Plan Review Details - Permit 07090628
Plan Review Stops For Permit 07090628
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-08 Cont ID  
Sent By jwitmer Date 2009-04-08 Time 09:07 Rev Time 1.11
Received By jwitmer Date 2009-04-08 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By jwitmer Date 2008-06-16 Time 13:26 Rev Time 0.77
Received By jwitmer Date 2008-06-16 Time 13:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-16 Cont ID  
Sent By jwitmer Date 2007-10-16 Time 16:43 Rev Time 0.66
Received By jwitmer Date 2007-10-16 Time 16:43 Sent To  
Notes
2007-10-16 16:50:15BUILDING PLAN REVIEW
 PERMIT: 07090628
 ADD: 2800 N FLAGLER DR
 CONT: SCHEHR CONSTRUCTION
 TEL: (954)415-5705
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 2) SHEET 7 OF 8 GENERAL NOTES WIND THE IMPORTANCE
 FACTOR IS PROVIDED AS 1.0 PLEASE SEE ASCE 7-02 TABLE
 1-1DESIGNATED EMERGENCY PREPAREDNESS, COMMUNICATIONS
 THIS SITE AND ALL CELLULAR TOWERS ARE REQUIRED BY STATE
 STATUTE TO HAVE THE GENERATOR BACKUP AS PART OF THE
 DESIGNATED EMERGENCY COMMUNICATIONS SYSTEMS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-07 Cont ID  
Sent By dpalmer Date 2009-04-07 Time 15:15 Rev Time 0.00
Received By dpalmer Date 2009-04-07 Time 15:15 Sent To  
Notes
2009-04-07 15:15:568 HRS REQUIRED BACK UP PROVIDED BY BATTERIES.
 SIGNAGE FOR FUEL SHUT OFF.
 FIRE COMMAND RM ANNUNCIATOR
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-13 Cont ID  
Sent By dpalmer Date 2008-06-13 Time 14:36 Rev Time 0.00
Received By dpalmer Date 2008-06-13 Time 14:36 Sent To  
Notes
2008-06-13 14:36:20** DENIED **
  
 1) NOTE: PLEASE SHOW LOCATION OF PROPOSED FUEL SHUT OFF
 IN THE PROXIMITY OF THE MAIN ELECTRICAL SWITCH GEAR.
 PLEASE PROVIDE NOTES AND ACTUAL WORDING FOR PROPOSED
 SIGNAGE AT THE MAIN ELECTRICAL EQUIPMENT LOCATION AS
 WELL AS ANY FIRE COMMAND ROOM, ACTUAL FUEL SHUT OFF
 LOCATION AND FIRE ENUNCIATOR LOCATION. ANY SIGNAGE IN
 BUILDING WHICH DIRECT EMERGENCY PERSONNEL TO THE
 LOCATIONS TO SHUT DOWN POWER ETC IN AN EMERGENCY SHALL
 BE STATED ON PLANS AND WILL BE VERIFIED IN FIELD.
  
 AS STATED IN PART 12 OF TITLE 47 THE TIME FOR BACK UP
 ARE REQUIRED TO BE A MINIMUM OF 8HRS. PLEASE SHOW THE
 EXISTING BATTERY BACK UP UNITS.
  
 AS PLANS ARE COMING BACK FOR COMMENTS PLEASE SUPPLY AT
 THIS TIME.
  
 ** AS STATED ON PREVIOUS AS NOT ALL ITEMS ARE SHOWN AS
 OF YET THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 14:23 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 13:52 Sent To  
Notes
2007-10-14 14:23:15 
 ** DENIED**
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110 ( FBC CHAPTER 27 REFERENCED.
  
 2) NOTE: PLEASE SEE THIS APPEARS BY ALL INFORMATION TO
 THIS REVIEWER TO BE A LEGALLY REQUIRED SYSTEM PER FS
 365.172 AND TITLE 47 OF FEDERAL REGULATION CODES WHICH
 WOULD REQUIRED A ON-SITE FUEL FOR BACK UP OF THE
 GENERATOR PER 701.11B3 AND NFPA-1221
 PLEASE SEE REQUIREMENTS FROM THE FIRE MARSHAL AS A
 *ROOF-TOP* LP MAY NOT BE PERMITTED.
  
 3) NOTE: PLEASE CLARIFY HOW THE DISCONNECTING MEANS FOR
 POWER TO BUILDING IS GROUPED OR IN CLOSE PROXIMITY.
 230.72.
 THE *SHUNT-TRIP* KILL SWITCH AS SHOWN DOES NOT MEET THE
 REQUIREMENTS OF 230.76, 230.79.
 ** A COMPLETE SHUT DOWN OF FUEL SUPPLY WOULD BE
 REQUIRED AT A MINIMUM. LOCATION ETC WOULD NEED TO BE
 GONE OVER ONCE ALL REVIEWS ARE DONE FROM ALL TRADES.
  
 4) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEET
 WHICH CORRELATE WITH PLANS AND PERMIT APPLICATION FOR
 GENERATOR. SPECS/CUT SHEETS INDICATE 25 AND 27KW UNIT,
 NOT 30.
 90.7, 110.3
  
 5) NOTE: PLEASE PROVIDE LOAD ON THE GENERATOR AND TIME
 ON ON-SITE FUEL TO BE DETERMINED.701.5
  
 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK INCLUDING ALL LABOR, MATERIALS AND EQUIPMENT EVEN
 IF ANY OF THESE ITEMS ARE SUPPLIED BY THE OWNER. AS GAS
 IS APPLIED FOR AT THIS TIME, THIS VALUE SHALL ALSO BE
 INCLUDED.
 PLEASE KEEP IN MIND AS SCOPE OF MAY CHANGE DUE TO
 COMMENTS, THE VALUE MAY ALSO NEED TO BE ADJUSTED. THIS
 ALSO INCLUDES VALUE FOR DESIGN FEES (PLANS). FBC 108.3
  
 ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR
 REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS
 SUBMITTED.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-04-14 Cont ID  
Sent By mawillia Date 2009-04-14 Time 12:36 Rev Time 0.00
Received By mawillia Date 2009-04-14 Time 12:17 Sent To  
Notes
2009-04-14 12:34:37*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS 3 & 7 (OF 7) AND ELECTRICAL
 SITE PLAN (1 OF 1) WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-06-30 Cont ID  
Sent By mwennerg Date 2008-06-30 Time 14:28 Rev Time 0.00
Received By mwennerg Date 2008-06-30 Time 14:28 Sent To  
Notes
2008-06-30 14:32:45***DENIED***
  
 PLEASE SEE ATTACHED COMMENTS FROM FIRST FIRE PLAN
 REVIEW. ALTHOUGH A RESPONSE LETTER IS NOT MANDATORY, IT
 WOULD BE HELPFUL AS THIS WRITER DID NOT CONDUCT THE
 FIRST PLAN REVIEW. PLEASE NOTE THAT RESPONSES WERE
 SUBMITTED FOR OTHER TRADES. SOME OF THE PREVIOUS
 COMMENTS WOULD REQUIRE AN EXPLANATION OR
 CLARIFICATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mcarsill Date 2007-10-22 Time 15:25 Rev Time 0.00
Received By mcarsill Date 2007-10-22 Time 14:57 Sent To  
Notes
2007-10-22 15:25:521. WRONG INSPECTIONS DEPARTMENT LISTED ON PAGE 1. LISTS
 PALM BEACH COUNTY INSTEAD OF WEST PALM BEACH.
  
 2. ANY INSTALLATION OF EQUIPMENT SHALL NOT INTERFERE
 WITH ANY EXISTING FIRE SAFETY EQUIPMENT LOCATED ON THE
 ROOF OR WITHIN THE BUILDING.
  
 3. NO ROUTING OF ELECTRICAL CONDUITS OR PIPING SHALL
 OCCUR WITHIN ANY REQUIRED STAIRWELL FOR THE BUILDING.
  
 4. WHAT SYSTEMS WILL THE GENERATOR BE PROVIDING STANDBY
 POWER FOR. IF ONLY USED FOR COMMUNICATION PURPOSES, IS
 IT LEGALLY REQUIRED TO HAVE STANDBY FUEL SUPPLIES.
 PLEASE PROVIDE MORE DETAILS.
  
 5. PLEASE EXPLAIN INSTALLATION OF FUEL LINE THROUGH
 EXISTING BALCONIES.
  
 6. PLEASE PROVIDE ALL APPLICABLE LISTINGS FOR THE
 GENERATOR.
  
 7. NO PROPANE STORAGE TANKS ARE ALLOWED TO BE INSTALLED
 ON THE ROOF. IF A SECONDARY FUEL SUPPLY IS NECESSARY IT
 WILL NOT BE ALLOWED TO BE STORED ON THE ROOF.
  
 8. A RISER DIAGRAM OF GAS PIPING SHOULD BE PROVIDED
 ILLUSTRATING THE RUN OF PIPING IN RELATION TO BUILDING
 ELEMENTS TO INCLUDE DOORS, WINDOWS, AND OTHER FEATURES
 OF THE BUILDING.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2007-11-11 Cont ID  
Sent By rregueir Date 2007-11-11 Time 10:10 Rev Time 0.00
Received By rregueir Date 2007-11-11 Time 10:10 Sent To  
Notes
2007-11-11 10:09:57REVIEW #: 1ST
 ACTION: NOT REQUIRED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 AT THIS TIME THE SCOPE OF WORK DOES NOT INDICATE
 ON-SITE FUEL STORAGE. IF THIS SHOULD CHANGE WITH FUTURE
 RESUBMITTAL, PLANS WILL BE REVIEWED FOR COMPLIANCE AT
 THAT TIME.
 NOTE: FUEL STORAGE, PIPING AND REFUELING SYSTEMS FOR
 STATIONARY COMBUSTION ENGINES SHALL COMPLY WITH NFPA
 37-02 AND NFPA 30-00 IN ACCORDANCE WITH FBC,M SECTION
 915.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-04-17 Cont ID  
Sent By kstevens Date 2009-04-17 Time 13:54 Rev Time 0.00
Received By kstevens Date 2009-04-17 Time 13:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-06-05 Cont ID  
Sent By jleech Date 2008-06-05 Time 09:10 Rev Time 0.00
Received By jleech Date 2008-06-05 Time 07:25 Sent To  
Notes
2008-06-05 09:36:15DENIED;
  
 (ONE COPY OF OLD PLANS WAS NOT SUBMITED)
 OLD COMMENTS 1 AND 2, OK
 NEW COMMENTS;
 1.TYPE OF GAS PIPE USED? I.E. BLACK IRON, GALV. ETC.
 PLEASE LIST ON PLAN.
 2.SIZE ALL PIPE.
 3. PAGE 3 OF 3 " DESIGN PARAMETER" SHOWS INLET PRESSURE
 AT 14 "WC, USING FBC FUEL GAS CODE TABLE 402.4(5) PIPE
 WOULD BE 2 1/2".
 4. A REGULATOR IS CALLED FOR AT GENERATOR, AT 1/2 LB
 REGULATOR IS NOT REQUIRED. IF PRESSURE IS CHANGED
 SUBMIT MANUFACTURE AND MOLEL NUMBER OF REGULATOR TO BE
 USED. THE SHUTOFF VALVE SHOWN ON ISOMETRIC AT GENERATOR
 SHOULD BE UP STREAM OF REGULATOR AND A UNION IS
 REQUIRED BEFORE GENERATOR.
 5. TYPE OF GAS USED NATURAL OR L.P.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-11-21 Cont ID  
Sent By jleech Date 2007-11-21 Time 09:04 Rev Time 0.00
Received By jleech Date 2007-11-21 Time 07:49 Sent To  
Notes
2007-11-21 09:17:53DENIED;
 1.SHOW THE PIPE SUPPORT SPACING PERFBC FUELGAS
 TABLE 415.
 2. ADD NOTE TO GAS PIPING PAGES, " METALLIC PIPING AND
 FITTINGS COATED WITH A CORROSION-RESISTANT MATERIAL
 SHALL BE USED ". SEE SECTION 403.8.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-12 Cont ID  
Sent By adarroug Date 2009-03-12 Time 11:43 Rev Time 0.00
Received By adarroug Date 2009-03-12 Time 11:43 Sent To  
Notes
2009-03-12 11:47:27TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 14:54 Sent To  
Notes
2008-05-19 14:56:18TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-21 Cont ID  
Sent By jleech Date 2007-11-21 Time 09:19 Rev Time 0.00
Received By jleech Date 2007-09-24 Time 08:22 Sent To  
Notes
2007-10-12 16:52:23TO "COMM" BD#7
2007-09-24 08:22:38WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2009-03-30 Cont ID  
Sent By rregueir Date 2009-03-30 Time 15:08 Rev Time 0.00
Received By rregueir Date 2009-03-30 Time 15:08 Sent To  
Notes
2009-03-30 15:11:11GAS GENERATOR. NO FURTHER MECHANICAL REVIEW REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-06-16 Cont ID  
Sent By rregueir Date 2008-06-16 Time 10:48 Rev Time 0.00
Received By rregueir Date 2008-06-16 Time 10:48 Sent To  
Notes
2008-06-16 10:50:16PREVIOUS COMMENTS ADDRESSED. PLANS WILL NOT BE STAMPED
 FOR MECHANICAL COMPLIANCE AS THIS IS A GAS APPLIANCE
 AND SUBJECT TO GAS REVIEW BY THE PLUMBING PLAN
 REVIEWER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-11 Cont ID  
Sent By rregueir Date 2007-11-11 Time 11:32 Rev Time 0.00
Received By rregueir Date 2007-11-11 Time 10:19 Sent To  
Notes
2007-11-11 11:32:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE SHOW THE LOCATION OF ALL OUTSIDE AIR INTAKES,
 GRAVITY VENTS AND OPENINGS INTO THE BUILDING AND THEIR
 RELATED DISTANCE TO THE GENERATOR EXHAUST TO SHOW
 COMPLIANCE WITH FBC,M 401.5.1 AND FBC,M 501.2.
  
 2. THE AIR SUPPLY FOR THE ENGINE SHALL BE DESIGNED TO
 MEET AT LEAST THE MINIMUM REQUIREMENTS FOR COMBUSTION,
 COOLING, AND VENTILATION, AND TO PREVENT FLUE GAS
 PRODUCTS FROM BEING DRAWN FROM STACKS OR FLUES OF
 BOILERS OR OTHER COMBUSTION DEVICES. SHOW THE LOCATION
 OF ANY VENTS OR STACKS ON THE ROOF AND THEIR DISTANCES
 FROM THE COMBUSTION/VENTILATION AIR INTAKES FOR THE
 GENERATOR IN ACCORDANCE WITH NFPA 37-02 SEC 4.1.1.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-11-21 Cont ID  
Sent By jleech Date 2007-11-21 Time 09:19 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2009-02-12 Cont ID  
Sent By dfulcher Date 2009-02-12 Time 14:13 Rev Time 0.00
Received By dfulcher Date 2009-02-12 Time 14:12 Sent To  
Notes
2009-02-12 14:13:30EXTEND PERMIT APP TO 3/30/09 PER RREGUEIRO - DRF

Review Stop Z ZONING
Rev No 3 Status P Date 2009-03-17 Cont ID  
Sent By kdfreema Date 2009-03-17 Time 11:11 Rev Time 0.00
Received By kdfreema Date 2009-03-17 Time 11:11 Sent To  
Notes
2009-03-17 11:11:59PROPOSED GENERATOR DOES NOT EXCEED HEIGHT OF EXISTING
 ROOFTOP EQUIPMENT NOR IS IT VISIBLE FROM THE GROUND.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-05-21 Cont ID  
Sent By choops Date 2008-05-21 Time 14:10 Rev Time 0.00
Received By choops Date 2008-05-21 Time 14:10 Sent To  
Notes
2008-05-21 14:11:54***APPROVED - RESUB #1***
  
 *THE PROPOSED EQUIPMENT IS NOT HIGHER THAN THE EXISTING
 EQUIPMENT ON THE ROOF AND CANNOT BE SEEN FROM GROUND.
  
  
  
  
  
 SENT TO COMM. BOARD #39

Review Stop Z ZONING
Rev No 1 Status F Date 2007-10-18 Cont ID  
Sent By choops Date 2007-10-18 Time 13:10 Rev Time 0.00
Received By choops Date 2007-10-18 Time 13:10 Sent To  
Notes
2007-10-18 13:14:48***FAILED***
  
  
 1)PURSUANT TO SECTION 94-216(D)(9) OF THE CITY OF
 WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS:MECHANICAL SYSTEMS, BACKFLOW PREVENTERS,
 TELEVISION ANTENNAS, SATELLITE DISHES AND COMMUNICATION
 DEVICES SHALL BE SCREENED FROM VIEW BY LANDSCAPING OR
 BUILT ELEMENTS DESIGNED AS AN INTEGRAL PART OF THE
 BUILDING ARCHITECTURE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720