Plan Review Details - Permit 07090772
Plan Review Stops For Permit 07090772
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-08 Cont ID  
Sent By shill Date 2007-11-08 Time 12:02 Rev Time 0.00
Received By shill Date 2007-11-08 Time 12:02 Sent To  
Notes
2007-11-08 12:02:58**PROVISO**
  
 1.SUBMIT CALCS IN ACCORDANCE WITH FAC61G15 WITH NO
 ERRORS,
  
 OR
  
 2.REVISE TITLE SHEET TO REMOVE CALCS FROM PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-08 Cont ID  
Sent By shill Date 2007-11-08 Time 07:28 Rev Time 0.00
Received By shill Date 2007-11-08 Time 07:28 Sent To  
Notes
2007-11-08 07:55:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 5.FOR THE CALCULATIONS, ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS REQUIRED AND EITHER EACH SHEET IS TO
 BE SIGNED, SEALED, AND DATED OR AN INDEX SHEET IN
 COMPLIANCE WITH FAC61G15-23 IS TO BE USED.
  
 2ND REVIEW, NOT ADDRESSED.PLEASE CONTACT ME IF YOU
 NEED ASSISTANCE.
  
 7.THE SECOND SHEET, THIRD SHEET, AND OTHER SHEETS
 HAVE "#VALUE!" IN A BOX WHERE THERE SHOULD BE A NUMBER.
 THIS APPEARS TO BE AN ERROR MESSAGE GENERATED BY THE
 SOFTWARE.EITHER PREPARE CALCULATIONS WITHOUT THESE
 ERROR MESSAGES OR INCLUDE A LETTER CLARIFYING WHY THIS
 A PART OF THE CALCULATIONS, WHAT THIS MEANS, AND
 RELEVANCE TO THIS JOB.
  
 2ND REVIEW; ENGINEER WROTE A LETTER STATING THAT THIS
 IS AN EXCEL SIZE OF CELL ERROR.I DO NOT BELIEVE THIS
 IS CORRECT; THIS ERROR OCCURS WHEN THERE IS AN
 INCOMPATIBILITY OF FORMAT TYPES, USUALLY INCLUDING A
 TEXT FORMATTED CELL IN THE FORMULA.THIS CAN BE FIXED
 BY REVISING THE FORMULA.PLEASE CONTACT ME IF YOU NEED
 ASSISTANCE.ALSO, EVEN IF IT IS A SIZE ERROR, THIS
 COULD BE CORRECTED BY FORMATTING TO INCLUDE LESS
 NUMBERS AFTER THE DECIMAL AS THIS FIELD SHOULD BE IN
 THE SAME NUMBER RANGE AS THE OTHER NUMBERS (THEREFORE,
 SHOULD FIT THE CELL).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By shill Date 2007-10-18 Time 12:50 Rev Time 0.00
Received By shill Date 2007-10-18 Time 12:50 Sent To  
Notes
2007-10-18 13:31:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE SEE FBC CHAPTER 35; CORRECT ASCE VERSION IS
 ASCE7-02.REVISE PLANS AND CALCULATIONS.
  
 2.DESIGN CRITERIA STATES THAT THIS IS LATERAL DESIGN
 CRITERIA (SHEET 1).WIND DESIGN CRITERIA IS REQUIRED
 FBC1603.1.4.PLEASE CLARIFY HOW LATERAL LOADS APPLY TO
 THE INFORMATION PROVIDED ON THE PLAN.
  
 3.SHEET 2 OF 13 REFERS TO NOA 04-1123.01, BUT
 05-0110.01 WAS SUBMITTED.EITHER REVISE THE PLAN OR
 PROVIDE THE REFERENCED NOA.
  
 4.A LOCAL PRODUCT APPROVAL WAS REQUESTED AND ISSUED
 FOR NOA05-1220.16.A LOCAL PRODUCT APPROVAL WAS
 REQUESTED FOR NOAS 05-0110.01 AND 04-0331.02.SEE THE
 BOTTOM LEFT CORNER OF SHEET 1 OF 5, "A 33% INCREASE IN
 ALLOWABLE STRESS WAS USED IN DESIGN OF ANCHORS."THIS
 IS NOT COMPLIANY WITH THE FLORIDA BUILDING CODE,
 FBC1605.3.1.1(2), BUT WAS PREVIOUSLY ALLOWED UNDER THE
 SOUTH FLORIDA BUILDING CODE.THIS COMMENT MAY BE
 ADDRESSED IN ONE OF THE FOLLOWING WAYS:
  
 A.A LETTER STATING THAT ANCHORING WITHOUT THE 33%
 STRESS INCREASE HAS BEEN PERFORMED, REVISE ANCHORING
 ACCORDINGLY.THIS MAY BE DONE BY THE ENGINEER FOR THE
 PROJECT, THE ENGINEER ON THE PRODUCT APPROVAL, OR OTHER
 QUALIFIED DESIGN PROFESSIONAL
  
 B.PROVIDE AN ALTERNATE PRODUCT WHICH IS COMPLIANT
 WITH FAC9B72 (PRODUCT APPROVAL RULE).IF THE PRODUCT
 IS REVISED, APPROVAL BY THE DESIGNER OF RECORD IS
 REQUIRED FBC*106.3.3.
  
 C.ALTERNATE METHOD OF SHOWING CODE COMPLIANCE CAN BE
 PROPOSED AND FEEL FREE TO CONTACT ME TO DISCUSS.
  
 5.FOR THE CALCULATIONS, ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS REQUIRED AND EITHER EACH SHEET IS TO
 BE SIGNED, SEALED, AND DATED OR AN INDEX SHEET IN
 COMPLIANCE WITH FAC61G15-23 IS TO BE USED.
  
 6.THE CALCULATIONS DO NOT HAVE PAGE NUMBERS. ALTHOUGH
 NOT REQUIRED, LACK OF PAGE NUMBERS MAKES IT DIFFICULT
 TO REFER TO PAGES (SEE ITEM 7).
  
 7.THE SECOND SHEET, THIRD SHEET, AND OTHER SHEETS
 HAVE "#VALUE!" IN A BOX WHERE THERE SHOULD BE A NUMBER.
 THIS APPEARS TO BE AN ERROR MESSAGE GENERATED BY THE
 SOFTWARE.EITHER PREPARE CALCULATIONS WITHOUT THESE
 ERROR MESSAGES OR INCLUDE A LETTER CLARIFYING WHY THIS
 A PART OF THE CALCULATIONS, WHAT THIS MEANS, AND
 RELEVANCE TO THIS JOB.
  
 8.SEE DETAIL 20/9, 19/9 ON SHEET 10, AS WELL AS OTHER
 DETAILS ON OTHER SHEETS.WHAT DOES "@ 6" REST" MEAN?
 ANCHOR SPEC IS NOT CLEAR.
  
 9.SEE DETAIL 20/9, 19/9 ON SHEET 10, DETAIL **/6 ON
 SHEET 7, AS WELL AS OTHER DETAILS ON OTHER SHEETS.THE
 STANDARD IS THAT THE BOTTOM NUMBER IS THE PAGE, BUT
 THIS DETAIL IS ON SHEET 10 RATHER THAN SHEET 9.
  
 10.AS THE PRODUCTS ARE NOT COMPLIANT FOR THE WORST
 CASE DESIGN PRESSURE ON THE DESIGN PRESSURE CHART,
 PROVIDE A SCHEDULE OF OPENINGS WITH REQUIRED DESIGN
 PRESSURE.YOU PROVIDED A GENERIC CHART FOR DESIGN
 PRESSURES BASED ON SIZE AND ZONE, BUT NO SIZES OR
 LOCATIONS FOR OPENINGS.GENERALLY, IF THE PRODUCT
 APPROVALS SUBMITTED DO NOT MEET THE WORST CASE DP, A
 SCHEDULE IS REQUIRED TO EXPEDITE PLAN REVIEW.
  
 11.PROVIDE LOCATION AND TYPES OF PRODUCTS BEING
 INSTALLED.NO INFORMATION PROVIDED OTHER THAN PRODUCT
 APPROVAL NUMBERS.THE FLOOR PLANS HAVE REFERENCE
 LETTERS AT OPENINGS BUT NO SIZES OR TYPE (DOOR, WINDOW,
 OR SGD) PER OPENING AND THE LETTERS DO NOT CORRELATE
 WITH ANYTHING.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 09:53 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 09:53 Sent To B
Notes
2007-11-02 09:53:25TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-18 Cont ID  
Sent By shill Date 2007-10-18 Time 13:40 Rev Time 0.00
Received By shill Date 2007-09-27 Time 11:16 Sent To  
Notes
2007-09-27 11:21:27TO "MISC" BOX#1