| | BUILDING PLAN REVIEW |
| | PERMIT: 07090550 |
| | ADD: 2800 N FLAGLER DR. #905 |
| | CONT: JOHN JOKI PESOLA GENERAL CONTRACTOR INC. |
| | TEL: (561)642-1776 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006/2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST. |
| | ACTION: DENIED 10/5/07 |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING: |
| | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | D)IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED F) |
| | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | |
| | . ------------------------------------- |
| | |
| | **NO RESPONSE NOT ADDRESSED** |
| | 3)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. **THIS APPEARS |
| | TO BE A LEVEL 2 ALTERATION**. |
| | |
| | 4) W. PALM BEACH AMENDMENTS 106.1.3 BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER.PENCIL DRAWN PLANS ARE NOT |
| | ACCEPTABLE. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME, DATE |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER |
| | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE, THEN |
| | HE/SHE SHALL SEAL THE DRAWINGS IN ACCORDANCE WITH |
| | CHAPTER 481 AND 471 OF THE FLORIDA STATUTES. |
| | |
| | 5)PROVIDE AN EXISTING AND PROPOSED FLOOR PLAN OF THE |
| | PROJECT INDICATING WHERE ALL WALLS WILL BE REMOVED AND |
| | IF NEW WALL WILL BE BUILT. CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED, AND SHOWS IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THE |
| | CODE AND RELEVANT LAWS. 106.1.1. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |