Plan Review Details - Permit 07090655
Plan Review Stops For Permit 07090655
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-11-13 Cont ID  
Sent By mwennerg Date 2007-11-13 Time 14:00 Rev Time 0.00
Received By mwennerg Date 2007-11-13 Time 14:00 Sent To  
Notes
2007-11-13 14:01:57FIRE ALARM PANEL TO BE CLASS A OR FULLY ADDRESSABLE.
 PLANS STAMPED WITH THIS INFORMATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-05 Cont ID  
Sent By mwennerg Date 2007-10-05 Time 11:57 Rev Time 0.00
Received By mwennerg Date 2007-10-05 Time 11:57 Sent To  
Notes
2007-10-05 12:10:46***DENIED***
  
 1) DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 LOCATION, NATURE AND EXTENT OF WORK. 106.1.1. PLEASE
 CLEARLY ILLUSTRATE ALL DEVICES NEW OR EXISTING.
  
 2) IF THIS IS CONSIDERED A NEW FIRE ALARM SYSTEM THAT
 SUPERVISES AN AUTOMATIC FIRE SPRINKLER SYSTEM, THE FIRE
 ALARM IS REQUIRED TO BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 3) PREVIOUS PLANS SUBMITTED SHOWED VISUAL DEVICES IN
 ADDITION TO AUDIBLE. THIS IS NOT CLEARLY SHOWN ON THIS
 SUBMITTAL.
  
 4) FIRE ALARM RISER INDICATES AN "F" BUT THIS IS NOT
 SHOWN ON THE LEGEND?
  
 5) FIRE ALARM SYSTEMS SHALL BE CLASS A OR FULLY
 ADDRESSABLE.
  
 6) THE LETTERS C AND K ARE SHOWN ON DRAWINGS. PLEASE
 EXPLAIN.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 10:41 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 10:41 Sent To FIRE
Notes
2007-11-06 10:41:35TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-05 Cont ID  
Sent By mwennerg Date 2007-10-05 Time 12:13 Rev Time 0.00
Received By mwennerg Date 2007-09-24 Time 14:27 Sent To  
Notes
2007-09-24 14:27:52TO "F" BOX