Plan Review Details - Permit 07090539
Plan Review Stops For Permit 07090539
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-17 Cont ID  
Sent By mjacobs Date 2008-04-17 Time 15:19 Rev Time 0.00
Received By mjacobs Date 2008-04-17 Time 14:16 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-08 Cont ID  
Sent By mjacobs Date 2008-04-08 Time 07:10 Rev Time 0.00
Received By mjacobs Date 2008-04-07 Time 15:38 Sent To PC
Notes
2008-04-08 07:10:05BUILDING PLAN REVIEW
 PERMIT: 07090539
 ADD: 5601 CORPORATE WAY #200
 CONT: CLAY KOHLMEYER GEN. CONTR INC.
 TEL: (561)694-1214
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 1)ALL PLANS AND SPECIFICATIONS SUBMITTED BY AN
 ENGINEER BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 ORIGINAL SEAL, SIGNATURE AND DATE ON SUCH INFORMATION.
 IF PRACTICING THROUGH A DULY AUTHORIZE ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. PHOTO-COPY SEAL, AND SIGNATURES
 ARE NOT ACCEPTABLE.
  
 2)WPB AMENDMENTS 106.1.3* ONLY THE ENGINEER OF RECORD
 CAN ADD INFORMATION TO THE DRAWINGS. NO WHITE-OUT, PEN
 OR PENCIL HANDWRITING IS ALLOWED ON THE DRAWINGS. THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS AND SPECIFICATIONS IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 SOME OF THE INFORMATION ON THE SUBMITTAL IS ILLEGIBLE.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION AND NATURE OF THE WORK
 PROPOSED.
  
 3)INDICATE HOW THE 2X8 WILL BE ATTACHED TO THE
 EXISTING CONCRETE BLOCK WALL. PROVIDE AN ELEVATION
 DETAIL DRAWING OF THE EACH WALL WHERE THE SUPPORT ANGLE
 HAS TO BE INSTALLED, INCLUDING THE FULL HEIGHT OF THE
 WALL. ADDITIONAL INFORMATION IS REQUIRED 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-12 Cont ID  
Sent By mjacobs Date 2008-01-12 Time 06:35 Rev Time 0.00
Received By mjacobs Date 2008-01-12 Time 05:54 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-12-07 Cont ID  
Sent By mjacobs Date 2007-12-07 Time 18:58 Rev Time 0.00
Received By mjacobs Date 2007-12-07 Time 16:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-13 Cont ID  
Sent By mjacobs Date 2007-10-13 Time 12:33 Rev Time 0.00
Received By mjacobs Date 2007-10-13 Time 09:41 Sent To  
Notes
2007-10-13 12:33:38 
 BUILDING PLAN REVIEW
 PERMIT: 07090539
 ADD: 5601 CORPORATE WAY SUITE 200-204
 CONT: CLAY KOHLMEYER GEN. CONT, INC
 TEL: (561)694-1214
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 10/13/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL BE
 DESIGNED TO THE 2004 FLORIDA BUILDING CODE WITH THE
 2006 AMENDMENTS.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING.
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 . -------------------------------------
 ) NUMBER OF FLOORS
 ) SQ. FT. FOOTPRINT
  
 5)TABLE 803.3 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
 6)SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR. 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST
 27" HIGH 30" WIDE, AND 19" DEEP SHALL BE PROVIDED
 UNDERNEATH SINKS. CLEAR FLOOR SPACE 11-4.24.5. A CLEAR
 FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK. NO DOORS IN THIS AREA.
  
 7)FBC 11-7.2 (2) (I)SUBMIT A FRONT ELEVATION DETAIL
 DRAWING WITH DIMENSIONS SHOWING THAT A PORTION OF THE
 MAIN COUNTER IS A MINIMUM 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES.
  
 8)INDICATE BY CIRCLING OR HI-LIGHT WHICH TYPE OF
 WINDOW WILL BE USED FROM THE PRODUCT APPROVAL PACKAGE.
 ON THE DRAWINGS, SUBMIT AN ELEVATION SECTION ON THE NEW
 WINDOW INDICATING THE SIZE OF THE WINDOW WITH THE
 DESIGN PRESSURE, ALSO MARK THE PAGES OF THE PRODUCT
 APPROVAL IN REFERENCE TO THE INSTALLATION OF THE
 WINDOW.
  
 NOTE:ADDITIONAL NOTES MAY APPEAR ON NEXT REVIEW
 ACCORDING THE RESPONSE.
  
 MYRON JACOBS
 BUILDING PLANS REVIEWER
 (561) 805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-08 Cont ID  
Sent By dpalmer Date 2008-01-08 Time 14:07 Rev Time 0.00
Received By dpalmer Date 2008-01-08 Time 14:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-04 Cont ID  
Sent By dpalmer Date 2007-12-04 Time 11:50 Rev Time 0.00
Received By dpalmer Date 2007-12-04 Time 11:50 Sent To  
Notes
2007-12-04 11:50:27** DENIED 2NDREVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING
  
 1) NOTE: PLEASE SEE NO MAXIMUM TIMES FOR OCCUPANCY TYPE
 DEVICES NOTED.
 13-415.1.ABC.1.2.
 PLEASE KNOW THE MAXIMUM TIME OF 30MINS COULD HAVE BEEN
 REDLINED HOWEVER THE COMMENT NUMBER TWO NEEDS TO BE
 ADDRESSED. THIS INFORMATION CAN BE ADDED AS PLANS NEED
 CORRECTIONS.
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PANEL IS STILL BEING
 SHOWN IN THE STORAGE ROOM WHICH IS NOT PERMITTED.
 PLEASE SEE RESPONSE MENTIONS ROOM WAS NOT LABELED
 CORRECTLY HOWEVER PLANS HAVE NOT CHANGED. PLEASE SEE
 POWER ON E-2.
 PLEASE SEE 408.7, 110.26, AND 240.24 AS THIS IS A FIRE
 AND LIFE SAFETY ISSUE.
 PLEASE RELOCATE PANEL.
 IF ROOM IS AN ELECTRICAL ROOM, NOTES FOR SIGNS FOR NO
 STORAGE ON DOOR, ETC WILL BE REQUIRED.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-10-14 Cont ID  
Sent By dpalmer Date 2007-10-14 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2007-10-14 Time 14:48 Sent To  
Notes
2007-10-14 15:06:18** DENIED**
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE THE LOCATION OF THE ELECTRICAL
 PANEL IS NOT PERMITTED IN THE STORAGE ROOM. THIS IS A
 LIFE SAFETY AND FIRE HAZARD AND EVEN THOUGH THIS IS
 BEING SHOWN AS EXISTING, THIS WILL BE REQUIRED TO BE
 ADDRESSED AT THIS TIME.
 PLEASE SEE 240.24D, 408.17, 110.26 ETC
  
 3) NOTE: PLEASE PROVIDE MAXIMUM LIGHTING DENSITIES PER
 13-415.2 FOR NEW AREAS/NEW LIGHTING.
 PLEASE SEE TABLE B.
 PLEASE ALSO SEE THAT AN *NEW* LIGHTING CONTROLS BEING
 INSTALLED MUST MEET 13-415.1.ABC.1.1, .1.2. THIS IS
 ONLY FOR NEW DEVICES. 13-101
 PLEASE SPECIFY THE MAXIMUM TIMES FOR DEVICE(S) CHOSEN.
  
 4) NOTE: PLEASE CLARIFY PLANS AS NOW RISER INDICATES
 TWO METERS AND MAIN DISCONNECTS TO A SINGLE TENANT.
 PLEASE BE AWARE OF A SINGLE OCCUPANCY WITH ONLY ONE
 METER PER BUILDING AND ZONING. (METER MAY BE REQUIRED
 TO BE CHANGED OUT TO A SINGLE METER.)
 ** THIS IS ONLY NOTED AS THIS COULD AFFECT EXISTING
 RISER AS SHOWN.
 ** LABEL ALL MAINS/DISCONNECTS
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE KNOW AS NOT ALL INFORMATION WAS SUBMITTED FOR
 REVIEW AND DUE TO COMMENTS ABOVE, THERE MAY VERY WELL
 BE NEW COMMENTS ON THE FOLLOWING REVIEW.
 NOTES CAN ONLY BE GIVEN BASED ON PLANS/DOCUMENTS
 SUBMITTED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-01-11 Cont ID  
Sent By mawillia Date 2008-01-11 Time 11:36 Rev Time 0.00
Received By mawillia Date 2008-01-11 Time 11:25 Sent To  
Notes
2008-01-11 11:36:09*****APPROVED*****
  
 PLAN SHEETS A-1 AND E-1 WERE STAMPED, INITIALED, AND
 DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEWER
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-18 Cont ID  
Sent By mawillia Date 2007-12-18 Time 22:37 Rev Time 0.00
Received By mawillia Date 2007-12-18 Time 14:21 Sent To  
Notes
2007-12-18 23:27:48*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;THE APPROPIATE PLAN SHEET(S) TO BE
 FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEWER
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-10-22 Cont ID  
Sent By mcarsill Date 2007-10-22 Time 11:42 Rev Time 0.00
Received By mcarsill Date 2007-10-22 Time 11:26 Sent To  
Notes
2007-10-22 11:42:501. ONLY ONE EXIT SIGN DISPLAYED FOR NEW EXPANSION AREA
 ON PAGE E-1. ADDITIONAL EXIT SIGNS ARE NEEDED OR TO BE
 SHOWN IF EXISTING.
  
 2. PLEASE ILLUSTRATE ANY PORTABLE FIRE EXTINGUISHING
 EQUIPMENT LOCATED IN THE NEW OR EXISTING REVISED
 AREAS.
  
 3. PLEASE DECLARE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 4. DEMOLITION, CONSTRUCTION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 5. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 6. DEMOLITION OR CONSTRUCTION ACTIVITIES SHALL NOT
 INTERFERE WITH ANY EXITING.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-15 Cont ID  
Sent By adarroug Date 2008-04-15 Time 16:32 Rev Time 0.00
Received By adarroug Date 2008-04-15 Time 16:32 Sent To B
Notes
2008-04-15 16:32:37TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 09:56 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 09:56 Sent To B
Notes
2008-04-02 09:56:57TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-08 Cont ID  
Sent By shill Date 2008-01-08 Time 12:14 Rev Time 0.00
Received By shill Date 2008-01-08 Time 12:14 Sent To  
Notes
2008-01-08 12:15:10TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-21 Time 12:48 Rev Time 0.00
Received By adarroug Date 2007-11-21 Time 12:48 Sent To  
Notes
2007-11-30 13:56:10TO "COMM" BD#61
2007-11-21 12:48:52WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-11-21 Cont ID  
Sent By adarroug Date 2007-11-11 Time 12:50 Rev Time 0.00
Received By adarroug Date 2007-09-19 Time 10:40 Sent To  
Notes
2007-10-12 16:13:14TO "COMM" BD#2
2007-09-19 10:40:49WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-12-06 Cont ID  
Sent By rregueir Date 2007-12-06 Time 15:57 Rev Time 0.00
Received By rregueir Date 2007-12-06 Time 15:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-11-11 Cont ID  
Sent By rregueir Date 2007-11-11 Time 09:44 Rev Time 0.00
Received By rregueir Date 2007-11-10 Time 15:45 Sent To PC
Notes
2007-11-11 09:44:16REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO LEVEL OF ALTERATION HAS BEEN DECLARED ON PLANS.
 THE DESIGN PROFESSIONAL MUST ELECT ONE OR A COMBINATION
 OF LEVELS OF ALTERATION PURSUANT TO SECTIONS 303, 304
 AND 305 OF THIS CODE. SEE FBC,EB 301.5.
  
 2. THIS APPEARS TO BE A LEVEL 2 ALTERATION AS THERE IS
 RECONFIGURATION OF SPACES SHOWN ON PLANS. IN LEVEL 2
 ALTERATIONS, RECONFIGURED SPACES INTENDED FOR OCCUPANCY
 SHALL BE PROVIDED WITH MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL IN ACCORDANCE WITH FBC,EB 609.1. SHOW
 OUTSIDE AIR CALCULATIONS BASED ON OCCUPANCY
 CLASSIFICATION, OCCUPANT LOADS AND VENTILATION RATES AS
 REQUIRED BY FBC,M TABLE 403.3. BE SURE TO INCLUDE
 RESTROOM EXHAUST.
  
 3. ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 13 OF THE FLORIDA
 BUILDING CODE, BUILDING IN ACCORDANCE WITH FBC,EB
 611.1. BASIC PRESCRIPTIVE REQUIREMENTS SHALL BE MET FOR
 ALL BUILDINGS WITH REGARD TO NEW COMPONENTS BEING
 INSTALLED OR COMPONENTS BEING RETROFITTED (SUCH AS
 LIGHTING, NEW WINDOW AND NEW DUCTS) IN ACCORDANCE WITH
 FBC 13-400.1. PROVIDE DOCUMENTATION AND SUFFICIENT
 NOTATION ON PLAN TO DEMONSTRATE COMPLIANCE WITH THESE
 SECTIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]