Plan Review Details - Permit 07090643
Plan Review Stops For Permit 07090643
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-27 Cont ID  
Sent By jwitmer Date 2008-08-27 Time 14:47 Rev Time 0.77
Received By jwitmer Date 2008-08-27 Time 14:47 Sent To  
Notes
2008-08-27 14:47:49GENERATOR PROVISO:
 THE INSTALLED ELEVATION OF THE EQUIPMENT SHALL BE
 REQUIRED TO BE DETERMINED AND CERTIFIED BY A QUALIFIED
 SURVEYOR, ENGINEER OR ARCHITECT, AS MEETING AT LEAST
 THE MINIMUM REQUIRED (BASE FLOOD ELEVATION PLUS SIX
 INCHES), FOR THE SPECIAL FLOOD HAZARD AREAIN WHICH IT
 IS INSTALLED.
 SPECIAL FLOOD ZONE AREA: A0
 BASE FLOOD:

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-04-18 Cont ID  
Sent By jwitmer Date 2008-04-18 Time 08:25 Rev Time 0.77
Received By jwitmer Date 2008-04-18 Time 08:25 Sent To  
Notes
2008-04-18 08:25:53GENERATOR PROVISO:
 THE INSTALLED ELEVATION OF THE EQUIPMENT SHALL BE
 REQUIRED TO BE DETERMINED AND CERTIFIED BY A QUALIFIED
 SURVEYOR, ENGINEER OR ARCHITECT, AS MEETING AT LEAST
 THE MINIMUM REQUIRED (BASE FLOOD ELEVATION PLUS SIX
 INCHES), FOR THE SPECIAL FLOOD HAZARD AREAIN WHICH IT
 IS INSTALLED.
 SPECIAL FLOOD ZONE AREA: A0
 BASE FLOOD:

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-23 Cont ID  
Sent By jwitmer Date 2007-10-23 Time 09:31 Rev Time 0.77
Received By jwitmer Date 2007-10-23 Time 09:00 Sent To  
Notes
2007-10-23 09:57:22BUILDING PLAN REVIEW
 PERMIT: 07090643
 ADD: 6901 OKEECHOBEE BLVD
 CONT: HUFFMAN GENERAL CONTRACTING
 TEL: (305)778-3437
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 2) DISCREPANCY, PLEASE SEE SHEET 2.0 VERSES E5.2,
 SUBMITTED ARE TWO DIFFERENT MONOLITHIC SLAB CONCEPTS,
 E5.2 DOES PROVIDE THE ANCHOR BOLT INFORMATION THAT IS
 MISSING ON THE
 SHEET 2.0. PLEASE CORRELATE THE TWO PLANS TO COENSIDE
 WITH EACH OTHER. 106.1.2. ADDITIONAL INFORMATION
 REQUIRED. THE ARCHITECT OF RECORD UNDER THE
 ARCHITECTURAL SHEET FAILED TO PROVIDE
 ANCHOR DETAIL. 1609.1.3. ANCHORAGE AGAINST OVERTURNING,
 UPLIFT AND SLIDING.
  
 3) BUILDING PROVISO: THE GENERATOR PAD IS LOCATED IN A
 **AO** FLOOD ZONE,STRUCTURE IS LOCATED IN AN "A"
 FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIREDBEFORE THE ISSUANCE OF
 A CERTIFICATE OF COMPLETION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-09-02 Cont ID  
Sent By dpalmer Date 2008-09-02 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2008-09-02 Time 11:13 Sent To  
Notes
2008-09-02 11:15:04SHEET E-5.1 HAD *TYPO* PER LON CARTER. REDLINE DTO ATS
 AS THE TRANSFER SWITCH PER SPECS AND RISER IS
 *AUTOMATIC* NOT MTS AS NOTED IN PART PLAN.
 THIS WAS CONFRIMED BY MR. CARTER ON PHONE CALL 9/2/08

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-08-29 Cont ID  
Sent By dpalmer Date 2008-08-29 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2008-08-29 Time 16:20 Sent To  
Notes
2008-08-29 16:21:03 
  
  
  
 ** DENIED 5TH TIME**
  
  
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW. PLANS
 IN LOWER RIGHT HAND CORNER INDICATES A * AUTOMATIC
 TRANSFER SWITCH MTS-FMC* AND YET THE RISER STATES
 ***ATS-FMC**> THIS WAS GONE OVER EXTENSIVELY WITH THE
 ENGINEER OF RECORD PREVIOUS TO PLANS BEING RE-DONE AND
 RE-SUBMITTED YET THE SAME INCONSISTENCIES EXIST. THIS
 OFFICE OR REVIEWER HAS NO AUTHORITY TO REVISE OR ADJUST
 PLANS NOR DOES THIS REVIEW HAVE THE RIGHT TO REDLINED
 PLANS BASED ON WHAT THE ENGINEER MAY OR MAY NOT WANT AS
 HIS/HER DESIGN. IT IS NOT FOR THE REVIEWER TO DECIDE
 WHAT THE DESIGNERS INTENT IS.
 THIS REVIEWER HAS CALLED MR. LON CARTER AND LEFT A
 VOICE-MAIL AS OF THIS REVIEW. MR. CARTER IS OUT OF THE
 OFFICE UNTIL TUESDAY THE 2ND OF SEPT.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 12:15 Sent To  
Notes
2008-07-18 12:15:14** DENIED 4TH REVIEW **
  
 ** NEW COMMENTS DUE TO ITEMS NOW CHANGED WHICH WERE NOT
 ON PREVIOUS PLANS. THERE IS ALSO ONE COMMENT WHICH HAS
 BEEN THE SAME SINCE THE INITIAL REVIEW.
  
 1) NOTE: PLEASE SEE THE NEW SPECIFICATIONS SUBMITTED
 FOR THE TRANSFER SWITCH ONLY HAS ONE COPY IN SET.
 PLEASE ALSO SEE THE SPECS SHOW THIS BEING AN AUTOMATIC
 TRANSFER SWITCH HOWEVER DETAIL LABELED AS *PART PLAN*
 ON SHEET E5.1 NOW SHOWS A MTS FOR MANUAL TRANSFER
 SWITCH AND THE RISER SHOWS ATS FOR AUTOMATIC TRANSFER
 SWITCH. IN THE LAST CONVERSATION WITH THE ENGINEER OF
 RECORD THE COMMENT WAS THE TRANSFER SWITCH WAS GOING TO
 BE MANUAL, HOWEVER APPLICATION, RISER SPECS AND OTHER
 INFORMATION INDICATES AUTOMATIC.
 WHICH ONE WILL IT BE?
 PLEASE SEE LOAD SUMMARY ON SHEET 5.2 WHICH CALLS FOR
 MAINS FOR PANELS A AND B AND A MAIN #3 FOR PANEL *C*.
 HOW ARE THE DISCONNECTS ON THE LOAD SIDE OF THE SINGLE
 MAIN SHOWN ON RISERNOW CALLED *MAINS* ON THE LOAD
 SUMMARY?
  
 PLEASE CORRECT PLANS.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 LIFE SAFETY CODE/ NFPA-101. PREVIOUS PLANS CALLED FOR A
 2005 NFPA-101 AND THE REVIEW NOTES STATED THERE WAS NO
 SUCH CODE. THE REVIEW NOTES GAVE THE CODE IN AFFECT
 WHICH WAS ADOPTED BY FS 553.73 YET THE PLANS NOW
 REFLECT A 2006 NFPA-101. HOW CAN A CODE BE REFERENCED
 ON DESIGN PLANS WHEN THE 2006 LIFE SAFETY CODE IS NOT
 SCHEDULED TO BE ADOPTED BY THE STATE OF FLORIDA UNTIL
 THE END OF 2008?
 NO JURISDICTION IS PERMITTED TO ADOPTED ANY CODE UNLESS
 ADOPTED BY THE STATE OF FLORIDA.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-22 Cont ID  
Sent By dpalmer Date 2008-05-22 Time 13:30 Rev Time 0.00
Received By dpalmer Date 2008-05-22 Time 13:29 Sent To  
Notes
2008-05-22 13:42:31** DENIED 3RD REVIEW**
  
  
 1) NOTE: THE NOTES BELOW ARE THE SAME COMMENTS AS THE
 PREVIOUS REVIEW. AS THE SAME PLANS WERE RE-SUBMITTED
 WIHT NO CORRECTIONS THE SAME COMMENTS APPLY.
  
 2) NOTE: PLEASE SEE A FEE HAS NOW BEEN ASSESSED AS
 REQUIRED PER FS 553.80(2)(B) FOR REPEAT CODE COMPLIANCE
 COMMENTS.
  
 3) NOTE: PLEASE SEE ONE OF THE COMMENTS BELOW FROM
 PREVIOUS REVIEW WITH RESPECTTO VALUE WAS IN A
 RESPONSE LETTER WHICH MENTIONS VALUE FOR COMPLETE SCOPE
 WAS INCREASED HOWEVER THIS WAS NOT DONE WHEN PLANS WERE
 RESUBMITTEED. THE APPLICAITON WAS NOT CHANGED ETC. THIS
 VALUE HAS BEEN CHANGED AND FEES WILL BE DUE BEFORE
 RESUBMITTING PLANS.
  
 4) NOTE: TOTAL FEES DUE INCLUDING NOTES 2 AND 3 IS
 $5,400
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEWS WHICH ARE
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE NOT
 ACCURATE ON PLANS. IF THIS WAS THE ONLY COMMENT THESE
 COULD HAVE BEEN RED-LINED HOWEVER PLANS ARE COMING BACK
 FOR OTHER COMMENTS.
 PLEASE SEE THE FOLLOWING CODES SHALL BE STATED. 2002
 NFPA-110. (PLANS STATE 2005 NFPA-110 WHICH DOES NOT
 EXIST).
 2003 NFPA-101. (PLANS STATE 2005 NFPA-101WHICH DOES NOT
 EXIST).
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE APPLIED
 SCOPE OF DOES NOT MEET THE TABLES FOR THE SCOPE OF WORK
 FOR ALL TRADES.
 PLEASE SE RESPONSE LETTER MENTIONS THE APPLIED VALUE IS
 NOW $200K HOWEVER THE PERMIT APPLICATION, THE RE-SUB
 COVER SHEET ETC WAS NOT UPDATED,
 FBC 108.3
  
 3) NOTE: PLEASE SEE THE SPECS/MANUFACTURES CUT SHEETS
 SUBMITTED DO NOT CORRELATE WITH PLANS.
 THESE INDICATE A KOHLER ATS AND THE PLANS NOW INDICATE
 CUTLER HAMMER.
 WHICH ONE WILL BE INSTALLED?
 PLEASE SEE THAT IN EITHER CASE THE SPECIFICATIONS ON
 PLANS ARE NOT EASILY READ AND ARE *BLURRY* TO READ
 DETAILS REQUIRED.
 PLEASE SEE NEC 225.31-225.39 AS THE DISCONNECTING MEANS
 IS NOT READILY AVAILABLE BASED ON PLANS SUBMITTED.
 PLEASE SEE THE SECTIONS MENTIONED ABOVE AS THE
 DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD SERVED
 AND SHALL BE LOCATED ON THE OUTSIDE OF EQUIPMENT WITH
 OUT EXPOSING ANY INDIVIDUAL TO LIVE PARTS. 110.27.
 PLEASE SEE THE PICTURE DOES APPEAR TO SHOW TWO BREAKERS
 HOWEVER DOES NOT APPEAR TO MEET CODE AS STATED ABOVE.
 THIS IS BASED ON PLANS SUBMITTED AND THE TWO SETS OF
 DOCUMENTS.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT CODE COMPLIANT COMMENTS. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
 ** PLANS MAY BE RETAINED BY THIS OFFICE.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-14 Cont ID  
Sent By dpalmer Date 2008-04-14 Time 18:28 Rev Time 0.00
Received By dpalmer Date 2008-04-10 Time 17:14 Sent To  
Notes
2008-04-14 18:28:30** DENIED 2RD REVIEW**
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEWS WHICH ARE
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE NOT
 ACCURATE ON PLANS. IF THIS WAS THE ONLY COMMENT THESE
 COULD HAVE BEEN RED-LINED HOWEVER PLANS ARE COMING BACK
 FOR OTHER COMMENTS.
 PLEASE SEE THE FOLLOWING CODES SHALL BE STATED. 2002
 NFPA-110. (PLANS STATE 2005 NFPA-110 WHICH DOES NOT
 EXIST).
 2003 NFPA-101. (PLANS STATE 2005 NFPA-101WHICH DOES NOT
 EXIST).
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE APPLIED
 SCOPE OF DOES NOT MEET THE TABLES FOR THE SCOPE OF WORK
 FOR ALL TRADES.
 PLEASE SE RESPONSE LETTER MENTIONS THE APPLIED VALUE IS
 NOW $200K HOWEVER THE PERMIT APPLICATION, THE RE-SUB
 COVER SHEET ETC WAS NOT UPDATED,
 FBC 108.3
  
 3) NOTE: PLEASE SEE THE SPECS/MANUFACTURES CUT SHEETS
 SUBMITTED DO NOT CORRELATE WITH PLANS.
 THESE INDICATE A KOHLER ATS AND THE PLANS NOW INDICATE
 CUTLER HAMMER.
 WHICH ONE WILL BE INSTALLED?
 PLEASE SEE THAT IN EITHER CASE THE SPECIFICATIONS ON
 PLANS ARE NOT EASILY READ AND ARE *BLURRY* TO READ
 DETAILS REQUIRED.
 PLEASE SEE NEC 225.31-225.39 AS THE DISCONNECTING MEANS
 IS NOT READILY AVAILABLE BASED ON PLANS SUBMITTED.
 PLEASE SEE THE SECTIONS MENTIONED ABOVE AS THE
 DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD SERVED
 AND SHALL BE LOCATED ON THE OUTSIDE OF EQUIPMENT WITH
 OUT EXPOSING ANY INDIVIDUAL TO LIVE PARTS. 110.27.
 PLEASE SEE THE PICTURE DOES APPEAR TO SHOW TWO BREAKERS
 HOWEVER DOES NOT APPEAR TO MEET CODE AS STATED ABOVE.
 THIS IS BASED ON PLANS SUBMITTED AND THE TWO SETS OF
 DOCUMENTS.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT CODE COMPLIANT COMMENTS. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
 ** PLANS MAY BE RETAINED BY THIS OFFICE.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By dpalmer Date 2007-10-16 Time 09:27 Rev Time 0.00
Received By dpalmer Date 2007-10-15 Time 16:58 Sent To  
Notes
2007-10-16 09:27:47 
  
 **** DENIED ****
  
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW UNDER
 EXPIRED PERMIT ARE STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SOME NEW COMMENTS BASED ON
 PLANS/DOCUMENTS SUBMITTED.
  
  
 1) NOTE:PLEASE KNOW AS THE PERMIT APPLICATION DATE
 HAS CHANGED.
 PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT CODES ARE
 STATED ON PLANS.
 PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER
 DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A
 MINIMUM.
 PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE
 REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE
 FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS
 FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (2002 SHOWN ON PLANS)
  
 IF THIS WAS THE ONLY COMMENT PLANS WOULD HAVE BEEN
 REDLINED, HOWEVER THEY ARE COMING BACK FOR OTHER
 COMMENTS.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORKWAS STILL NOT INCREASED. THE VALUE IS REQUIRED TO
 BE BASED ON ALL LABOR, MATERIALS, EQUIPMENT, DESIGN
 COST ETC EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 BASED ON ALL THE WORK AS SHOWN ON PLANS ETC THE VALUE
 AS APPLIED IS VERY LOW.
 IF AN APPROPRIATE VALUE IS NOT ADJUSTED, ONE WILL BE
 ASSESSED.
 FBC 108.3
  
 3) NOTE: PLEASE CLARIFY WHY THE GENERATOR SUBMITTALS
 CONTAIN A SEPARATE ELECTRICAL CONTRACTOR ON THE LISTING
 OF COVER SHEET.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 ATS SWITCHES WHICH ARE BEING SHOWN ON THE RISER. PLEASE
 SEE THE NEXT COMMENT FOR DISCONNECTING MEANS REQUIRED.
 FBC 106.1.2.
 NEC 90.7, 110.3.
  
 4) NOTE: PLEASE SEE THE RISER DOES NOT INCLUDE A
 DISCONNECTING MEANS FOR FEEDERS COMING FROM THE
 GENERATOR.
 225.31-225.39.
 (MAY NOT USE BREAKER ON THE GENERATOR AS IT DOES NOT
 MEET 702.11)
 PLEASE INCLUDE DISCONNECT/DISCONNECTS ON THE FEEDERS
 EITHER ON THE LINE SIDE OF GUTTER FROM GENERATOR, OR
 LOAD SIDE OF ATS DEVICES.
 IF THE ATS DEVICES CONTAIN A BREAKER FOR NORMAL SIDE
 AND A BREAKER FOR EMERGENCY SIDE, PLEASE ADJUST RISER
 ACCORDINGLY AND PLEASE BE SURE SPECS/CUT SHEETS
 INDICATE THIS.
 110.3, 90.7, 225.31-225.39, 702.11 ETC
  
 5) NOTE: PLEASE SEE CIRCLED NOTE # 1 ON RISER ON THE
 METER CAN STILL DOES NOT SEEM TO BE AN ACCURATE NOTE.
 THE NOTE CALLS FOR THIS METER AS A CT METER ENCLOSURE,
 HOWEVER A CT METER ENCLOSURE WOULD NOT INCLUDE A METER
 WHICH IS BEING SHOWN ON BOTH RISERS AND PLANS.
 PLEASE ADJUST.
 IF THIS IS A CT ENCLOSURE, CHANGE RISER TO SHOW THE CT
 METER LOCATION.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE GENERATOR SLAB DETAIL ON E-5.2
 IS NOT AS THE SAME AS THE SLAB/FOOTING DETAIL ON
 ARCHITECTURAL SHEET 2.0.
 PLEASE SEE BUILDING REVIEW COMMENTS. THIS IS NOTED FOR
 INFORMATION ONLY AS BOTH OF THESE NEEDS TO COORDINATE.
 FBC 106.1.2
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-16 07:59:202007-10-16 07:59:20
  
 IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-09-05 Cont ID  
Sent By mawillia Date 2008-09-05 Time 12:34 Rev Time 0.00
Received By mawillia Date 2008-09-05 Time 12:22 Sent To B
Notes
2008-09-05 12:34:38*****APPROVED*****
  
  
  
 PLAN SHEETS 2.0 AND E0.1 WERE STAMPED, INITIALED, AND
 DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-08-07 Cont ID  
Sent By mawillia Date 2008-08-07 Time 13:01 Rev Time 0.00
Received By mawillia Date 2008-09-05 Time 12:21 Sent To  
Notes
2008-08-07 13:01:01*****PROVISO*****
  
  
  
 PLEASE BE ADVISED THAT THE 2003 EDITION OF NFPA 101
 SHALL BE REFERENCED; PLAN SHEET E0.1 TO BE FIRE-STAMPED
 WHEN THE COMMENT HAS BEEN ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-28 Cont ID  
Sent By mawillia Date 2008-05-28 Time 18:23 Rev Time 0.00
Received By mawillia Date 2008-05-28 Time 18:13 Sent To  
Notes
2008-05-28 18:22:31*****UNSAT*****
  
 (THE BELOW COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW
 STILL HAS NOT BEEN ADDRESSED:)
  
 PLAN SHEET E0.1 TO BE FIRE-STAMPED WHEN THE OTHER PLAN
 REVIEWERS HAVE BEEN SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-05-02 Cont ID  
Sent By mawillia Date 2008-05-02 Time 14:15 Rev Time 0.00
Received By mawillia Date 2008-05-02 Time 14:04 Sent To  
Notes
2008-05-02 14:11:09*****PROVISO*****
  
  
 PLAN SHEET E0.1 TO BE FIRE-STAMPED WHEN THE OTHER PLAN
 REVIEWERS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-10-23 Cont ID  
Sent By mcarsill Date 2007-10-23 Time 11:13 Rev Time 0.00
Received By mawillia Date 2007-10-23 Time 14:03 Sent To  
Notes
2007-10-23 11:13:211. SEVERAL REVISION CLOUDS EXIST ON PAGE EO.1 THAT
 PROVIDES INFORMATION RELATING TO THE GENERATOR
 INSTALLATION. ON PAGE EO.1 A REVISION CLOUD STATES "THE
 INSTALLATION OF THE PROPOSED STRUCTURE SHALL IN NO WAY
 OBSTRUCT EMERGENCY RESPONSE AND TO SAID PROPERTY AND/OR
 VICINITY".
  
