Plan Review Details - Permit 07090773
Plan Review Stops For Permit 07090773
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-11 Cont ID  
Sent By mjacobs Date 2008-01-11 Time 07:35 Rev Time 0.00
Received By mjacobs Date 2008-01-11 Time 06:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-16 Cont ID  
Sent By mjacobs Date 2007-11-16 Time 17:58 Rev Time 0.00
Received By mjacobs Date 2007-11-16 Time 16:51 Sent To  
Notes
2007-11-16 18:22:13 
 BUILDING PLAN REVIEW
 PERMIT: 07090773
 ADD: 2101 CENTREPARK BLVD SUITE110-115
 CONT:
 TEL: (561)682-6472
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND11/16/07
 ACTION: DENIED
  
 1A) OK
 1B) OK
 1C) OK
 2)OK
 3)OK
 4)OK
 5)OK
 6)OK
  
 **NEW** UNTIL A CONTRACTOR IS SIGNED ON THE APPLICATION
 AND A PERMIT IS APPLIED FOR, THE PROJECT WILL REMAIN IN
 A FAIL STATUS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-09 Cont ID  
Sent By mjacobs Date 2007-10-09 Time 09:16 Rev Time 0.00
Received By mjacobs Date 2007-10-09 Time 05:56 Sent To  
Notes
2007-10-09 09:16:42 
 BUILDING PLAN REVIEW
 PERMIT: 07090773
 ADD: 2101 CENTREPARK BLVD SUITE110-115
 CONT:
 TEL: (561)682-6472
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL
 VOID SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM
 LOOSELY ON TOP OF THE COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 . -------------------------------------
 ) SQ. FT. FOOTPRINT
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 4)MEANS OF EGRESS: A CONTINUOUS AND UNOBSTRUCTED WAY
 OF TRAVEL FROM ANY POINT IN A BUILDING OR STRUCTURE TO
 A PUBLIC WAY, CONSISTING OF THREE SEPARATE AND DISTINCT
 PARTS: (1) THE WAY OF THE EXIT ACCESS, (2) THE EXIT,
 AND (3) THE WAY OF THE EXIT DISCHARGE. A MEANS OF
 EGRESS COMPRISES THE VERTICAL AND HORIZONTAL WAYS OF
 TRAVEL AND INCLUDE THE INTERVENING ROOM SPACE, DOORS
 CORRIDORS, PASSAGEWAYS, BALCONIES, STAIRS, RAMPS,
 ENCLOSURES, LOBBIES, HORIZONTAL EXITS, COURTS AND
 YARDS. SHOW THIS INFORMATION ON THE LIFE SAFETY PLAN.
  
 5)PROVIDE ARCHITECTURAL DRAWINGS OF AN EXISTING AND A
 PROPOSED FLOOR PLAN INDICATING ALL CHANGES ON THE
 DRAWINGS.
  
 6)ON SHEET M-3 IN REFERENCE TO NOTE #1, ARE THE
 DOUBLE DOORS BEING REPLACED OR A NEW OPENING IS CREATED
 FOR THE DOUBLE DOORS?CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED. FBC.106.1.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-10 Cont ID  
Sent By btrobaug Date 2008-01-10 Time 07:33 Rev Time 0.00
Received By btrobaug Date 2008-01-10 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-14 Cont ID  
Sent By btrobaug Date 2007-11-14 Time 11:19 Rev Time 0.00
Received By btrobaug Date 2007-11-14 Time 07:50 Sent To  
Notes
2007-11-14 11:27:45 
  
  
  
 ELECTRIC OK, FAILED UNTILL CONTRACTOR APPLIES./WRT.
 THE ROOM BEING ALTERED IS TO SUPPORT THE PHONE SYSTEM
 NOT COMPUTER EQUIPMENT PER CRAIG NYHUIS./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-05 Cont ID  
Sent By btrobaug Date 2007-10-05 Time 11:49 Rev Time 0.00
Received By btrobaug Date 2007-10-05 Time 11:20 Sent To  
Notes
2007-10-05 11:49:35 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
 ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} 645.10 DISCONNECTING MEANS
 A MEANS SHALL BE PROVIDED TO DISCONNECT POWER TO ALL
 ELECTRONIC EQUIPMENT IN THE INFORMATION TECHNOLOGY
 EQUIPMENT ROOM. THERE SHALL ALSO BE A SIMILAR MEANS TO
 DISCONNECT THE POWER TO ALL DEDICATED HVAC SYSTEMS
 SERVING THE ROOM AND CAUSE ALL REQUIRED FIRE/SMOKE
 DAMPERS TO CLOSE. THE CONTROL FOR THESE DISCONNECTING
 MEANS SHALL BE GROUPED AND IDENTIFIED AND SHALL BE
 READILY ACCESSIBLE AT THE PRINCIPAL EXIT DOORS. THE UPS
 DISCONNECT DOES NOT COMPLY WITH THIS ARTICLE. SHEET
 E-2.
  
 2} 645.4(3) LISTED INFORMATION TECHNOLOGY EQUIPMENT IS
 INSTALLED. PROVIDE THE LISTING AND MANUFACTURERS
 SPECIFICATIONS FOR THE UPS SHOWN ON SHEET E-2.
  
 3} 645.4 (5) THE ROOM IS SEPARATED FROM OTHER
 OCCUPANCIES BY FIRE-RESISTANT-RATED WALLS, FLOORS, AND
 CEILINGS WITH PROTECTED OPENINGS. PROVIDE DETAILS
 INDICATING COMPLIANCE WITH THIS ARTICLE.
  
 4} SHEET E-4 INDICATES THE FEED TO THE IT PANEL BEING
 4-#3/0, WITH A #8 EQUIPMENT GROUND. THE PANEL IS LISTED
 AS SINGLE PHASE THREE WIRE. CORRELATE THE FEED
 CONDUCTORSWITH THE PANEL RATING.
  
 5} THE EQUIPMENT GROUNDING CONDUCTOR RAN WITH THE
 FEEDER TO THE IT PANEL,MUST COMPLY WITH 250.122,
 MINIMUM #6.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-01-10 Cont ID  
Sent By mawillia Date 2008-01-10 Time 13:21 Rev Time 0.00
Received By mawillia Date 2008-01-10 Time 13:13 Sent To  
Notes
2008-01-10 13:19:16**********
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A-2 AND E-3 WERE STAMPED,
 INITIALED, AND DATED ON 11/18/2007.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-19 Cont ID  
Sent By mawillia Date 2007-11-19 Time 11:08 Rev Time 0.00
Received By mawillia Date 2007-11-19 Time 10:46 Sent To  
Notes
2007-11-19 11:03:25*****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A-2 AND E-3 WERE STAMPED,
 INITIALED, AND DATED.
  
 PROJECT WILL REMAIN IN A FAIL STATUS UNTIL A CONTRACTOR
 IS SIGNED AND A PERMIT IS IN THE APPLICATION
 PROCESS!!!!!!!!!!
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-12 Cont ID  
Sent By mawillia Date 2007-10-12 Time 07:39 Rev Time 0.00
Received By mawillia Date 2007-10-11 Time 15:40 Sent To  
Notes
2007-10-12 08:54:07*****UNSAT*****
  
  
 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE ADDRESS
 LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.ON SHEET E-3, THERE IS AN EXISTING EXIT LIGHT IN
 THE NORTH END OF THE MAIN CORRIDOR THAT DIRECTS
 PERSON(S) TO EITHER DIRECTION FOR EXITING.WHERE IS
 THE MEANS OF EGRESS GOING NORTH?
  
 5.ON SHEET E-3,THERE IS AN EXISTING EXIT LIGHT AT
 THE EASTERN MOST END OF A CORRIDOR. PLEASE INDICATE
 WHERE THIS EXIT LIGHT IS DIRECTING PERSON(S) TO EXIT.
  
 6.SHOW LOCATION OF THE EMERGENCY LIGHTS FOR THIS
 TENANT SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-08 Cont ID  
Sent By shill Date 2008-01-08 Time 15:43 Rev Time 0.00
Received By shill Date 2008-01-08 Time 15:43 Sent To  
Notes
2008-01-08 15:45:03TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 12:59 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 12:59 Sent To  
Notes
2007-11-13 08:58:37TO "BOB"#5
2007-11-08 12:59:46WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-11 Cont ID  
Sent By mawillia Date 2007-10-11 Time 15:40 Rev Time 0.00
Received By mawillia Date 2007-09-28 Time 14:07 Sent To  
Notes
2007-10-03 16:43:57TO "BOB"#16
2007-09-28 14:13:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-09 Cont ID  
Sent By tgordon Date 2008-01-09 Time 12:27 Rev Time 0.25
Received By tgordon Date 2008-01-09 Time 12:27 Sent To  
Notes
2008-01-09 12:28:12FOR PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-11 Cont ID  
Sent By tgordon Date 2007-10-11 Time 09:00 Rev Time 0.25
Received By tgordon Date 2007-10-11 Time 09:00 Sent To  
Notes
2007-10-11 09:04:01IN FOR PLAN REVIEW ONLY NOT FOR PERMIT.
  
 ** PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLANS ARE O.K. AT THIS TIME A CONTRACTOR
 WILL NEED TO SIGN ON AND APPLY FOR A PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  