Plan Review Details - Permit 07090714
Plan Review Stops For Permit 07090714
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-09 Cont ID  
Sent By btrobaug Date 2007-10-09 Time 10:45 Rev Time 0.00
Received By btrobaug Date 2007-10-09 Time 07:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-01 Cont ID  
Sent By btrobaug Date 2007-10-01 Time 13:18 Rev Time 0.00
Received By btrobaug Date 2007-10-01 Time 13:05 Sent To I
Notes
2007-10-01 13:15:08 
  
 APPLICATION #07090714
 ELECTRICAL PLAN REVIEW
 1000 OKEECHOBEE ROAD
  
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 230.7 OTHER CONDUCTORS IN RACEWAY OR CABLE
 CONDUCTORS OTHER THAN SERVICE CONDUCTORS SHALL NOT BE
 INSTALLED IN THE SAME SERVICE RACEWAY OR SERVICE
 CABLE.
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-01 Cont ID  
Sent By btrobaug Date 2007-10-01 Time 13:18 Rev Time 0.00
Received By btrobaug Date 2007-09-27 Time 10:42 Sent To PC
Notes
2007-09-27 10:42:54TO "E" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved