Plan Review Details - Permit 07090747
Plan Review Stops For Permit 07090747
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-04-10 Cont ID  
Sent By mjacobs Date 2008-04-10 Time 15:41 Rev Time 0.00
Received By mjacobs Date 2008-04-10 Time 12:16 Sent To  
Notes
2008-04-10 15:41:27BUILDING PLAN REVIEW
 PERMIT: 07090747
 ADD: 307 EVERNIA STREET #100
 CONT: G3 CONST.
 TEL: (561)393-3939
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-10-08
 REVIEW: REVISION
 ACTION: DENIED
  
 NOTE: THESE NOTES ARRE IN REFERENCE TO THE EXHAUST WALL
 CAP WITH WMS ON SHEET M1.1
  
 1)FBC 1403.2 THE EXTERIOR WALL ENVELOPE SHALL BE
 DESIGNED AND CONSTRUCTED IN SUCH A MANNER AS TO PREVENT
 THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY
 PROVIDING A WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR
 VENEER, AS DESCRIBED IN SECTION 1404.2 AND A MEANS FOR
 DRAINING WATER THAT ENTERS THE ASSEMBLY TO THE EXTERIOR
 OF THE VENEER, UNLESS IT IS DETERMINED THAT PENETRATION
 OF WATER BEHIND THE VENEER SHALL NOT BE DETRIMENTAL TO
 THE BUILDING PERFORMANCE.
  
 2)FBC 1203. NATURAL VENTILATION OF AN OCCUPIED SPACE
 SHALL BE THROUGH WINDOWS, DOORS, LOUVERS OR OTHER
 OPENINGS TO THE OUTDOORS. THE OPERATING MECHANISM FOR
 SUCH OPENINGS SHALL BE PROVIDED WITH READY ACCESS SO
 THAT THE OPENINGS ARE READILY CONTROLLABLE BY THE
 BUILDING OCCUPANTS.
  
 3)1609.1.4 (5.) LOUVERS PROTECTING INTAKE AND EXHAUST
 VENTILATION DUCTS NOT ASSUMED TO BE OPEN THAT ARE
 LOCATED WITHIN 30 FEET OF GRADE SHALL MEET REQUIREMENTS
 OF THE LARGE MISSILE TEST.
 IMPACT-RESISTANT COVERINGS SHALL BE TESTED AT 1.5 TIMES
 THE DESIGN PRESSURE (POSITIVE OR NEGATIVE) EXPRESSED IN
 POUNDS PER SQUARE FEET AS DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING SECTION 1609 FOR WHICH THE
 SPECIMEN IS TO BE TESTED.
  
 4)PROVIDE PRODUCT APPROVAL FOR THE LOUVER PER DCA
 RULE 9B-72, WHICH STATES ?THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL.
 SUBMIT TWO COPIES OF PRODUCT APPROVAL FOR THE LOUVER
 AND SHOW HOW IT WILL PREVENT WATER INTRUSION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2008-02-15 Cont ID  
Sent By mjacobs Date 2008-02-15 Time 07:34 Rev Time 0.00
Received By mjacobs Date 2008-02-15 Time 06:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-10 Cont ID  
Sent By mjacobs Date 2008-01-10 Time 14:40 Rev Time 0.00
Received By mjacobs Date 2008-01-10 Time 14:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-21 Cont ID  
Sent By mjacobs Date 2007-12-19 Time 17:16 Rev Time 0.00
Received By mjacobs Date 2007-12-19 Time 15:56 Sent To  
Notes
2007-12-21 08:54:40BUILDING PLAN REVIEW
 PERMIT: 07090747
 ADD: 307 EVERNIA ST
 CONT: RIZNICK CONSTRUCTION CORP.
 TEL: (561) 584-0363
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/2006 AND 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
 12/19/07
  
 1A)
  
 1B) OK
 1D) OK
 1E) OK
 2)OK
 3)OK
  
 **NO RESPONSE NOT ADDRESSED**
 4)PROVIDE THE WALL DETAIL OF EACH WALL ENCLOSING THE
 NEW SERVER ROOM AND SUBMIT THE UL LISTING OF THE WALLS
 AND THE MANUFACTURE SPECS FOR THE FIRE RATED DOOR. A
 WALL LEGEND WILL BE HELPFUL TO IDENTIFY EACH TYPE OF
 WALL. THE FLOOR AND UNIT NUMBER OF THE PROJECT SHALL BE
 INDICATING ON THE APPLICATION AND EACH SHEET OF THE
 DRAWINGS. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE, AND EXTENT OF
 THE WORK PROPOSED. WPB AMENDMENTS 106.1.1. **THE DETAIL
 FOR THE EXTENSION OF THE EXISTING WALL TO THE SLAB
 ABOVE SHALL BE SHOWN ON THE DRAWINGS.
  
 **NEW**
 THE DRAWINGS SUBMITTED ARE NOT SIGN, DATED OR SEAL BY
 THE ARCHITECT. ALL FINAL CONSTRUCTION DOCUMENTS,
 DRAWINGS, PLANS AND SPECIFICATIONS, OR REPORTS PREPARED
 OR ISSUED BY THE REGISTERED ARCHITECT SHALL BEAR THE
 SIGNATURE AND SEAL OF THE REGISTERED ARCHITECT WHO
 PREPARED OR APPROVED THE DOCUMENT AND THE DATE ON WHICH
 THEY WERE SEALED. THE SIGNATURE, DATE, AND SEAL SHALL
 BE EVIDENCE OF THE AUTHENTICITY OF THAT TO WHICH THEY
 ARE AFFIXED. FLORIDA STATUTES 481.221
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-27 Cont ID  
Sent By mjacobs Date 2007-11-27 Time 10:09 Rev Time 0.00
Received By mjacobs Date 2007-11-27 Time 06:36 Sent To  
Notes
2007-11-28 09:51:12 
 BUILDING PLAN REVIEW
 PERMIT: 07090747
 ADD: 307 EVERNIA ST
 CONT: RIZNICK CONSTRUCTION CORP.
 TEL: (561) 584-0363
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/2006 AND 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 11/27/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) OK
 1D) OK
 1E) OK
 2)OK
  
 **NO RESPONSE NOT ADDRESSED**
 3)PROVIDE A DETAIL ELEVATION DRAWING OF THE MOUNTING
 UNIT RACKS AND SHOW HOW THE RACKS WILL BE ATTACHED TO
 EXISTING FLOOR. STATE CLEARLY ON THE DETAIL DRAWING
 WHAT MATERIALS WILL BE USED TO CONSTRUCT THE MOUNTING
 RACKS.ADDITIONAL DETAILS INFORMATION IS REQUIRED FOR
 THE NEW SEVER RACKS WHERE THE UNITS WILL BE 18 INCHES
 OFF THE FLOOR. WPB AMENDMENTS SECTION 106.1.2.
 **NO RESPONSE NOT ADDRESSED**4)PROVIDE THE WALL
 DETAIL OF EACH WALL ENCLOSING THE NEW SERVER ROOM AND
 SUBMIT THE UL LISTING OF THE WALLS AND THEMANUFACTURE
 SPECS FOR THE FIRE RATED DOOR. A WALL LEGEND WILL BE
 HELPFUL TO IDENTIFY EACH TYPE OF WALL. THE FLOOR AND
 UNIT NUMBER OF THE PROJECT SHALL BE INDICATING ON THE
 APPLICATION AND EACH SHEET OF THE DRAWINGS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE, AND EXTENT OF THE
 WORK PROPOSED. WPB AMENDMENTS 106.1.1.
  
 **NEW**
 THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS LOW.
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST EXCLUDING
 LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3FBC*
 NOTE: THIS NEW ROOM NEEDS A 1 HOUR FIRE SEPERATION FROM
 OTHER ROOMS. SEE ELECTRICAL NOTE #4. THE 1HOUR RATED
 NOTE WAS REMOVED FROM THE NEW SETS OF DRAWINGS. GIVE AN
 EXPLAINATION WHY.
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-17 Cont ID  
Sent By mjacobs Date 2007-10-17 Time 16:14 Rev Time 0.00
Received By mjacobs Date 2007-10-17 Time 07:13 Sent To  
Notes
2007-10-17 16:14:30 
 BUILDING PLAN REVIEW
 PERMIT: 07090747
 ADD: 307 EVERNIA ST
 CONT: RIZNICK CONSTRUCTION CORP.
 TEL: (561) 584-0363
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/2006 AND 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 10/17/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)PROVIDE A DETAIL ELEVATION DRAWING OF THE MOUNTING
 UNIT RACKS AND SHOW HOW THE RACKS WILL BE ATTACHED TO
 EXISTING FLOOR. STATE CLEARLY ON THE DETAIL DRAWING
 WHAT MATERIALS WILL BE USED TO CONSTRUCT THE MOUNTING
 RACKS.ADDITIONAL DETAILS INFORMATION IS REQUIRED FOR
 THE NEW SEVER RACKS WHERE THE UNITS WILL BE 18 INCHES
 OFF THE FLOOR. WPB AMENDMENTS SECTION 106.1.2.
  
 4)PROVIDE THE WALL DETAIL OF EACH WALL ENCLOSING THE
 NEW SERVER ROOM AND SUBMIT THE UL LISTING OF THE WALLS
 AND THE MANUFACTURE SPECS FOR THE FIRE RATED DOOR. A
 WALL LEGEND WILL BE HELPFUL TO IDENTIFY EACH TYPE OF
 WALL. THE FLOOR AND UNIT NUMBER OF THE PROJECT SHALL BE
 INDICATING ON THE APPLICATION AND EACH SHEET OF THE
 DRAWINGS. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE, AND EXTENT OF
 THE WORK PROPOSED. WPB AMENDMENTS 106.1.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-04-09 Cont ID  
Sent By dpalmer Date 2008-04-09 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2008-04-09 Time 12:27 Sent To  
Notes
2008-04-09 12:27:45** DENIED REVIEW**
  
 ** PLANS PLACED ON COMM BOARD ON 4/9
  
 1) NOTE: SUBMITTED REVISIONS WERE COUNTER TO BE ONLY
 ONE SHEET HOWEVER THERE WERE FOUR SHEETS IN SETS
 SUBMITTED SETS. WILL OWE $30.00 ADDITIONAL FEE.
  
 2) NOTE: PLEASE BE SURE TO SUBMIT ANY REVISIONS FOR
 LAYOUTS AND EQUIPMENT IN ELECTRICAL PLANS DONE BY THE
 ENGINEER OF RECORD.
 NO ELECTRICAL PLANS SUBMITTED AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-08 Cont ID  
Sent By dpalmer Date 2008-01-08 Time 12:22 Rev Time 0.00
Received By dpalmer Date 2008-01-08 Time 12:22 Sent To  
Notes
2008-01-08 12:30:52SPECS SUBMITTEDARE NOT THE MTS AS STATED ON PLANS.
 PLANS PASSED PENDING CONFIRMATION FROM ENGINEER.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-01-07 Cont ID  
Sent By dpalmer Date 2008-01-07 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2008-01-07 Time 08:18 Sent To  
Notes
2008-01-07 08:20:51***TEMP FAILED STATUS.
  
 1) NOTE: PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT
 SHEETS ON THE MTS. THESE WERE REQUESTED ON ORIGINAL
 REVIEW AND WERE SUBMITTED PREVIOUSLY HOWEVER ARE NO
 LONGER IN PACKAGE.
 THESE CAN BE BROUGHT IN AT ANY TIME WHILE REVIEWS ARE
 BEING DONE. PLEASE CONTACT THIS REVIEWER IF THERE ARE
 ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-19 Cont ID  
Sent By dpalmer Date 2007-12-19 Time 12:21 Rev Time 0.00
Received By dpalmer Date 2007-12-19 Time 12:21 Sent To  
Notes
2007-12-19 12:21:39** DENIED 3RD REVIEW **
  
  
 1) NOTE: PLEASE SEE BOTH SETS OF PLANS SUBMITTED
 CONTAIN REVISED ARCHITECTURAL AND ELECTRICAL SHEETS
 WHICH ARE NOT SIGNED, DATED OR SEALED BY THE
 RESPONSIBLE DESIGNERS OF RECORD.
 PLEASE SEE FAC 61G1-16, 61G15-23.002, FS 471.025 AND
 481.221.
  
 2) NOTE: PLEASE SEE PLANS ARE NOW INDICATING ON SOME OF
 THE ARCHITECTURAL SHEETS THAT NO FIRE RATE WALLS WILL
 BE PROVIDED AND WIRING METHODS SHALL MEET CHAPTERS 1-4
 OF THE ELECTRICAL CODE.
 PLEASE SEE THAT PLANS SPECIFICALLY STILL STATE DESIGN
 IS TO MEET NFPA-75 2003 WHEN THIS IS APPARENTLY NOT THE
 DESIGN SHOWN ON PLANS.
 PLEASE BE SURE THE ELECTRICAL PLANS STATE THE WIRING
 METHODS AND REMOVE ANY ?IT? ROOM OR EQUIPMENT
 DESIGNATIONS. AS THIS IS NOT AN IT ROOM, ALL WIRING
 METHODS SHALL MEET THE MORE RESTRICTIVE CODES AS NOTED
 ABOVE.
 BELOW IS THE COMMENTARY TO 645.4
 **USE OF THE REQUIREMENTS IN ARTICLE 645 IS BASED ON
 THE ASSUMPTION THAT CONSTRUCTION OF THE INFORMATION
 TECHNOLOGY EQUIPMENT (ITE) ROOM COMPLIES WITH NFPA 75,
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT. FOR THOSE ITE ROOMS CONSTRUCTED IN
 ACCORDANCE WITH NFPA 75, ARTICLE 645 CONTAINS
 ELECTRICAL INSTALLATION REQUIREMENTS THAT ARE LESS
 STRINGENT THAN THE REQUIREMENTS IN THE FIRST FOUR
 CHAPTERS OF THE CODE. APPLICATION OF THESE PROVISIONS
 IS CONTINGENT ON THE ITE ROOM CONSTRUCTION AND
 EQUIPMENT MEETING ALL FIVE PROVISIONS SPECIFIED IN
 645.4. FOR EXAMPLE, THE PROVISIONS FOR WIRING
 INSTALLATIONS IN THE SPACE BENEATH THE RAISED FLOOR OF
 AN ITE ROOM WHERE THAT SPACE IS ALSO USED FOR
 ENVIRONMENTAL AIR ARE LESS STRINGENT THAN THOSE IN
 CHAPTERS 1 THROUGH 4 FOR THAT SAME TYPE OF SPACE. THE
 LESS RESTRICTIVE PROVISIONS IN ARTICLE 645 CANNOT BE
 TAKEN ADVANTAGE OF IF ANY ONE OF THE CONDITIONS
 SPECIFIED IN 645.4 IS ABSENT.**
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-26 Cont ID  
Sent By dpalmer Date 2007-11-26 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2007-11-26 Time 13:23 Sent To  
Notes
2007-11-26 13:36:31** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE THE PERMIT APPLICATION STILL DOES
 CONTAIN THE SUITE/UNIT # AS PREVIOUSLY REQUESTED.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR, ALL MATERIALS, EQUIPMENT,
 DESIGN COST ETC EVEN FOR OTHER WORK WHICH IS DONE UNDER
 SUB PERMITS.
 THIS IS ALSO IF ANY OF THE EQUIPMENT IS OWNER SUPPLIED.
 (IT EQUIPMENT)
 AS THE SUB-PERMITS ONLY PAY A $50 FEE, THEIR COMPLETE
 VALUE FOR SCOPE OF WORK ON PLANS SHALL BE INCLUDED.
  
 3) NOTE: PLEASE SEE THAT NO MANUFACTURE SPECS/CUT
 SHEETS WERE SUBMITTED.
 PLANS DO MENTION THE IT RACK EQUIPMENT IS NIC. PLEASE
 KNOW THIS MAY BE ARRANGED SO THAT OTHER EQUIPMENT IS
 SUBMITTED UNDER SEPARATE PERMIT, PLANS AND FEES AT A
 LATER DATE AND BEFORE INSTALLATION.
 FBC 106.1, 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE EXPLAIN WHY THE RATING OF THE WALLS HAS
 BEEN DELETED FROM THE A-SHEETS. PLEASE SEE MINIMUM
 RATINGS FOR WALLS PER NFPA-75 CHAPTER 5 AND NEC 645.7.
 PLEASE ALSO SEE POSSIBLE BUILDING REVIEW COMMENTS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By dpalmer Date 2007-10-16 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2007-10-16 Time 10:15 Sent To  
Notes
2007-10-16 10:37:56**** DENIED ****
  
  
 1) NOTE: ** PERMIT APPLICATION NEEDS TO INDICATE THE
 FLOOR/SUITE/UNIT # IN WHICH THE WORK IS BEING DONE.
 THIS WILL NEED TO BE CORRECTED IN OUR SYSTEM AS WELL
 AND APPLICATION.
 FBC 110.1.2, FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE:PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS.
 2003 NFPA-75
  
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR
 CODES.
  
 3) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK IS TO INCLUDE ALL LABOR, ALL MATERIALS, AND ALL
 EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF THESE ARE
 OWNER SUPPLIED.
 THIS INCLUDES IT EQUIPMENT.
 FBC 108.3
 ** PLEASE KNOW AS THE CERTAIN SUB PERMITS (ELECTRICAL)
 DO NOT PAY FEES BASED ON VALUE, THE COMPLETE SCOPE OF
 WORK VALUE SHALL BE ON BASE PERMIT.
 PLEASE SEE COMMENTS FROM OTHER TRADES WHICH ALSO MAY BE
 NOTED.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE MTS.
 90.7, 110.3
 FBC 106.1.2
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED IT EQUIPMENT. 90.7, 110.3
 PLEASE BE SURE ALL SPECS/CUT SHEETS CONTAIN LISTINGS
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY.
 (NRTL).
 PLEASE CLARIFY IF THERE WILL BE ANY UPS EQUIPMENT?
 645.11
 PLEASE CLARIFY THE PLANS WHICH INDICATE A CONTROL PANEL
 HOWEVER IT IS NOT CLEAR WHAT THIS CONTROL PANEL DOES.
 PLEASE SEE 645.10 FOR POSSIBLE DISCONNECTING MEANS OF
 ELECTRICAL EQUIPMENT IN ROOM WHICH.
 PLEASE KNOW AT THIS TIME SOME ITEMS CAN NOT BE REVIEWED
 FOR CODE COMPLIANCE.
  
 6) NOTE: PLEASE COMPLETE LIGHTING POWER DENSITIES FOR
 NEW LIGHTING IN ROOM.
 13-415.2
  
 7) NOTE: PLEASE SEE THAT ANY NEW LIGHTING CONTROL
 DEVICES WILL BE REQUIRED TO MEET 13-415.1.ABC.1.1/.1.2.
 THIS IS ONLY FOR THE NEW ROOM AND LIGHTING CONTROL FOR
 THAT ROOM.
  
 8) NOTE: PLEASE SEE RISER WHICH SHOWS AN OCTAGONAL NOTE
 #7 WHICH ON FEEDER SCHEDULE MENTIONS #4 FOR EQUIPMENT
 GROUND. THE RISER SHOWS #3 WITH THE 500MCM WHICH IS
 CORRECT PER 250.122 HOWEVER THE #4 AS ON KEY NOTES IS
 TOO SMALL.
 PLEASE ADJUST.
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 COMPLETED ON PLANS FOR REVIEW, NOT ALL COMMENTS MAY BE
 PRESENT AT THIS TIME.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2008-04-14 Cont ID  
Sent By mawillia Date 2008-04-14 Time 10:51 Rev Time 0.00
Received By mawillia Date 2008-04-12 Time 17:12 Sent To  
Notes
2008-04-12 17:15:15*****PROVISO*****
  
 THE REVISED PLAN SHEETS A1-3, A1-4, FP1.1, AND ANY
 OTHER SHEETS AFFECTED BY THE REVISIONS WILL BE
 FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-02-13 Cont ID  
Sent By mawillia Date 2008-02-13 Time 15:36 Rev Time 0.00
Received By mawillia Date 2008-02-13 Time 14:40 Sent To M
Notes
2008-02-13 15:23:19*****REVISION #4, DATED 01/22/2008, APPROVED*****
  
 REVISED PLAN SHEETS FP1.1 AND D1-2 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-10 Cont ID  
Sent By mawillia Date 2008-01-10 Time 13:10 Rev Time 0.00
Received By mawillia Date 2008-01-10 Time 12:57 Sent To  
Notes
2008-01-10 13:10:47*****APPROVED*****
  
 PLAN SHEETS D1.1, A1.3, E2.1, AND FP1.1 WERE
 RE-STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 14:50 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 14:25 Sent To E
Notes
2007-12-20 14:48:59*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADRESSED;PLAN SHEETS D1.1, A1.3, E2.1, AND FP1.1
 WERE STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-29 Cont ID  
Sent By mawillia Date 2007-11-29 Time 12:55 Rev Time 0.00
Received By mawillia Date 2007-11-29 Time 12:22 Sent To  
Notes
2007-11-29 12:52:43*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADRESSED:
  
 1.THE COMPLETE ADDRESS OF THE PROJECT SITE, INCLUDING
 SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.ADDRESS MISSING ON SHEETS
 FP1.1, M1.1
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. ADD
 COMMENT TO SHEET D1-1
  
 3.THE BUILDING AND/OR TENANT SPACE SHALL BE PERMITTED
 TO BE OCCUPIED DURING THE SCOPE OF WORK ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED. ADD
 COMMENT TO SHEET D1-1
  
 4.WHERE ALTERATION REQUIRES MODIFICATION OF A PORTION
 OF THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE
 SYSTEM SHALL BE KEPT IN SERVICE AND THE FIRE DEPARTMENT
 SHALL BE NOTIFIED.ADD COMMENT TO SHEET FP1-1
  
 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 NEW FM-200 FIRE SUPPRESSION SYSTEM.ADD COMMENT TO
 SHEET A1-3
  
 8.THE NEW FIRE DOOR AND WINDOW SHALL BE IN ACCORDANCE
 WITH NFPA 80.ADD COMMENT TO SHEET A1-3
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By mawillia Date 2007-10-18 Time 23:43 Rev Time 0.00
Received By mawillia Date 2007-10-18 Time 21:26 Sent To  
Notes
2007-10-18 23:43:00*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF THE PROJECT SITE, INCLUDING
 SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE BUILDING AND/OR TENANT SPACE SHALL BE PERMITTED
 TO BE OCCUPIED DURING THE SCOPE OF WORK ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED.
  
 4.WHERE ALTERATION REQUIRES MODIFICATION OF A PORTION
 OF THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE
 SYSTEM SHALL BE KEPT IN SERVICE AND THE FIRE DEPARTMENT
 SHALL BE NOTIFIED.
  
 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION AND THE
 FLORIDA FIRE PREVENTION CODE 2004 SHALL BE REFERENCED.
  
 6.NFPA 75,PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT, 2003 EDITION SHALL BE REFERENCED.
  
 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 NEW FM-200 FIRE SUPPRESSION SYSTEM.
  
 8.THE NEW FIRE DOOR AND WINDOW SHALL BE IN ACCORDANCE
 WITH NFPA 80.
  
 9.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-04-09 Cont ID  
Sent By adarroug Date 2008-04-09 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-04-09 Time 11:20 Sent To  
Notes
2008-04-09 11:20:50PLANS ROUTTED TO "COMM" BD#6

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-28 Cont ID  
Sent By adarroug Date 2008-03-28 Time 13:26 Rev Time 0.00
Received By adarroug Date 2008-03-28 Time 13:26 Sent To FIRE
Notes
2008-03-28 13:26:47TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 09:24 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 09:24 Sent To FIRE
Notes
2008-02-01 09:24:23TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 16:32 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 16:32 Sent To  
Notes
2008-01-04 16:33:07TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 10:28 Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 10:28 Sent To  
Notes
2007-12-14 10:31:18TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 10:03 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 10:03 Sent To  
Notes
2007-11-19 10:01:07TO "BOB"#3
2007-11-15 10:04:05WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-22 Cont ID  
Sent By jleech Date 2007-10-22 Time 09:31 Rev Time 0.00
Received By jleech Date 2007-09-27 Time 11:28 Sent To  
Notes
2007-10-15 11:08:20TO "BOB"#12
2007-09-27 11:28:38WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-04-11 Cont ID  
Sent By tgordon Date 2008-04-11 Time 13:32 Rev Time 0.30
Received By tgordon Date 2008-04-11 Time 13:32 Sent To  
Notes
2008-04-11 13:34:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLAN M1.1**
 *** DENIED ***
 1) SEE BUILDING REVIEW NOTES REGARDING THE EXHAUST WALL
 CAP, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-02-14 Cont ID  
Sent By tgordon Date 2008-02-14 Time 08:35 Rev Time 1.00
Received By tgordon Date 2008-02-14 Time 08:35 Sent To B
Notes
2008-02-14 08:50:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION PAGE M1.1 **
  
 *** DENIED ***
 1) THE A/C CONDENSATE LINE MAY NOT CONNECT INTO THE
 STORM RISER AT THAT POINT, IT MUST GO TEN FEET FROM THE
 BUILDING THEN TIE-IN TO THE STORM RISER WITH A RELIEF
 VENT. ALSO A CHECK VALVE WOULD STOP THE CONDENSATE
 WATER FROM GETTING PAST AS IT IS NOT UNDER PRESSURE.
 THERE ARE ALSO OTHER OPTIONS TO DISPOSE OF THE
 CONDENSATE WATER. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By tgordon Date 2008-01-08 Time 09:51 Rev Time 0.25
Received By tgordon Date 2008-01-08 Time 09:51 Sent To  
Notes
2008-01-08 09:53:04PASSED REVIEW ON 12-17-07.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-17 Cont ID  
Sent By tgordon Date 2007-12-17 Time 16:04 Rev Time 0.30
Received By tgordon Date 2007-12-17 Time 16:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-27 Cont ID  
Sent By tgordon Date 2007-11-27 Time 16:05 Rev Time 0.45
Received By tgordon Date 2007-11-27 Time 16:05 Sent To  
Notes
2007-11-27 16:06:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 10-18-07.THE JOB ADDRESS
 NEED TO BE IN THE TITLE BLOCK OF EACH PAGE OF THE
 PLANS, SEE W.P.B. 106.1.3. SEE MECHANICAL PLAN PAGE
 M1.1 MISSING ADDRESS.
  
 2) PLAN A1-3STATES,NEW CONDENSING UNIT FOR NEW
 LIEBERT A/C SYSTEM, ETC. ETC. AND ENDS WITH "VERIFY
 WITH ENGINEER". NO ENGINEERING WITH WIND LOAD
 CALCULATIONS SHOWING THAT THE TRELLIS WITH THE
 CONDENSER UNIT ON TOP WILL WITHSTAND 140 MPH WINDS WAS
 SUBMITTED. PLEASE COMPLY WITH 2004 FBC 1609 AS
 REQUESTED IN LAST REVIEW 10-18-07.
  
 3)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 07:56 Rev Time 0.30
Received By tgordon Date 2007-10-18 Time 07:55 Sent To  
Notes
2007-10-18 08:04:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE JOB ADDRESS NEED TO BE IN THE TITLE BLOCK OF
 EACH PAGE OF THE PLANS, SEE W.P.B. 106.1.3.
  
 2) NEED A ENGINEERING DETAIL SHOWING HOW THE A/C
 CONDENSER METAL BRACKET IS TO BE CONSTRUCTED AND
 SECURED TO THE WALL, ALSO HOW THE A/C CONDENSER UNIT IS
 TO BE SECURED TO THE METAL BRACKET ALL TO WITHSTAND 140
 MPH WINDS, PER 2004 FBC 1609.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-10-22 Cont ID  
Sent By jleech Date 2007-10-22 Time 09:30 Rev Time 0.00
Received By jleech Date 2007-10-22 Time 09:30 Sent To  
Notes
2007-10-22 09:30:53NO PLUMBING SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 4 Status P Date 2008-01-09 Cont ID  
Sent By mflis Date 2008-01-09 Time 15:50 Rev Time 0.00
Received By mflis Date 2008-01-09 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-19 Cont ID  
Sent By mflis Date 2007-12-19 Time 11:16 Rev Time 0.00
Received By mflis Date 2007-12-19 Time 11:16 Sent To  
Notes
2007-12-19 11:17:31ZONING REVIEW: PASSED
  
 * INTERIOR RENOVATION AND EXTERIOR MOD AT REAR
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-02 Cont ID  
Sent By mflis Date 2007-12-02 Time 14:10 Rev Time 0.00
Received By mflis Date 2007-12-02 Time 14:10 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mflis Date 2007-10-22 Time 08:31 Rev Time 0.00
Received By mflis Date 2007-10-22 Time 08:31 Sent To  
Notes
2007-10-22 08:32:55ZONING REVIEW: FAILED
  
 * PLEASE CONFIRM EQUIPMENT PLACEMENT WILL NOT IMPACT
 ABILITY TO ACCESS DUMPSTER/COMPACTOR
  
 MATT FLIS - 822-1445