Plan Review Details - Permit 07090646
Plan Review Stops For Permit 07090646
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-12-19 Cont ID  
Sent By amorse Date 2007-12-19 Time 17:21 Rev Time 0.00
Received By amorse Date 2007-12-19 Time 17:21 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-20 Cont ID  
Sent By amorse Date 2007-10-20 Time 12:07 Rev Time 0.00
Received By amorse Date 2007-10-20 Time 12:07 Sent To PC
Notes
2007-10-20 12:13:35 
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $303.11 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 4)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER
 AND OWNER/AGENT PRIOR
 TO SUBMITTAL. THIS IS REQUIRED FOR SPACE THAT WILL BE
 CONDITIONED IN FUTURE
  
 5)SUBMIT ENGINEERED TRUSS DRAWINGS THAT COMPLY WITH
 R802.10.1 FBC WITH PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7)THE GLAZING THICKNESS ON THE PLANS ARE NOT PROVIDED
 IN THE PRODUCT APPROVALS FOR THE SINGLE HUNG AND FIXED
 WINDOWS OR THE SLIDING GLASS DOORS
  
 8)THERE ARE MIXED NOA'S SUPPLIED FOR THE SINGLE HUNG
 AND FIXED WINDOWS
  
 9)WINDOW DESIGNATION IN RESTROOM ON 2ND FLOOR PLAN IS
 FOR FIXED WINDOW
  
 10)PROVIDE SCHEDULE FOR ALL STRAPS/CONNECTORS THAT
 INCLUDES THEIR FLORIDA STATEWIDE PRODUCT APPROVAL
 NUMBERS OR THE SIMPSON TIE INDEX SHEET OF FLORIDA
 APPROVED CONNECTORS WITH THE PRODUCTS HIGHLIGHTED OR
 PROVIDE THE PRODUCT APPROVALS
  
 11)STRUCTURAL DRAWINGS DO NOT SHOW BLOCK TO BE
 INSTALLED AT LOCATION OF EXISTING WOOD FRAME WALL AT
 NORTH EAST CORNER OF GARAGE ON THE FOUNDATION PLAN
  
 12)PROVIDE DETAIL FOR THE ATTACHMENT OF THE STEEL
 COLUMN BASE PLATE TO THE BLOCK COLUMN AT REAR DECK.
 WILL THERE BE A CONCRETE CAP OR IS BASE PLATE MOUNTED
 DIRECTLY TO THE GROUTED FILL CELLS?
  
 13)STRUCTURAL STEEL COLUMN DESIGNATION IN SCHEDULE
 DOES NOT MATCH PLAN DESIGNATION
  
 14)GUARDS AND HANDRAILS SHALL MEET THE LOAD
 REQUIREMENTS OF 1607.7.1.1 FBC
  
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-28 Cont ID  
Sent By btrobaug Date 2007-11-28 Time 17:18 Rev Time 0.00
Received By btrobaug Date 2007-11-28 Time 16:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-10-01 Cont ID  
Sent By btrobaug Date 2007-10-01 Time 17:11 Rev Time 0.00
Received By btrobaug Date 2007-10-01 Time 15:08 Sent To M
Notes
2007-10-01 17:10:57 
  
 PROVISO
  
 THE PANELS SHOWN BEHIND THE WASHER ON SHEET A-2 ARE IN
 VIOLATION OF ARTICLE 110.26. ALTHOUGH EXISTING, THE
 VIOLATION MUST BE CORRECTED AS IT IS A LIFE SAFETY
 ISSUE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 13:14 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 13:14 Sent To Z
Notes
2007-11-19 13:15:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-10-20 Time   Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 12:27 Sent To  
Notes
2007-09-24 12:33:09TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-10-10 Cont ID  
Sent By tgordon Date 2007-10-10 Time 16:49 Rev Time 0.25
Received By tgordon Date 2007-10-10 Time 16:49 Sent To B
Notes
2007-10-10 16:50:32NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-12 Cont ID  
Sent By jleech Date 2007-12-12 Time 08:43 Rev Time 0.00
Received By jleech Date 2007-12-12 Time 08:43 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-10-04 Cont ID  
Sent By jleech Date 2007-10-04 Time 09:10 Rev Time 0.00
Received By jleech Date 2007-10-04 Time 09:07 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-28 Cont ID  
Sent By choops Date 2007-11-28 Time 10:35 Rev Time 0.00
Received By choops Date 2007-11-28 Time 10:35 Sent To E
Notes
2007-11-28 10:36:17***APPROVED - RESUB #1***
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By choops Date 2007-09-27 Time 10:59 Rev Time 0.00
Received By choops Date 2007-09-27 Time 10:59 Sent To E
Notes
2007-09-27 11:04:33***FAILED***
  
  
 1)***NO SEPARATE DWELLING UNIT PERMITTED WITHIN THE
 SINGLE FAMILY LOW DENSITY (SF7) RESIDENTIAL ZONING
 DISTRICT***
  
 THE FOLLOWING COMMENT IS FOR YOUR INFORMATION ONLY:
  
 2)PLEASE PROVIDE TWO (2) COPIES OF ALL SUBMITTED
 PLANS (SURVEYS).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720
  