| Plan Review Stops For Permit 07090539 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-04-17 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-04-17 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-04-17 |
Time |
14:16 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2008-04-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-04-08 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-04-07 |
Time |
15:38 |
Sent To |
PC |
|
| Notes |
| 2008-04-08 07:10:05 | BUILDING PLAN REVIEW | | | PERMIT: 07090539 | | | ADD: 5601 CORPORATE WAY #200 | | | CONT: CLAY KOHLMEYER GEN. CONTR INC. | | | TEL: (561)694-1214 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: REVISION | | | ACTION: DENIED | | | | | | 1)ALL PLANS AND SPECIFICATIONS SUBMITTED BY AN | | | ENGINEER BEING FILED FOR PUBLIC RECORD SHALL HAVE THE | | | ORIGINAL SEAL, SIGNATURE AND DATE ON SUCH INFORMATION. | | | IF PRACTICING THROUGH A DULY AUTHORIZE ENGINEERING | | | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME | | | AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND | | | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. PHOTO-COPY SEAL, AND SIGNATURES | | | ARE NOT ACCEPTABLE. | | | | | | 2)WPB AMENDMENTS 106.1.3* ONLY THE ENGINEER OF RECORD | | | CAN ADD INFORMATION TO THE DRAWINGS. NO WHITE-OUT, PEN | | | OR PENCIL HANDWRITING IS ALLOWED ON THE DRAWINGS. THE | | | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL | | | POLICY, STANDARDS FOR PLANS AND SPECIFICATIONS IN ORDER | | | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. | | | SOME OF THE INFORMATION ON THE SUBMITTAL IS ILLEGIBLE. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION AND NATURE OF THE WORK | | | PROPOSED. | | | | | | 3)INDICATE HOW THE 2X8 WILL BE ATTACHED TO THE | | | EXISTING CONCRETE BLOCK WALL. PROVIDE AN ELEVATION | | | DETAIL DRAWING OF THE EACH WALL WHERE THE SUPPORT ANGLE | | | HAS TO BE INSTALLED, INCLUDING THE FULL HEIGHT OF THE | | | WALL. ADDITIONAL INFORMATION IS REQUIRED 106.1.2* | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-01-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-12 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-12 |
Time |
05:54 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-07 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-07 |
Time |
16:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-10-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-13 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-13 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2007-10-13 12:33:38 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07090539 | | | ADD: 5601 CORPORATE WAY SUITE 200-204 | | | CONT: CLAY KOHLMEYER GEN. CONT, INC | | | TEL: (561)694-1214 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | 10/13/07 | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS & | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO | | | THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR | | | IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED | | | AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION | | | DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS | | | OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 2)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE | | | DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE | | | 2006 AMENDMENTS. | | | | | | 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | | THAT IS REQUIRED FOR RECORD KEEPING. | | | A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS | | | DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | | PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | | . ------------------------------------- | | | ) NUMBER OF FLOORS | | | ) SQ. FT. FOOTPRINT | | | | | | 5)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION; | | | PROVIDE INFORMATION BASED ON INTERIOR FINISH | | | REQUIREMENTS BASED ON OCCUPANCY. | | | 6)SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE | | | MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE | | | FINISH FLOOR. 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST | | | 27" HIGH 30" WIDE, AND 19" DEEP SHALL BE PROVIDED | | | UNDERNEATH SINKS. CLEAR FLOOR SPACE 11-4.24.5. A CLEAR | | | FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES (760 MM BY | | | 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE | | | PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD APPROACH. | | | THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE | | | AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) | | | UNDERNEATH THE SINK. NO DOORS IN THIS AREA. | | | | | | 7)FBC 11-7.2 (2) (I)SUBMIT A FRONT ELEVATION DETAIL | | | DRAWING WITH DIMENSIONS SHOWING THAT A PORTION OF THE | | | MAIN COUNTER IS A MINIMUM 36 INCHES IN LENGTH AND A | | | MAXIMUM HEIGHT OF 36 INCHES. | | | | | | 8)INDICATE BY CIRCLING OR HI-LIGHT WHICH TYPE OF | | | WINDOW WILL BE USED FROM THE PRODUCT APPROVAL PACKAGE. | | | ON THE DRAWINGS, SUBMIT AN ELEVATION SECTION ON THE NEW | | | WINDOW INDICATING THE SIZE OF THE WINDOW WITH THE | | | DESIGN PRESSURE, ALSO MARK THE PAGES OF THE PRODUCT | | | APPROVAL IN REFERENCE TO THE INSTALLATION OF THE | | | WINDOW. | | | | | | NOTE:ADDITIONAL NOTES MAY APPEAR ON NEXT REVIEW | | | ACCORDING THE RESPONSE. | | | | | | MYRON JACOBS | | | BUILDING PLANS REVIEWER | | | (561) 805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-08 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-08 |
Time |
14:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-04 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-04 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2007-12-04 11:50:27 | ** DENIED 2NDREVIEW ** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE | | | STILL IN NEED OF ADDRESSING | | | | | | 1) NOTE: PLEASE SEE NO MAXIMUM TIMES FOR OCCUPANCY TYPE | | | DEVICES NOTED. | | | 13-415.1.ABC.1.2. | | | PLEASE KNOW THE MAXIMUM TIME OF 30MINS COULD HAVE BEEN | | | REDLINED HOWEVER THE COMMENT NUMBER TWO NEEDS TO BE | | | ADDRESSED. THIS INFORMATION CAN BE ADDED AS PLANS NEED | | | CORRECTIONS. | | | | | | 2) NOTE: PLEASE SEE THE ELECTRICAL PANEL IS STILL BEING | | | SHOWN IN THE STORAGE ROOM WHICH IS NOT PERMITTED. | | | PLEASE SEE RESPONSE MENTIONS ROOM WAS NOT LABELED | | | CORRECTLY HOWEVER PLANS HAVE NOT CHANGED. PLEASE SEE | | | POWER ON E-2. | | | PLEASE SEE 408.7, 110.26, AND 240.24 AS THIS IS A FIRE | | | AND LIFE SAFETY ISSUE. | | | PLEASE RELOCATE PANEL. | | | IF ROOM IS AN ELECTRICAL ROOM, NOTES FOR SIGNS FOR NO | | | STORAGE ON DOOR, ETC WILL BE REQUIRED. | | | | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-10-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-14 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-14 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2007-10-14 15:06:18 | ** DENIED** | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | | | | 2) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL | | | PANEL IS NOT PERMITTED IN THE STORAGE ROOM. THIS IS A | | | LIFE SAFETY AND FIRE HAZARD AND EVEN THOUGH THIS IS | | | BEING SHOWN AS EXISTING, THIS WILL BE REQUIRED TO BE | | | ADDRESSED AT THIS TIME. | | | PLEASE SEE 240.24D, 408.17, 110.26 ETC | | | | | | 3) NOTE: PLEASE PROVIDE MAXIMUM LIGHTING DENSITIES PER | | | 13-415.2 FOR NEW AREAS/NEW LIGHTING. | | | PLEASE SEE TABLE B. | | | PLEASE ALSO SEE THAT AN *NEW* LIGHTING CONTROLS BEING | | | INSTALLED MUST MEET 13-415.1.ABC.1.1, .1.2. THIS IS | | | ONLY FOR NEW DEVICES. 13-101 | | | PLEASE SPECIFY THE MAXIMUM TIMES FOR DEVICE(S) CHOSEN. | | | | | | 4) NOTE: PLEASE CLARIFY PLANS AS NOW RISER INDICATES | | | TWO METERS AND MAIN DISCONNECTS TO A SINGLE TENANT. | | | PLEASE BE AWARE OF A SINGLE OCCUPANCY WITH ONLY ONE | | | METER PER BUILDING AND ZONING. (METER MAY BE REQUIRED | | | TO BE CHANGED OUT TO A SINGLE METER.) | | | ** THIS IS ONLY NOTED AS THIS COULD AFFECT EXISTING | | | RISER AS SHOWN. | | | ** LABEL ALL MAINS/DISCONNECTS | | | | | | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL | | | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL | | | PLANS. | | | | | | ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR | | | REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL | | | BE NEW COMMENTS ON THE FOLLOWING REVIEW. | | | NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS | | | SUBMITTED. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-11 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-11 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2008-01-11 11:36:09 | *****APPROVED***** | | | | | | PLAN SHEETS A-1 AND E-1 WERE STAMPED, INITIALED, AND | | | DATED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEWER | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-18 |
Time |
22:37 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-18 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2007-12-18 23:27:48 | *****PROVISO***** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;THE APPROPIATE PLAN SHEET(S) TO BE | | | FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN | | | SATISFIED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEWER | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-10-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2007-10-22 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2007-10-22 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2007-10-22 11:42:50 | 1. ONLY ONE EXIT SIGN DISPLAYED FOR NEW EXPANSION AREA | | | ON PAGE E-1. ADDITIONAL EXIT SIGNS ARE NEEDED OR TO BE | | | SHOWN IF EXISTING. | | | | | | 2. PLEASE ILLUSTRATE ANY PORTABLE FIRE EXTINGUISHING | | | EQUIPMENT LOCATED IN THE NEW OR EXISTING REVISED | | | AREAS. | | | | | | 3. PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR | | | WALLS AND CEILINGS. | | | | | | 4. DEMOLITION, CONSTRUCTION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 6. DEMOLITION OR CONSTRUCTION ACTIVITIES SHALL NOT | | | INTERFERE WITH ANY EXITING. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | 804-4709 PHONE | | | 804-4774 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-04-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-15 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-15 |
Time |
16:32 |
Sent To |
B |
|
| Notes |
| 2008-04-15 16:32:37 | TO "MJACOBS" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-04-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-02 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-02 |
Time |
09:56 |
Sent To |
B |
|
| Notes |
| 2008-04-02 09:56:57 | TO "MJACOBS" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-08 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-08 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2008-01-08 12:15:10 | TO "COMM" BD#13 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-21 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-21 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2007-11-30 13:56:10 | TO "COMM" BD#61 | | 2007-11-21 12:48:52 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-11 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-19 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2007-10-12 16:13:14 | TO "COMM" BD#2 | | 2007-09-19 10:40:49 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2007-12-06 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-12-06 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-12-06 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-11-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-11 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-10 |
Time |
15:45 |
Sent To |
PC |
|
| Notes |
| 2007-11-11 09:44:16 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NO LEVEL OF ALTERATION HAS BEEN DECLARED ON PLANS. | | | THE DESIGN PROFESSIONAL MUST ELECT ONE OR A COMBINATION | | | OF LEVELS OF ALTERATION PURSUANT TO SECTIONS 303, 304 | | | AND 305 OF THIS CODE. SEE FBC,EB 301.5. | | | | | | 2. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS THERE IS | | | RECONFIGURATION OF SPACES SHOWN ON PLANS. IN LEVEL 2 | | | ALTERATIONS, RECONFIGURED SPACES INTENDED FOR OCCUPANCY | | | SHALL BE PROVIDED WITH MECHANICAL VENTILATION OR | | | EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, | | | MECHANICAL IN ACCORDANCE WITH FBC,EB 609.1. SHOW | | | OUTSIDE AIR CALCULATIONS BASED ON OCCUPANCY | | | CLASSIFICATION, OCCUPANT LOADS AND VENTILATION RATES AS | | | REQUIRED BY FBC,M TABLE 403.3. BE SURE TO INCLUDE | | | RESTROOM EXHAUST. | | | | | | 3. ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY | | | WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA | | | BUILDING CODE, BUILDING IN ACCORDANCE WITH FBC,EB | | | 611.1. BASIC PRESCRIPTIVE REQUIREMENTS SHALL BE MET FOR | | | ALL BUILDINGS WITH REGARD TO NEW COMPONENTS BEING | | | INSTALLED OR COMPONENTS BEING RETROFITTED (SUCH AS | | | LIGHTING, NEW WINDOW AND NEW DUCTS) IN ACCORDANCE WITH | | | FBC 13-400.1. PROVIDE DOCUMENTATION AND SUFFICIENT | | | NOTATION ON PLAN TO DEMONSTRATE COMPLIANCE WITH THESE | | | SECTIONS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|