTACHED OR DETACHED ADDITIONS OF 1,000 OR
 MORE GROSS SQUARE FEET TO AN EXISTING NONRESIDENTIAL
 STRUCTURE REQUIRES AN INFORMAL SITE PLAN APPROVAL PRIOR
 TO BUILDING PERMIT APPROVAL.PLEASE CONTACT THE
 PLANNING AND ZONING DEPARTMENT TO OBTAIN A DEVELOPMENT
 APPLICATION.
  
 2. PLEASE NOTE THAT IF ANY TREES ARE TO BE REMOVED
 AND/OR RELOCATES, A TREE ALTERATION PERMIT IS REQUIRED.
 TREE ALTERATION PERMIT MAY BE OBTAINED FROM THE
 PLANNING AND ZONING DEPARTMENT.
  
 COMMENT/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved