| 2007-10-20 12:13:35 | |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $303.11 FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER |
| | AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL. THIS IS REQUIRED FOR SPACE THAT WILL BE |
| | CONDITIONED IN FUTURE |
| | |
| | 5)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH |
| | R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE |
| | INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD |
| | |
| | 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 7)THE GLAZING THICKNESS ON THE PLANS ARE NOT PROVIDED |
| | IN THE PRODUCT APPROVALS FOR THE SINGLE HUNG AND FIXED |
| | WINDOWS OR THE SLIDING GLASS DOORS |
| | |
| | 8)THERE ARE MIXED NOA'S SUPPLIED FOR THE SINGLE HUNG |
| | AND FIXED WINDOWS |
| | |
| | 9)WINDOW DESIGNATION IN RESTROOM ON 2ND FLOOR PLAN IS |
| | FOR FIXED WINDOW |
| | |
| | 10)PROVIDE SCHEDULE FOR ALL STRAPS/CONNECTORS THAT |
| | INCLUDES THEIR FLORIDA STATEWIDE PRODUCT APPROVAL |
| | NUMBERS OR THE SIMPSON TIE INDEX SHEET OF FLORIDA |
| | APPROVED CONNECTORS WITH THE PRODUCTS HIGHLIGHTED OR |
| | PROVIDE THE PRODUCT APPROVALS |
| | |
| | 11)STRUCTURAL DRAWINGS DO NOT SHOW BLOCK TO BE |
| | INSTALLED AT LOCATION OF EXISTING WOOD FRAME WALL AT |
| | NORTH EAST CORNER OF GARAGE ON THE FOUNDATION PLAN |
| | |
| | 12)PROVIDE DETAIL FOR THE ATTACHMENT OF THE STEEL |
| | COLUMN BASE PLATE TO THE BLOCK COLUMN AT REAR DECK. |
| | WILL THERE BE A CONCRETE CAP OR IS BASE PLATE MOUNTED |
| | DIRECTLY TO THE GROUTED FILL CELLS? |
| | |
| | 13)STRUCTURAL STEEL COLUMN DESIGNATION IN SCHEDULE |
| | DOES NOT MATCH PLAN DESIGNATION |
| | |
| | 14)GUARDS AND HANDRAILS SHALL MEET THE LOAD |
| | REQUIREMENTS OF 1607.7.1.1 FBC |
| | |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | BLDG PLAN REVIEW |