Plan Review Details - Permit 07090731
| Plan Review Stops For Permit 07090731 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-10-29 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-10-29 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2007-10-29 15:24:27 | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3)106.3 PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE.SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG | | | WINDOWS AND THE ROOF COVERING MATERIAL. | | | | | | 4)106.3.3*CITY AMENDMENTS PRODUCT APPROVALS- 2004 | | | THOSE PRODUCTS THAT ARE REGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 5) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE, | | | ANCHORS, ANCHOR SPACING, EDGE DISTANCE, GLASS | | | SEPARATION, ETC. FBC 106.1.2 | | | | | | 6) THE STORM PANEL INFORMATION FOR THE TOWN AND COUNTRY | | | ACCORDIAN SHUTTERS IS FOR THE 2001 FBC AND HAS EXPIRED. | | | PLEASE REMOVE IT FROM THE SUBMITTAL PACKAGE. | | | | | | 7) SUBMIT UPDATED ENERGY CALCULATIONS. THE ONES | | | SUBMITTED ARE FOR THE 2001 FBC AND THE CURRENT CODE IS | | | THE 2004 FBC. THE ENERGY CALCS. THAT WERE SUBMITTED | | | INCORRECTLY SPECIFY WOOD FRAME ADJACENT INSULATION AND | | | THERE ARE NO ADJACENT WALLS SHOWN ON THE PLAN. PLEASE | | | CORRECT. MAKE SURE THE OWNER/AGENT SIGNS THE NEW ENERGY | | | FORMS. SEE FBC CHAPTER 13. | | | | | | 8) THE VALUE OF THE WORK HAS BEEN INCREASED BASED ON | | | THE ICC BUILDING VALUATION DATA AND RADON FEES HAVE | | | BEEN ACCESSED. ADDITIONAL FEES OF $ 1770.79 ARE DUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-10-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-02 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-02 |
Time |
07:34 |
Sent To |
M |
|
| Notes |
| 2007-10-02 09:41:34 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. | | | | | | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED | | | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. | | | 108.1 FBC. | | | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | | | 2} SHEET #2 INDICATES " ELECTRIC METER AND DISCONNECT" | | | THE RISER DIAGRAM ON SHEET #5SHOWS A METER AND A PANEL. | | | CORRELATE SAME. | | | | | | 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN | | | IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION | | | ON THE APPLICATION, PROVIDE AN AIC RATING, AND LOCATE | | | ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, | | | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH | | | ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER | | | DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE. | | | | | | 4} SHOW THE LOCATION OF THE A/C CONDENSER ON THE PLAN. | | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63. | | | | | | 5} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH | | | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. ADD NEXT TO | | | THE RANGE. | | | | | | 6} IN DWELLING UNITS, HALLWAYS OF 3.0 M (10 FT) OR MORE | | | IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET. | | | 210.52(H) | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2007-10-29 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-09-27 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2007-09-27 16:49:42 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-15 |
Time |
09:03 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-10-15 |
Time |
09:03 |
Sent To |
P |
|
| Notes |
| 2007-10-15 09:13:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, | | | PER 2004 FBC 13-600.3.A, (12-8-06 REVISION). | | | | | | 2) MECHANICAL PERMIT #07090733 HAS BEEN APPLIED FOR BUT | | | NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE | | | SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY | | | OF WPB AMEND. 106.3.5.4 (10). | | | | | | 3) PLEASE ADJUST VALUE OF WORK TO BE DONE TO SHOW THE | | | FAIR MARKET VALUE OR THE CITY WILL NEED TO ADJUST THE | | | VALUE USING MARSHALL AND SWIFT SEGREGATED COST METHOD, | | | PER CITY W.P.B. AMEND. 108.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-10-22 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-10-22 |
Time |
10:14 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-09-28 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-09-28 |
Time |
13:24 |
Sent To |
E |
|
| Notes |
| 2007-09-28 13:35:00 | ***FAILED*** | | | | | | | | | 1)SURVEYS INDICATE SIDE SETBACKS AT 7.4' ON BOTH | | | SIDES.ANY NEW CONSTRUCTION WILL BE REQUIRED TO MEET | | | CURRENT REGULATIONS REGARDING SETBACKS.PURSUANT TO | | | SECTION 94-72 OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS:SIDE SETBACKS = A MINIMUM OF 5' WITH A | | | TOTAL OF 15' BETWEEN THE TWO SIDES. | | | | | | 2)DECLARED VALUE OF WORK SEEMS TO BE TOO LOW. | | | | | | 3)INDICATE HEIGHT DIMENSIONS ON ELEVATION PLAN OF | | | PROPOSED ADDITION. (FROM GRADE TO THE MIDPOINT OF THE | | | ROOF'S PITCH) | | | | | | 4)SHOW ANY PROPOSED OR RELOCATED A/C EQUIPMENT WITH | | | SETBACK DIMENSIONS TO THE PROPERTY LINES. | | | | | | 5)IF ADJUSTED VALUE EXCEEDS 50% OF THE VALUE OF THE | | | EXISTING STRUCTURE, A LANDSCAPE PLAN SHALL BE PROVIDED | | | SHOWING COMPLIANCE WITH THE CITY OF WEST PALM BEACH | | | ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION | | | 94-442. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | | TECHNICIAN | | | (561)805-6720 |
|
|
|