Plan Review Details - Permit 07090711
Plan Review Stops For Permit 07090711
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 17:41 Rev Time 0.00
Received By shill Date 2008-03-19 Time 17:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-03-07 Cont ID  
Sent By shill Date 2008-03-07 Time 09:05 Rev Time 0.00
Received By shill Date 2008-03-07 Time 09:05 Sent To  
Notes
2008-03-07 09:06:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE HAVE THE ENGINEER ALBERT RHUI-HONG TENG
 CONTACT ME.I HAVE HAD CONVERSATIONS WITH HIS OFFICE
 REGARDING THE LIFE SAFETY ISSUE OF NON REQUIRED ITEMS
 IN A PROTECTED STAIR, FBC1019.1.THE ELECTRIC RUNNING
 THROUGH THE STAIRWELL WAS REMOVED, BUT NOW IT IS SHOWN
 AGAIN AS PENETRATING THE PROTECTED STAIR.IT IS NOT
 CLEAR WHY THE ENGINEER IS SEALING A PLAN WITH A LIFE
 SAFETY ISSUE WHICH HAS ALREADY BEEN BROUGHT TO HIS
 ATTENTION.IS THIS NOT A PROTECTED EXIT STAIR?
  
 A SET HAS BEEN RETAINED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-28 Cont ID  
Sent By shill Date 2007-12-28 Time 11:29 Rev Time 0.00
Received By shill Date 2007-12-28 Time 11:29 Sent To  
Notes
2007-12-28 11:31:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.THE CALCULATIONS STILL HAVE THE COMPANY NAME "DELTA
 ENGINEERING" AND IS NOT SIGNED, SEALED, AND DATED;
 FAC61G15-23.002.
  
 2.INFORMATIONAL - A ROOF PERMIT WILL BE REQUIRED.
 WHEN THE ROOFING CONTRACTOR SUBMITS FOR ROOF PERMIT,
 DESIGN PRESSURES FOR THIS BUILDING MUST BE DETERMINED
 BY AN ARCHITECT OR ENGINEER.THE ROOFING CONTRACTOR IS
 TO INDICIATE WHICH APPROVED ASSEMBLY IS BEING PROPOSED,
 AND ENHANCED FASTENING PATTERN SPECIFIED BY AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-27 Cont ID  
Sent By shill Date 2007-11-27 Time 11:33 Rev Time 0.00
Received By shill Date 2007-11-27 Time 11:33 Sent To  
Notes
2007-11-27 11:53:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.FAC61G15-23.002 REQUIRES THE FOLLOWING:
  
 C.ALL INFORMATION REQUIRED REGARDING ENGINEER AND
 COMPANY (CERTIFICATE OF AUTHORIZATION NUMBER ON EACH
 SHEET)
  
 RESPONSE LETTER STATES THAT THE COFA WAS ADDED.
 WHERE?
  
 THE SEAL, PREVIOUSLY NOT LEGIBLE, STATES "CERTIFICATE".
 THIS SEAL HAS BEEN EXPIRED FOR YEARS; THE CURRENT SEAL
 STATES "LICENSE" AND FBPE HAS GIVEN THE DIRECTIVE NOT
 TO ACCEPT EXPIRED SEALS.PLEASE CONTACT FBPE IF YOU
 HAVE QUESTIONS, WWW.FBPE.ORG.
  
 2-3.ADDRESSED.
  
 4.ITEMS 11 AND 21 STATE THAT NEW GUARDRAIL AND NEW
 CHASE AND STAIR WILL BE INSTALLED.PROVIDE
 SPECIFICATIONS.
  
 THE REVISIONS WERE NOT CLOUDED.PLEASE CLOUD ALL
 CHANGES AND MARK WITH A REVISION NUMBER SO THAT CHANGES
 CAN BE DETERMINED.
 THE RESPONSE LETTER STATES "NEW GUARDRAIL AND NEW CHASE
 IN STAIRWELL WILL BE INSTALLED . . . "BUT THE
 CORRECTION STATED THAT A NEW STAIR WILL BE INSTALLED,
 NOT THAT THESE NEW ITEMS WILL BE INSTALLED IN A
 STAIRWELL.YOU CANNOT INSTALL ANYTHING IN REQUIRED
 PROTECTED EGRESS STAIRS, FBC1019.1.WHERE WILL THE
 CHASE BE LOCATED?PLEASE CLARIFY YOUR RESPONSE.
  
 5.PROVIDE ROOF PRODUCT APPROVAL, 1-A5.PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD,
 FBC106.3.3.
  
 ENGINEER'S RESPONSE IS THAT THIS IS AN OUTDATED CODE
 REFERENCE AND THERE ARE NO REQUIREMENTS IN THE FBC FOR
 PRODUCT APPROVALS.PLEASE SEE FAC9B72.CITY OF WEST
 PALM BEACH AMENDMENTS TO THE FBC REQUIRE THAT PRODUCT
 APPROVALS BE REVIEWED BY DESIGNER OF RECORD.PRODUCT
 APPROVALS ARE REQUIRED FOR ALL COMPONENTS AND CLADDING,
 INCLUDING ROOFING.THIS IS COMMON INDUSTRY KNOWLEDGE
 IN SOUTH FLORIDA.IT IS POSSIBLE THAT YOUR CONTRACTOR
 ASSIST YOU WITH THIS REQUIREMENT.PRODUCT APPROVALS
 ARE AVAILABLE AT WWW.FLORIDABUILDING.ORG.THE PRODUCT
 APPROVAL WILL BE REQUIRED AT THIS TIME BUT THE OTHER
 INFORMATION REQUIRED FOR A ROOFING PERMIT CAN BE
 SUBMITTED AT THE TIME OF ROOF PERMIT APPLICATION.
  
 A SET HAS BEEN RETAINED (PENDING RESOLUTION OF THE
 CERTIFICATE OF AUTHORIZATION ISSUE).WHEN
 RESUBMITTING, SUBMIT TWO COMPLETE SETS OF PLANS.TO
 EXPEDITE PLAN REVIEW, PLEASE SUBMIT A RESPONSE LETTER
 STATING HOW EACH ITEM HAS BEEN ADDRESSED.
  
 PLEASE NOTE THAT I WAS UNABLE TO FIND A CERTIFICATE OF
 AUTHORIZATION FOR DELTA GROUPS ENGINEERING, INC. AT
 WWW.MYFLORIDALICENSE.COM.CERTIFICATE OF AUTHORIZATION
 REQUIRED TO PRACTICE ENGINEERING THROUGH A COMPANY,
 FS471.023.IF THE FIRM HAS NOT APPLIED, PLEASE DO SO
 AT THIS TIME.IF THE FIRM DOES NOT HAVE A CERTIFICATE
 OF AUTHORIZATION, THIS COMPANY CANNOT PRACTICE
 ENGINEERING IN FLORIDA (PLANS MUST BE SUBMITTED AND
 SEALED INDIVIDUALLY).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-19 Cont ID  
Sent By shill Date 2007-10-19 Time 17:30 Rev Time 0.00
Received By shill Date 2007-10-19 Time 17:30 Sent To E
Notes
2007-10-19 17:43:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.FAC61G15-23.002 REQUIRES THE FOLLOWING:
  
 A.LEGIBLE SEAL
 B.DATE WITH THE SIGNATURE AND SEAL
 C.ALL INFORMATION REQUIRED REGARDING ENGINEER AND
 COMPANY (CERTIFICATE OF AUTHORIZATION NUMBER ON EACH
 SHEET)
 D.EACH SHEET SIGNED, SEALED, AND DATED OR USE AN
 INDEX SHEET
  
 2.THE ADDRESS ON THE PLAN FOR THE ENGINEER CONFLICTS
 WITH THE ADDRESS WITH FBPE.
  
 3.THE PLAN STATES THAT THE CONSTRUCTION TYPE IS VN.
 WHAT IS THIS?SEE FBC CHAPTER 5.IT APPEARS THAT THIS
 BUILDING IS NON COMBUSTIBLE, TYPE V ALLOWS COMBUSTIBLE
 MATERIALS.ARE YOU REFERRING TO THE BUILDING OR THE
 IMPROVEMENT?SEE FBC1509, IT DOES NOT APPEAR THAT USE
 OF COMBUSTIBLE MATERIALS IS ALLOWED.
  
 4.ITEMS 11 AND 21 STATE THAT NEW GUARDRAIL AND NEW
 CHASE AND STAIR WILL BE INSTALLED.PROVIDE
 SPECIFICATIONS.
  
 5.PROVIDE ROOF PRODUCT APPROVAL, 1-A5.PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD,
 FBC106.3.3.
  
 A SET HAS BEEN RETAINED (PENDING RESOLUTION OF THE
 CERTIFICATE OF AUTHORIZATION ISSUE).WHEN
 RESUBMITTING, SUBMIT TWO COMPLETE SETS OF PLANS.TO
 EXPEDITE PLAN REVIEW, PLEASE SUBMIT A RESPONSE LETTER
 STATING HOW EACH ITEM HAS BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-03-17 Cont ID  
Sent By btrobaug Date 2008-03-17 Time 07:48 Rev Time 0.00
Received By btrobaug Date 2008-03-17 Time 07:06 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-02-26 Cont ID  
Sent By btrobaug Date 2008-02-26 Time 12:21 Rev Time 0.00
Received By btrobaug Date 2008-02-25 Time 10:03 Sent To B
Notes
2008-02-26 11:53:15 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 230.70(A) (1)READILY ACCESSIBLE LOCATION THE
 SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS.DO TO CONDITIONS NOW
 REQUIREING CONDUITS BE RAN THROUGH THE BUILDING
 UNPROTECTED, AND GIVEN THE FACT OF DIFFERING VOLTAGES
 ALLOWED PER 230.2(D) THE METER AND DISCONNECT WILL BE
 ALLOWED OUTSIDE THE BUILDING GROUPED WITH THE MANUAL
 TRANSFER SWITH SHOWN ON SHEET E2. ALSO NOTE THAT
 IDENTIFICATION PER 230.2(E) IS REQUIRED. INDICATE THESE
 CHANGES ON RESUBMITTED PLANS.
  
 2} SEE BUILDING COMMENTS REGARDING CONDUITS IN THE
 STAIRWELL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-01-28 Cont ID  
Sent By btrobaug Date 2008-01-28 Time 09:29 Rev Time 0.00
Received By btrobaug Date 2008-01-28 Time 07:56 Sent To B
Notes
2008-01-28 09:29:52 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING COMMENTS ARE REGARDING NOTES AND DRAWING
 ON SHEET E2: AND WERE NOT CORRECTLY RESPONDED TO FROM
 THE LAST REVIEW. NOTE: FURTHER EXPLANATION OF THE
 COMMENTS IS MARKED BY AN ASTERISK.
  
 1} 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. INDICATE UNDER WHICH EXCEPTION YOU ARE
 ASKING THE AHJ FOR PERMISSION FOR THIS SERVICE.* THIS
 COMMENT WAS NOT ADDRESSED, ONLY THE PROPOSED SERVICE IS
 SHOWN, NOT THE OTHER SERVICE(S) FOR THE BUILDING.
  
 2} INDICATE COMPLIANCE WITH 230.71 MAXIMUM NUMBER OF
 DISCONNECTS, AND 230.72 GROUPING OF DISCONNECTS.* SAME
 COMMENT AS ABOVE, THE OTHER SERVICE(S) ARE NOT SHOWN
 THERREFORE COMPLIANCE WITH THIS ARTICLE CANNOT BE
 REVIEWED.
  
 4} 250.24(D) GROUNDING ELECTRODE CONDUCTOR- A GROUNDING
 ELECTRODE CONDUCTOR SHALL BE USED TO CONNECT THE
 EQUIPMENT GROUNDING CONDUCTORS, THE SERVICE-EQUIPMENT
 ENCLOSURES, AND, WHERE THE SYSTEM IS GROUNDED, THE
 GROUNDED SERVICE CONDUCTOR TO THE GROUNDING
 ELECTRODE(S) REQUIRED BY PART III OF THIS ARTICLE.
 THERE IS NONE INDICATED ON THE PROPOSED SERVICE. SEE
 250.24(C) FOR POINT OF ATTACHMENT, SEE 250.66 FOR
 SIZING REQUIREMENTS.* INDICATING A GROUND ROD ON THE
 RISER DIAGRAM DOES NOT MEET THE REQUIREMENT OF THIS
 ARTICLE.IF THIS SERVICE IS GROUPED PER 230.72, AND
 ALLOWED BY EXCEPTION THEN THE GEC SHALL BE CONNECTED TO
 THE EXISTING GEC.PER THIS ARTICLE.
  
 NEW COMMENT:
  
 5} THE ENGINEERS SEAL IS NOT CORRECTLY DATED PER
 61G15-23.002(1) FAC.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-20 Cont ID  
Sent By btrobaug Date 2007-12-20 Time 11:36 Rev Time 0.00
Received By btrobaug Date 2007-12-20 Time 08:10 Sent To B
Notes
2007-12-20 11:35:54 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING COMMENTS ARE REGARDING NOTES AND DRAWING
 ON SHEET E2:
  
 1} 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. INDICATE UNDER WHICH EXCEPTION YOU ARE
 ASKINGTHE AHJ FOR PERMISSION FOR THIS SERVICE.
  
 2} INDICATE COMPLIANCE WITH 230.71MAXIMUM NUMBER OF
 DISCONNECTS, AND 230.72 GROUPING OF DISCONNECTS.
  
 3}250.6(B) ALTERATIONS TO STOP OBJECTIONABLE
 CURRENT- IF THE USE OF MULTIPLE GROUNDING CONNECTIONS
 RESULTS IN OBJECTIONABLE CURRENT, ONE OR MORE OF THE
 FOLLOWING ALTERATIONS SHALL BE PERMITTED TO BE MADE,
 PROVIDED THAT THE REQUIREMENTS OF 250.4(A)(5) OR (B)(4)
 ARE MET: SEE ARTICLE FOR MORE CLARIFICATION. THE #8
 GROUND RAN WITH THE SERVICE CONDUCTORS TO THE FIRST
 MEANS OF DISCONNECT ARE IN VIOLATION OF THIS ARTICLE
 AND MUST BE REMOVED.
  
 4} 250.24(D) GROUNDING ELECTRODE CONDUCTOR- A GROUNDING
 ELECTRODE CONDUCTOR SHALL BE USED TO CONNECT THE
 EQUIPMENT GROUNDING CONDUCTORS, THE SERVICE-EQUIPMENT
 ENCLOSURES, AND, WHERE THE SYSTEM IS GROUNDED, THE
 GROUNDED SERVICE CONDUCTOR TO THE GROUNDING
 ELECTRODE(S) REQUIRED BY PART III OF THIS ARTICLE.
 THERE IS NONE INDICATED ON THE PROPOSED SERVICE. SEE
 250.24(C) FOR POINT OF ATTACHMENT, SEE 250.66 FOR
 SIZING REQUIREMENTS.
  
 5} VERIFY THAT A 3 PHASE SERVICE IS FEEDING A SINGLE
 PHASE LOAD.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-11-20 Cont ID  
Sent By btrobaug Date 2007-11-20 Time 12:34 Rev Time 0.00
Received By btrobaug Date 2007-11-20 Time 11:59 Sent To B
Notes
2007-11-20 12:34:29 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 2} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC. THE SEAL IS INDISCERNIBLE, ALL SHEETS
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 13:50 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 13:50 Sent To E
Notes
2008-03-13 13:50:38TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-15 Cont ID  
Sent By adarroug Date 2008-02-15 Time 12:02 Rev Time 0.00
Received By adarroug Date 2008-02-15 Time 12:02 Sent To  
Notes
2008-02-15 12:02:51TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-17 Cont ID  
Sent By shill Date 2008-01-17 Time 16:31 Rev Time 0.00
Received By shill Date 2008-01-17 Time 16:31 Sent To E
Notes
2008-01-17 16:32:05TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 13:57 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 13:57 Sent To E
Notes
2007-12-13 13:59:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 13:44 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 13:44 Sent To Z
Notes
2007-11-15 13:44:35TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-25 Cont ID  
Sent By btrobaug Date 2007-10-21 Time 09:57 Rev Time 0.00
Received By btrobaug Date 2007-09-27 Time 10:51 Sent To PC
Notes
2007-09-27 10:53:42TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-16 Cont ID  
Sent By adavila Date 2007-11-16 Time 15:10 Rev Time 0.00
Received By adavila Date 2007-11-16 Time 11:17 Sent To E
Notes
2007-11-16 15:11:50PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PROVISO CONDUIT SHALL BE PAINTED TO MATCH THE
 BUILDING.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-03 Cont ID  
Sent By adavila Date 2007-10-03 Time 10:45 Rev Time 0.00
Received By adavila Date 2007-10-03 Time 08:31 Sent To B
Notes
2007-10-03 10:46:31PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.SITE PLAN APPROVAL REQUIRED PRIOR TO BUILDING
 PERMIT APPROVAL.
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.