Plan Review Details - Permit 07090731
Plan Review Stops For Permit 07090731
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By rmcdouga Date 2007-10-29 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2007-10-29 Time 15:24 Sent To  
Notes
2007-10-29 15:24:27DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)106.3 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG
 WINDOWS AND THE ROOF COVERING MATERIAL.
  
 4)106.3.3*CITY AMENDMENTS PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5) SUBMIT 2 COPIES OF A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY THE MOUNT TYPE,
 ANCHORS, ANCHOR SPACING, EDGE DISTANCE, GLASS
 SEPARATION, ETC. FBC 106.1.2
  
 6) THE STORM PANEL INFORMATION FOR THE TOWN AND COUNTRY
 ACCORDIAN SHUTTERS IS FOR THE 2001 FBC AND HAS EXPIRED.
 PLEASE REMOVE IT FROM THE SUBMITTAL PACKAGE.
  
 7) SUBMIT UPDATED ENERGY CALCULATIONS. THE ONES
 SUBMITTED ARE FOR THE 2001 FBC AND THE CURRENT CODE IS
 THE 2004 FBC. THE ENERGY CALCS. THAT WERE SUBMITTED
 INCORRECTLY SPECIFY WOOD FRAME ADJACENT INSULATION AND
 THERE ARE NO ADJACENT WALLS SHOWN ON THE PLAN. PLEASE
 CORRECT. MAKE SURE THE OWNER/AGENT SIGNS THE NEW ENERGY
 FORMS. SEE FBC CHAPTER 13.
  
 8) THE VALUE OF THE WORK HAS BEEN INCREASED BASED ON
 THE ICC BUILDING VALUATION DATA AND RADON FEES HAVE
 BEEN ACCESSED. ADDITIONAL FEES OF $ 1770.79 ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-02 Cont ID  
Sent By btrobaug Date 2007-10-02 Time 09:41 Rev Time 0.00
Received By btrobaug Date 2007-10-02 Time 07:34 Sent To M
Notes
2007-10-02 09:41:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 2} SHEET #2 INDICATES " ELECTRIC METER AND DISCONNECT"
 THE RISER DIAGRAM ON SHEET #5SHOWS A METER AND A PANEL.
 CORRELATE SAME.
  
 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION
 ON THE APPLICATION, PROVIDE AN AIC RATING, AND LOCATE
 ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER
 DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE.
  
 4} SHOW THE LOCATION OF THE A/C CONDENSER ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63.
  
 5} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. ADD NEXT TO
 THE RANGE.
  
 6} IN DWELLING UNITS, HALLWAYS OF 3.0 M (10 FT) OR MORE
 IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET.
 210.52(H)
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-29 Cont ID  
Sent By rmcdouga Date 2007-10-29 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2007-09-27 Time 16:48 Sent To  
Notes
2007-09-27 16:49:42TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-15 Cont ID  
Sent By tgordon Date 2007-10-15 Time 09:03 Rev Time 0.30
Received By tgordon Date 2007-10-15 Time 09:03 Sent To P
Notes
2007-10-15 09:13:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R,
 PER 2004 FBC 13-600.3.A, (12-8-06 REVISION).
  
 2) MECHANICAL PERMIT #07090733 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 3) PLEASE ADJUST VALUE OF WORK TO BE DONE TO SHOW THE
 FAIR MARKET VALUE OR THE CITY WILL NEED TO ADJUST THE
 VALUE USING MARSHALL AND SWIFT SEGREGATED COST METHOD,
 PER CITY W.P.B. AMEND. 108.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-10-22 Cont ID  
Sent By jleech Date 2007-10-22 Time 10:14 Rev Time 0.00
Received By jleech Date 2007-10-22 Time 10:14 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-28 Cont ID  
Sent By choops Date 2007-09-28 Time 13:25 Rev Time 0.00
Received By choops Date 2007-09-28 Time 13:24 Sent To E
Notes
2007-09-28 13:35:00***FAILED***
  
  
 1)SURVEYS INDICATE SIDE SETBACKS AT 7.4' ON BOTH
 SIDES.ANY NEW CONSTRUCTION WILL BE REQUIRED TO MEET
 CURRENT REGULATIONS REGARDING SETBACKS.PURSUANT TO
 SECTION 94-72 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS:SIDE SETBACKS = A MINIMUM OF 5' WITH A
 TOTAL OF 15' BETWEEN THE TWO SIDES.
  
 2)DECLARED VALUE OF WORK SEEMS TO BE TOO LOW.
  
 3)INDICATE HEIGHT DIMENSIONS ON ELEVATION PLAN OF
 PROPOSED ADDITION. (FROM GRADE TO THE MIDPOINT OF THE
 ROOF'S PITCH)
  
 4)SHOW ANY PROPOSED OR RELOCATED A/C EQUIPMENT WITH
 SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
 5)IF ADJUSTED VALUE EXCEEDS 50% OF THE VALUE OF THE
 EXISTING STRUCTURE, A LANDSCAPE PLAN SHALL BE PROVIDED
 SHOWING COMPLIANCE WITH THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS, SECTION
 94-442.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720