Plan Review Details - Permit 07090837
Plan Review Stops For Permit 07090837
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By shill Date 2007-10-22 Time 17:24 Rev Time 0.00
Received By shill Date 2007-10-22 Time 17:24 Sent To  
Notes
2007-10-22 17:25:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE A REASONABLE VALUE FOR THIS JOB.
  
 2.PROVIDE ALL INFORMATION FOR THE BABY BARRIER TO
 SHOW CODE COMPLIANCE OR A SEPARATE PERMIT WILL BE
 REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By btrobaug Date 2007-10-09 Time 13:53 Rev Time 0.00
Received By btrobaug Date 2007-10-09 Time 13:04 Sent To P
Notes
2007-10-09 13:52:59 
  
 DENIED/INCOMPLETE INFORMATION
  
 PROVIDE A LOAD CALCULATION FOR THE ELECTRICALSERVICE
 INCLUDING ALL LOADS TO BE ADDED UNDER THIS PERMIT.
 INDICATE THE SIZE OF THE EXISTING SERVICE. 215.5 NEC,
 2005.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 10:51 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 10:51 Sent To B
Notes
2007-10-16 10:52:03NOTE: HEATER IS AN ELECTRIC HEAT PUMP.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-22 Cont ID  
Sent By shill Date 2007-10-22 Time 17:25 Rev Time 0.00
Received By shill Date 2007-09-28 Time 16:03 Sent To  
Notes
2007-09-28 16:03:34TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 10:47 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 10:47 Sent To G
Notes
2007-10-16 10:51:06DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, SECTIONS 424.2 &
 R4101 SWIMMING POOLS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 2. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 3. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-04 Cont ID  
Sent By choops Date 2007-10-04 Time 08:39 Rev Time 0.00
Received By choops Date 2007-10-04 Time 08:39 Sent To E
Notes
2007-10-04 08:42:45***FAILED***
  
  
 1)POOL EQUIPMENT PROJECTS TOO FAR INTO REQUIRED REAR
 SETBACK.PURSUANT TO SECTION 94-305(B)(4) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS:MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4' INTO A REQUIRED
 SETBACK.THERE IS A REQUIRED REAR SETBACK OF 13.4'
 FROM THE PRINCIPAL STRUCTURE, MINUS THE 4' ALLOWABLE
 ENCROACHMENT, YIELDS A REQUIRED REAR SETBACK OF 9.4' TO
 THE POOL EQUIPMENT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720