Plan Review Details - Permit 07090675
Plan Review Stops For Permit 07090675
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-21 Cont ID  
Sent By shill Date 2008-02-21 Time 17:23 Rev Time 0.00
Received By shill Date 2008-02-21 Time 17:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-14 Cont ID  
Sent By shill Date 2008-02-14 Time 17:38 Rev Time 0.00
Received By shill Date 2008-02-14 Time 17:38 Sent To  
Notes
2008-02-14 17:38:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.TWO COMPLETE COLLATED ORIGINAL SETS REQUIRED.ONLY
 ONE SET OF ENGINEERING WAS SUBMITTED.FS481.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 10:40 Rev Time 0.00
Received By shill Date 2007-10-29 Time 10:40 Sent To  
Notes
2007-10-29 10:47:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.TWO COMPLETE COLLATED ORIGINAL SETS REQUIRED.ONLY
 ONE SET OF ENGINEERING WAS SUBMITTED.FS481.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-04-08 Cont ID  
Sent By btrobaug Date 2008-04-08 Time 15:16 Rev Time 0.00
Received By btrobaug Date 2008-04-08 Time 15:01 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-10-02 Cont ID  
Sent By btrobaug Date 2007-10-02 Time 15:58 Rev Time 0.00
Received By btrobaug Date 2007-10-02 Time 15:38 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-02-14 Cont ID  
Sent By mperson Date 2008-02-14 Time 11:48 Rev Time 0.00
Received By mperson Date 2008-02-14 Time 11:48 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By mperson Date 2007-10-16 Time 11:22 Rev Time 0.00
Received By mperson Date 2007-10-16 Time 11:22 Sent To B
Notes
2007-10-16 11:39:24DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT INDICATE CORRESPONDING LENGTHS TO CUT SECTIONS
 OF PIPE.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: DRAWING DOES NOT INDICATE BTU'S OF PROPOSED
 GENERATOR OR BTU'S OF EXISTING GAS SYSTEM.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: GAS PLAN REVIEW CAN NOT BE DONE WITHOUT THIS
 INFORMATION. THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: GAS PLAN REVIEW CAN NOT BE DONE WITHOUT THIS
 INFORMATION.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: IF GAS DELIVERY PRESSURE IS 2 PSI PLEASE SUBMIT
 MANUFACTURER SPECIFICATION SHEETS OF THE MP REGULATORS
 WITH THE NAME, MODEL NUMBER,BTU LOAD CAPACITY AND A
 LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 11:26 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 11:26 Sent To E
Notes
2008-04-08 11:26:58TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 11:53 Sent To B
Notes
2008-02-19 11:54:06TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2008-02-08 Time 15:58 Rev Time 0.00
Received By adarroug Date 2008-02-08 Time 15:58 Sent To Z
Notes
2008-02-08 15:58:22TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-29 Cont ID  
Sent By shill Date 2007-10-29 Time 10:47 Rev Time 0.00
Received By shill Date 2007-09-25 Time 09:33 Sent To  
Notes
2007-09-25 09:33:46TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-13 Cont ID  
Sent By tgordon Date 2008-02-13 Time 14:39 Rev Time 0.25
Received By tgordon Date 2008-02-13 Time 14:39 Sent To G
Notes
2008-02-13 14:41:43*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-10-10 Cont ID  
Sent By tgordon Date 2007-10-10 Time 08:34 Rev Time 0.20
Received By tgordon Date 2007-10-10 Time 08:34 Sent To G
Notes
2007-10-10 08:36:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-13 Cont ID  
Sent By choops Date 2008-02-13 Time 14:27 Rev Time 0.00
Received By choops Date 2008-02-13 Time 14:27 Sent To M
Notes
2008-02-13 14:28:13***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-28 Cont ID  
Sent By choops Date 2007-09-28 Time 17:20 Rev Time 0.00
Received By choops Date 2007-09-28 Time 17:20 Sent To E
Notes
2007-09-28 17:23:49***FAILED***
  
  
 1)PURSUANT TO SECTION 94-305(B)(4) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS:MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.INDICATE SETBACK
 DIMENSIONS FROM THE GENERATOR TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720