| 2007-09-28 19:24:55 | 2007-09-28 19:24:55 |
| | |
| | ** DENIED ** |
| | |
| | CORRECTIONS/ADJUSTMENTS NEEDED. |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** SOME OF THE ABOVE ARE NOTED ON PLANS. |
| | |
| | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, 13-103 AS THE NEW |
| | LIGHTING CONTROL DEVICES BEING REPLACED NEED TO CONTAIN |
| | AUTOMATED CONTROL.(MAXIMUM OF 30MINS FOR OCCUPANCY TYPE |
| | DEVICES AND 4HRS FOR TIMERS). |
| | |
| | 3) NOTE: PLEASE INDICATE THE CIRCUITING FOR NEW |
| | RECEPTACLES/LIGHTS AND TO WHICH PANEL THESE WILL BE FED |
| | FROM. |
| | PLEASE CLARIFY SIZE OF CONDUCTORS AND CIRCUIT |
| | AMPERAGE. |
| | PLEASE CLARIFY IF THIS SPACE IS ONE TENANT. THIS SEEMS |
| | TO BE THE CASE HOWEVER THIS IS NOT COMPLETELY CLEAR AT |
| | THIS TIME. |
| | |
| | ** PLEASE KNOW, IF ALL OTHER TRADES PASS THEIR REVIEW, |
| | A *PROVISO* MAY BE CONSIDERED FOR ISSUANCE OF PERMIT AS |
| | THE ABOVE ITEMS COULD BE ADJUSTED AND SUBMITTED AS A |
| | REVISION BEFORE ROUGH. |
| | THIS IS ONLY IF ALL OTHER TRADES PASS REVIEWS. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |