Plan Review Details - Permit 07090784
Plan Review Stops For Permit 07090784
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-08 Cont ID  
Sent By mjacobs Date 2007-11-09 Time 07:15 Rev Time 0.00
Received By mjacobs Date 2007-11-08 Time 06:18 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By mjacobs Date 2007-10-09 Time 10:59 Rev Time 0.00
Received By mjacobs Date 2007-10-09 Time 09:55 Sent To  
Notes
2007-10-09 10:59:49 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07090784
 ADD: 650 OKEECHOBEE BLVD
 CONT: M.A.C. CONST. INC.
 TEL: (305)598-4317
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING &
 FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 . -------------------------------------
 ) SQ. FT. FOOTPRINT
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-07 Cont ID  
Sent By btrobaug Date 2007-11-07 Time 08:56 Rev Time 0.00
Received By btrobaug Date 2007-11-07 Time 07:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-10-05 Cont ID  
Sent By btrobaug Date 2007-10-05 Time 12:26 Rev Time 0.00
Received By btrobaug Date 2007-10-05 Time 12:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-08 Cont ID  
Sent By mawillia Date 2007-11-08 Time 14:58 Rev Time 0.00
Received By mawillia Date 2007-11-08 Time 14:45 Sent To  
Notes
2007-11-08 14:54:12*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET A-1 STAMPED, INITIALED, AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By mawillia Date 2007-10-11 Time 15:34 Rev Time 0.00
Received By mawillia Date 2007-10-11 Time 15:07 Sent To  
Notes
2007-10-11 15:34:26DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.PLEASE INDICATE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET THE SCOPE OF WORK AREA AS TO
 BETTER IDENTIFY PROJECT SITE LOCATION.I.E.1ST
 FLOOR,TENANT/UNIT SPACE
  
 3.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED
  
 4.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5.WILL THE ERECTION OF THE WALL IMPACT ANY FIRE
 SPRINKLERS/FIRE ALARM DEVICES IN THE PROJECT SCOPE
 AREA?IF SO, SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FOR THE MODIFICATION.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 14:25 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 14:25 Sent To  
Notes
2007-11-05 10:46:18TO "COMM" BD#13
2007-10-30 14:25:48WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-11 Cont ID  
Sent By mawillia Date 2007-10-11 Time 15:07 Rev Time 0.00
Received By mawillia Date 2007-09-28 Time 10:52 Sent To  
Notes
2007-10-03 16:41:07TO "BOB"#3
2007-09-28 10:55:10WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-06 Cont ID  
Sent By tgordon Date 2007-11-06 Time 14:41 Rev Time 0.20
Received By tgordon Date 2007-11-06 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By tgordon Date 2007-10-11 Time 08:38 Rev Time 0.20
Received By tgordon Date 2007-10-11 Time 08:38 Sent To  
Notes
2007-10-11 08:44:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SHOW THE SIZE OF THE RETURN AIR TRANSFER
 DUCT (FLEX), SEE 2004 FBC/M 601.4.
  
 2) NEED TO PROVIDE SUPPLY AIR TO OFFICE, SEE 2004 FBC/M
 401.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]