Plan Review Details - Permit 07090501
Plan Review Stops For Permit 07090501
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-21 Cont ID  
Sent By amorse Date 2007-11-21 Time 17:31 Rev Time 0.00
Received By amorse Date 2007-11-21 Time 17:31 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-10-08 Cont ID  
Sent By amorse Date 2007-10-08 Time 17:43 Rev Time 0.00
Received By amorse Date 2007-10-08 Time 17:43 Sent To PC
Notes
2007-10-08 17:44:27 
  
 DENIED
  
 1)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED. ****PLEASE SEE ONE COPY OF ATTACHED COVER
 SHEETS FOR STORM PANELS AND SINGLE HUNG WINDOWS****
  
 2)PRODUCT APPROVALS ARE REQUIRED FOR PGT MULLIONS
 (FL# 261-R3) WHERE TWO OR MORE WINDOW UNITS ARE
 ATTACHED TOGETHER
  
 3)THE NOA FOR THE EXTERIOR DOORS WAS SUBMITTED WITH
 THE INCORRECT DRAWINGS THAT BELONG TO IT PLEASE NOTE
 THAT THE MIAMI-DADE REPORT IS FOR GLAZED DOORS AND THEY
 HAVE NO IMPACT RATING AND WOULD THEREFORE REQUIRE
 SHUTTERS. THE FLORIDA STATEWIDE PRODUCT APPROVAL # FOR
 JELD WEN O/S STEEL DOORS WITH WOOD EDGES IS (FL#
 539-R3) AND THE MIAMI-DADE REPORT # 02-0712.06
  
 4)THE MIAMI-DADE REPORT FOR THE STORM PANELS HAS ALSO
 BEEN REVISED SEE THE ATTACHED UPDATED REPORT, PLEASE
 NOTE THAT THE ANCHOR SPACINGS ARE THE SAME.
  
 5)SHUTTER SPANS ON THE INSTALLATION SCHEDULE ARE
 INCORRECT SPAN = OPENING HEIGHT (IF APPLIED VERTICALLY)
 PLUS 2 X E.D. (7") EG. OPENING # 1
 4'-0' + 7" SPAN = 4'-7" OR 55"
  
 6)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 PLEASE MAKE CORRECTIONS TO PRODUCT APPROVALS AND
 SHUTTER INSTALLATION SCHEDULE AND RESUBMIT
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-02 Cont ID  
Sent By btrobaug Date 2007-11-02 Time 13:14 Rev Time 0.00
Received By btrobaug Date 2007-11-02 Time 12:54 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-26 Cont ID  
Sent By btrobaug Date 2007-09-26 Time 15:36 Rev Time 0.00
Received By btrobaug Date 2007-09-26 Time 13:47 Sent To M
Notes
2007-09-26 15:36:17 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING
 CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC
 AS
 AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. DECLARE SAME ON THE PLAN.
  
 3} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. LOCATE ON THE PLAN
 TO INDICATE COMPLIANCE.
  
 5} REGARDING THE AHU IN THE BATHROOM PER 240.24(E) IN
 DWELLING UNITS AND GUEST ROOMS OR GUEST SUITES OF
 HOTELS AND MOTELS, OVERCURRENT DEVICES, OTHER THAN
 SUPPLEMENTARY OVERCURRENT PROTECTION, SHALL NOT BE
 LOCATED IN BATHROOMS.
  
 6} LOCATE THE CONDENSING UNIT ON THE PLAN. ALSO SHOW
 COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14,
 RECEPTACLE PER 210.63. ALSO NOTE ZONING WILL NEED TO
 SEE THE LOCATION FOR SETBACK REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-03-21 Time 16:48 Rev Time 0.00
Received By adarroug Date 2008-03-21 Time 16:48 Sent To M
Notes
2008-03-21 16:48:23TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-21 Cont ID  
Sent By mmiller Date 2007-12-21 Time 16:31 Rev Time 0.00
Received By mmiller Date 2007-12-21 Time 16:31 Sent To M
Notes
2007-12-21 16:31:48SENT TO TOM GORDON'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-06 Cont ID  
Sent By adarroug Date 2007-12-06 Time 11:21 Rev Time 0.00
Received By adarroug Date 2007-12-06 Time 11:21 Sent To Z
Notes
2007-12-06 11:21:52TO "CHOOPS" DESK/RESUB--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-29 Cont ID  
Sent By adarroug Date 2007-10-29 Time 16:52 Rev Time 0.00
Received By adarroug Date 2007-10-29 Time 16:52 Sent To E
Notes
2007-11-28 11:22:02 
 ***EXPEDITED REVIEW. WPB HCD HOUSING***
 ***REHAB PROGRAM. 11/28/07. RB ***
2007-10-29 16:53:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-10-08 Time   Rev Time 0.00
Received By adarroug Date 2007-09-19 Time 09:23 Sent To  
Notes
2007-09-19 09:28:40TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-24 Cont ID  
Sent By tgordon Date 2008-03-24 Time 11:46 Rev Time 0.30
Received By tgordon Date 2008-03-24 Time 11:46 Sent To  
Notes
2008-03-24 11:47:00REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-28 Cont ID  
Sent By tgordon Date 2007-12-28 Time 13:35 Rev Time 0.40
Received By tgordon Date 2007-12-28 Time 13:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-12-07 Cont ID  
Sent By tgordon Date 2007-12-07 Time 08:26 Rev Time 0.30
Received By tgordon Date 2007-12-07 Time 08:26 Sent To  
Notes
2007-12-07 08:32:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE THREE TON A/C SYSTEM IS TO LARGE. COOLING LOAD
 CALCULATIONS ARE CALLING FOR 25,086 TOTAL COOLING
 BTU'S. MECHANICAL PLANS ARE SHOWING 33,600 TOTAL
 COOLING BTU'S. THE PLANS CAN ONLY CALL FOR 15% MORE
 BTU'S. THAN THE COOLING LOAD CAL'S., SEE 2004 FBC
 13-607.1.ABC.1.1. A 2.5 TON SYSTEM MAY MEET YOUR NEEDS,
 SEE ATTACHED ARI CERTIFICATE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-02 Cont ID  
Sent By tgordon Date 2007-11-02 Time 15:37 Rev Time 0.30
Received By tgordon Date 2007-11-02 Time 15:37 Sent To P
Notes
2007-11-02 15:48:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATION ARE SHOWING THE UNDER AIR
 AREA AS 918 SQUARE FEET AND THE CEILING HEIGHT AS 10
 FEET, THE BUILDING PLANS STATE THE UNDER AIR AREA AS
 828 SQUARE FEET AND THE CEILING HEIGHT AS 8 FOOT 4
 INCHES. PLEASE CORRECT THE COOLING LOAD CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-27 Cont ID  
Sent By tgordon Date 2007-09-27 Time 11:15 Rev Time 0.30
Received By tgordon Date 2007-09-27 Time 11:15 Sent To P
Notes
2007-09-27 11:30:10PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE
 FBC 13-600.3.A. OR YOU MAY SUBMIT FORM 600C-04R, SEE
 2004 FBC 13-101.2.3.
  
 2) ENERGY CALCULATIONS LINE #1 SHOWS CONSTRUCTION AS
 ADDITION, PLEASE CORRECT TO EXISTING OR RENOVATION, SEE
 FBC 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS LINE 11A SHOWS THE SUPPLY AIR
 DUCTS ARE IN A CONDITIONED SPACE, MECHANICAL PLANS SHOW
 THE SUPPLY AIR DUCTS TO BE IN ATTIC, PLEASE CORRECT
 ENERGY CAL'S.
  
 4) COOLING LOAD CALCULATIONS (MANUAL J) ARE CALLING FOR
 25,559 TOTAL BTU'S, THE A/C SYSTEM BEING INSTALLED ON
 THE MECHANICAL PLAN IS 33,600 TOTAL BTU'S. THE PLANS
 CAN ONLY CALL FOR 15% MORE TOTAL BTU'S THAN THE COOLING
 LOAD CAL'S, SEE FBC 13-607.1.ABC.1.1. (SEE ATTACHED ARI
 LISTING, PERHAPS A 2.5 TON SYSTEM WOULD MEET THE
 REQUIREMENTS). PLEASE CORRECT.
  
 5) THE MECHANICAL PLANS NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND
 CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE
 W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-17 Cont ID  
Sent By jleech Date 2007-11-17 Time 13:39 Rev Time 0.00
Received By jleech Date 2007-11-17 Time 13:32 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-10-03 Cont ID  
Sent By jleech Date 2007-10-03 Time 10:47 Rev Time 0.00
Received By jleech Date 2007-10-03 Time 10:44 Sent To B
Notes
2007-10-03 10:49:27DENIED;
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPON-
 SIBLE FOR THE DESIGN. SECTION 104.2.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-12-06 Cont ID  
Sent By choops Date 2007-12-06 Time 12:11 Rev Time 0.00
Received By choops Date 2007-12-06 Time 12:11 Sent To M
Notes
2007-12-06 12:12:05***APPROVED - RESUB #2 - (ZONING 2ND REVIEW)***
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 1 Status F Date 2007-11-02 Cont ID  
Sent By choops Date 2007-11-02 Time 14:05 Rev Time 0.00
Received By choops Date 2007-11-02 Time 14:05 Sent To M
Notes
2007-11-02 14:08:03***FAILED - RESUB #1 (ZONING 1ST REVIEW)***
  
  
 1)PLEASE PROVIDE TWO COPIES OF A CURRENT SURVEY
 SHOWING THE LOCATION OF THE PROPOSED A/C UNIT WITH
 SETBACK DIMENSIONS TO ALL PROPERTY LINES.NOTE:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4' INTO
 A REQUIRED SETBACK.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720