 2. NFPA 241 IS ALSO CALLED OUT IN A REVISION CLOUD ON
 PAGE EO.1.
  
 3. APPROPRIATE LABELS AND SIGNAGE SHALL BE PROVIDED FOR
 THE FUEL TANK.
  
 4. THE CONCRETE BOLLARDS DISPLAYED ON PLANS SHALL
 PROVIDE THE NECESSARY PROTECTION FOR THE GENERATOR AND
 FUEL TANK.
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2007-11-11 Cont ID  
Sent By rregueir Date 2007-11-11 Time 13:20 Rev Time 0.00
Received By rregueir Date 2007-11-11 Time 13:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-18 Cont ID  
Sent By adarroug Date 2008-08-18 Time 11:24 Rev Time 0.00
Received By adarroug Date 2008-08-18 Time 11:24 Sent To  
Notes
2008-08-18 11:27:21TO "COMM" BD#57

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-14 Cont ID  
Sent By adarroug Date 2008-07-14 Time 16:23 Rev Time 0.00
Received By adarroug Date 2008-07-14 Time 16:23 Sent To  
Notes
2008-07-14 16:26:14TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-06 Cont ID  
Sent By adarroug Date 2008-05-06 Time 15:14 Rev Time 0.00
Received By adarroug Date 2008-05-06 Time 15:14 Sent To  
Notes
2008-05-06 15:17:57TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 14:08 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 14:08 Sent To  
Notes
2008-04-07 14:14:57TO "COMM" BD#52

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2007-11-11 Time 14:07 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 14:02 Sent To  
Notes
2007-10-15 10:39:16TO "COMM" BD#31
2007-09-24 14:02:35WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-29 Cont ID  
Sent By rregueir Date 2008-08-29 Time 14:12 Rev Time 0.00
Received By rregueir Date 2008-08-29 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-22 Cont ID  
Sent By rregueir Date 2008-05-22 Time 09:17 Rev Time 0.00
Received By rregueir Date 2008-05-22 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-01 Cont ID  
Sent By rregueir Date 2008-05-01 Time 09:18 Rev Time 0.00
Received By rregueir Date 2008-04-29 Time 10:58 Sent To  
Notes
2008-05-01 09:17:54REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 FROM PREVIOUS REVIEW COMMENT #1: PLEASE PROVIDE PRODUCT
 APPROVAL DOCUMENTATION WHICH INCLUDES THE COVER SHEET
 FROM THE APPROVING AGENCY AND THE APPROVED INSTALLATION
 INSTRUCTIONS, MARKED AS APPROVED IN WRITING BY THE
 DESIGNER OF RECORD FOR THIS PROJECT IN ACCORDANCE WITH
 FBCB 106.3.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-11 Cont ID  
Sent By rregueir Date 2007-11-11 Time 13:34 Rev Time 0.00
Received By rregueir Date 2007-11-11 Time 13:23 Sent To  
Notes
2007-11-11 13:34:53REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. WALL LOUVER AS SHOWN ON PLANS IS CLASSIFIED AS A
 PANEL WALL PER FAC RULE 9B-72. AS SUCH, PRODUCT
 APPROVAL IS REQUIRED. PROVIDE A PRODUCT APPROVAL
 SPECIFIC TO THE MANUFACTURER AND MODEL OF LOUVER TO BE
 USED. FOR MORE INFORMATION ON THE FLORIDA PRODUCT
 APPROVAL SYSTEM PLEASE VISIT WWW.FLORIDABUILDING.ORG.
 NOTE: THOSE PRODUCTS WHICH ARE REGULATED BY RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP DRAWING
 REVIEW STAMP W/ SIGNATURE WILL SUFFICE) BY THE DESIGNER
 OF RECORD PRIOR TO SUBMITTAL IN ACCORDANCE WITH FBC
 106.3.3.
  
 2. ON SITE PLAN, PROVIDE DISTANCES FROM PROPERTY LINES
 AND ADJACENT BUILDINGS. ALSO, SHOW ELEVATION OF
 EQUIPMENT IN ACCORDANCE WITH FBC,M 301.14.
  
 3. APPLIANCES SERVING DIFFERENT AREAS OF A BUILDING
 OTHER THAN WHERE THEY ARE INSTALLED SHALL BE
 PERMANENTLY MARKED IN AN APPROVED MANNER THAT UNIQUELY
 IDENTIFIES THE APPLIANCE AND THE AREA IT SERVES. FBC,M
 304.11
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-16 Cont ID  
Sent By kdfreema Date 2008-04-16 Time 10:50 Rev Time 0.00
Received By kdfreema Date 2008-04-16 Time 10:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-09-25 Cont ID  
Sent By kdfreema Date 2007-09-25 Time 08:49 Rev Time 0.00
Received By kdfreema Date 2007-09-25 Time 08:49 Sent To  
Notes
***NONE***